Search:

Type: Posts; User: interop

Search: Search took 0.00 seconds.

  1. Replies
    1
    Views
    643

    never mind - I just found out that DSC out of the...

    never mind - I just found out that DSC out of the box doesn't have any IP address - it needs to be assigned by ORCaVIEW software.
    And then you can talk to the box.
  2. Replies
    1
    Views
    643

    New Delta DSC 1616 default IP address

    Hello,
    I've got a new Delta DSC 1616 and try to connect to it. But I can't find anywhere information what is the factory configured default ip address. please somebody tell me or point to...
  3. Unfortunately I grew up without watching Bugs...

    Unfortunately I grew up without watching Bugs Bunny (I am from Russia) so your joke got lost on me :putergreet:

    Well let me know if you decipher this puzzle - if I do I will post it here.
  4. :) Good results - but how about your previous...

    :) Good results - but how about your previous panel?

    "On my sample panel, the System Profile report shows 247 points, and the Panel Point Log shows 251. I've played around with the...
  5. Hehs - I am curious too. I thought maybe the...

    Hehs - I am curious too. I thought maybe the difference is that one report shows all the points from TECs even the ones which were not unbundled. Or that one report counts points like L2SL as two....
  6. System Profile has the following data: Field...

    System Profile has the following data:

    Field Panel

    Description
    Device instance
    ------
    Logical Ponts:

    so the number of Logical points doesn't...
  7. Siemens Insight System Profile and Panel Point definition reports

    Hello everyone,

    I run a system profile report in my Siemens workstation and it gives me a count for logical points in MEC or MBC panel. Then I run Panel Point definition report on the same panel...
  8. Energy monitoring dashboards - what would you use them for?

    I am thinking of developing dashboard or buy existing one for our energy metering products and I was thinking about the different ways they can be used - different requirements from the users.

    So...
  9. Replies
    0
    Views
    779

    Siemens Insight workstation error message

    I have one Insight Server and two Insight Clients. Once in a while all connections to BLN panels are lost and I get an error message trying to access any BLN or system panel:

    "There are no more...
  10. Replies
    37
    Views
    13,586

    Thank you ntech64 - it was very useful...

    Thank you ntech64 - it was very useful information!!
  11. Replies
    37
    Views
    13,586

    So PXC modular and PXC compact both have network...

    So PXC modular and PXC compact both have network layer? Because Siemens states for PXC compact that it "Features Ethernet/IP and BACnet/IP options"...
  12. Thank you ntech64 - it was very helpful!

    Thank you ntech64 - it was very helpful!
  13. Replies
    37
    Views
    13,586

    Can PXC work with a router to communicate with...

    Can PXC work with a router to communicate with MSTP devices on another network or it only can function on the same network and needs some kind of proxy in order to talk to the devices on another...
  14. Siemens PXC application BACnet and node addresses

    Need a help in Siemens addressing department. Our customers has MSTP/BACNet PXC which tries to communicate to third party IP BACnet server thru the router (MSTP BACnet to IP BACNet router).
    They...
  15. Replies
    5
    Views
    3,237

    Thank you Dave - I found it - that's what I...

    Thank you Dave - I found it - that's what I needed!
  16. Replies
    5
    Views
    3,237

    Tridium Jace as a BACnet client

    I have a Tridium Jace box I want to use for monitoring third party BACnet devices. I read in Tridium documentation that "As a standard feature, JACE’s support BACnet IP client to enable them to...
  17. Thread: ENE systems

    by interop
    Replies
    6
    Views
    547

    I don't know about TENE. Here it is. ...

    I don't know about TENE.

    Here it is.

    http://www.enesystems.com/

    I couldn't find any docs on their workstation and was wondering what performance diagnostics tools it might have - for...
  18. Thread: ENE systems

    by interop
    Replies
    6
    Views
    547

    Yes - please move

    Yes - please move
  19. Thread: ENE systems

    by interop
    Replies
    6
    Views
    547

    ENE systems

    Does anyone knows about ENE systems? If it has a performance or diagnostic tools for underlying control systems.
  20. Siemens Controlotron 1010 flow meter modbus card problem

    Our customers have Siemens Controlotron 1010 flow meter with 1015N modbus card. I configured the card according to manual but can only read first 6 registers.

    I set Datalogger Mode to RS-232...
  21. Replies
    18
    Views
    1,938

    Do you have this manual - I couldn't locate it? ...

    Do you have this manual - I couldn't locate it?

    I also curious how many BACnet point BCU can safely hold?

    Also when I do BCU diagnostics report it gives me an information about %% of memory...
  22. Replies
    0
    Views
    856

    Danfoss ADAPKOOL AKC255 TCP protocol

    I need help with Danfoss TCP protocol. We are trying to read setpoints from AKC255 system remotely - the site has AK2-SC 255 system controller. And I can't find the specs for the protocol Danfoss...
  23. Replies
    1
    Views
    743

    Tridium Staefa system

    I have a Tridium Staefa syste with Talon managers and NCRSs. I want to generate a spreadsheet with a list of points from all controllers system. I saw online sample format:

    Information from...
  24. nope. I can see the non-Alerton devices but not...

    nope.
    I can see the non-Alerton devices but not their objects and properties in Envision.
  25. Replies
    1
    Views
    441

    Where do I configure PTP network number for my...

    Where do I configure PTP network number for my BCU?
  26. Replies
    7
    Views
    1,293

    Thank you for advices - I found a problem, I had...

    Thank you for advices - I found a problem, I had another protocol on it which conflicted with Trane

    Thanks
  27. I have Alerton Envision V.1.0/1.2. I have non...

    I have Alerton Envision V.1.0/1.2. I have non Alerton BACnet devices connected to BACnet/Ip network and I can see them in Device manager.

    Is it possible to see also objects and their properties of...
  28. Replies
    7
    Views
    1,293

    I installed it on two machines. The minute I...

    I installed it on two machines. The minute I configure site BACnet/IP BBMD or without BBMD and click Save it gives me an error "Unable to bind socket" and then it crashes.
  29. Replies
    7
    Views
    1,293

    I have Win 2000 with Service pack 4 and Summit is...

    I have Win 2000 with Service pack 4 and Summit is 13.10 version
  30. Replies
    7
    Views
    1,293

    I have a demo version of Tracer Summit V.13 and...

    I have a demo version of Tracer Summit V.13 and when I configure the site it starts crashing. It says on startup - Unable to bind the socket and in Event Viwere it says it is looking for a ARPCROT...
  31. Thread: tracer summit

    by interop
    Replies
    13
    Views
    1,878

    I found an answer for my questions about...

    I found an answer for my questions about LON/BACnet in forum topics
  32. Thread: tracer summit

    by interop
    Replies
    13
    Views
    1,878

    I would like to generate report and see points...

    I would like to generate report and see points online without going into workstation plus security.

    I am qurious - why LON=good and BACnet=bad?
  33. Thread: tracer summit

    by interop
    Replies
    13
    Views
    1,878

    I looked at Trane website and didn't find any...

    I looked at Trane website and didn't find any information about v17 new features. What is the difference with v16?

    Does BCU v17 have a web interface or I still need WebOPC in order to access BCUs...