Search:
Type: Posts; User: the007
Search: Search took 0.01 seconds.
-
12-07-2010, 09:51 PM
Thread: Nxgen is failure of JCI
by the007- Replies
- 7
- Views
- 976
wow!! guess jork has really gone downhill, glad i...
wow!! guess jork has really gone downhill, glad i left 4 years ago. so nice now to take about 5 mins at the end of the day, hit one button and be done. fire up the laptop, check email, and my...
-
04-14-2010, 03:28 PM
Thread: Mc Quay Chiller with Turbocor
by the007- Replies
- 16
- Views
- 2,159
don't let the metasys control it.....the only...
don't let the metasys control it.....the only thing that controls is the price of the BAS contract which has no high limit cutout on it!!! one of the mcquays i have in nashville on metasys has only...
-
03-03-2009, 12:25 AM
Thread: Shaft seal forensic diagnosis
by the007- Replies
- 4
- Views
- 472
if ever replacing that seal again, would highly...
if ever replacing that seal again, would highly recommend some dow 111 on them o-rings....keeps the rigor mortis out for a while. and the seal pressure, well, i would recommend at least 4 psig at...
-
03-02-2009, 11:56 PM
Thread: York YTG Centrifugal
by the007- Replies
- 37
- Views
- 2,820
just isolate the purge, cut it off and install a...
just isolate the purge, cut it off and install a trane purifier purge.....simple. i've installed too many purifiers behind the redi's and won't even present that as an option to my customers anymore....
-
01-28-2009, 05:08 PM
Thread: How good is yours?
by the007- Replies
- 13
- Views
- 893
they are all great when they're running and you...
they are all great when they're running and you do an inspection and they are all even better when they crash and the customer says just get it running!! oh, and how good is this, there is a york ot...
-
01-14-2009, 09:53 AM
Thread: Why ammonia refrigeration system
by the007- Replies
- 6
- Views
- 591
ammonia is very efficient but very hard to work...
ammonia is very efficient but very hard to work with. can't use any copper otherwise it eats it up. it is very good for low temp applications i.e. dry ice manufacturing. if it gets on you, yes it...
-
01-03-2009, 12:43 PM
Thread: VFD YT's and bellows seals
by the007- Replies
- 8
- Views
- 425
on the YT's it doesn't matter how many hertz the...
on the YT's it doesn't matter how many hertz the machine is running at to set oil pressure on the seal, they gots the oil press reg valve on 'em. i know the factory is going to recommend some high...
-
12-29-2008, 03:54 PM
Thread: York ys chiller steel tubing pinholes
by the007- Replies
- 12
- Views
- 1,234
i would have a weld-o-let put on and run all the...
i would have a weld-o-let put on and run all the lines in copper. got at least a dozen of these machines and all but 3 are copper. well, they will be eventually. just run the lines slightly larger...
-
12-29-2008, 03:47 PM
Thread: Carrier 19DK Chiller problem
by the007- Replies
- 45
- Views
- 2,674
i wouldn't want to be the person who gave you the...
i wouldn't want to be the person who gave you the professional status and read that one.:eek:
-
11-23-2008, 10:59 AM
Thread: YT Style J liq level control valve?
by the007- Replies
- 29
- Views
- 1,285
just a wild guess here, but i would look at the...
just a wild guess here, but i would look at the actual valve here.....had to have replaced 5 of them over the years on yt's...not yk's. different valves with seals and yes the rubber seal in the...
-
11-23-2008, 10:51 AM
Thread: 19FA Carrier chiller
by the007- Replies
- 15
- Views
- 2,281
mikey...how did you get to be a professional...
mikey...how did you get to be a professional member? you're rses do that? scary thought....hehehe!! find a manual yet?
-
11-11-2008, 10:17 PM
Thread: 19FA Carrier chiller
by the007- Replies
- 15
- Views
- 2,281
yo mikey......the only thing i think that needs...
yo mikey......the only thing i think that needs attention is the transmission outside the ea/eb teardown goodies. better get some plastigage to reassemble it there bigga boy! hehe! remember the...
-
11-11-2008, 10:09 PM
Thread: York ZB6W Oil pump drive problem.
by the007- Replies
- 22
- Views
- 2,087
ahhhh, the glorious Z compressors.....good luck...
ahhhh, the glorious Z compressors.....good luck with the oil pump. york, when they went from the J to the Z, they used the same oil pump but forgot to re-engineer just what you found...the tang not...
-
10-28-2008, 08:43 PM
Thread: HELP!!! CGAC Trane
by the007- Replies
- 21
- Views
- 2,698
3 to peek at...the leaving chilled water sensor...
3 to peek at...the leaving chilled water sensor usually right at barrel, the saturated evap sensor on bottom of evap barrel and the last is suction temp sensor in the suction line just a foot or two...
-
10-28-2008, 08:23 PM
Thread: Proximity Probe?
by the007- Replies
- 5
- Views
- 682
personally, i would recalibrate it and check the...
personally, i would recalibrate it and check the new position against the reference position noted from the factory. if it is really close to the minimum of 35 mils, i would pull the charge and check...
-
10-19-2008, 03:53 PM
Thread: are YORK techs bailing?
by the007- Replies
- 208
- Views
- 26,581
it's amazing to see the turnabout with Jork. 18...
it's amazing to see the turnabout with Jork. 18 years ago when i got in, it was very difficult to do so and took alot of work to stay. it was a privilege to service the York chillers. man have times...
-
07-11-2008, 06:06 PM
Thread: different chillers
by the007- Replies
- 10
- Views
- 908
trane rtaa which is 22 or the rtac which is 134a....
trane rtaa which is 22 or the rtac which is 134a. jork air cooled scrolls suck.....and i mean suck. support and service is excellent with trane and good with carrier, but if i had a choice, go with...
-
07-11-2008, 05:51 PM
Thread: York turbo modulator
by the007- Replies
- 11
- Views
- 1,873
last TM 1 i saw was 15 years ago in a hospital...
last TM 1 i saw was 15 years ago in a hospital that replaced all three machines with new one. wish i would've saved parts. anywho.....about the only thing to do is call all the offices and see if...
-
05-22-2008, 02:58 PM
Thread: Chiller (centrifugal) Mechanics
by the007- Replies
- 39
- Views
- 3,135
as a former jork guy, and speaking about the...
as a former jork guy, and speaking about the local branch, i'd rather have......well, i wouldn't recommend them. as a current trane guy, they are very professional and living up to every promise they...
-
05-19-2008, 07:21 PM
Thread: YK Optiview Control Panel Password
by the007- Replies
- 16
- Views
- 2,128
not to get picky here, but feel free to call york...
not to get picky here, but feel free to call york factory and talk to either dave saylor or steve baer (he"s the one who actually designed the board) and see what they say.
-
05-18-2008, 07:42 PM
Thread: Chiller (centrifugal) Mechanics
by the007- Replies
- 39
- Views
- 3,135
i think a lot of the older guys, 55 plus, need to...
i think a lot of the older guys, 55 plus, need to take the younger guys under their wings and train them. at 21, i had two seasoned guys of 60 plus take me and mold me. it was a lot of crap to take,...
-
05-18-2008, 07:16 PM
Thread: YK Optiview Control Panel Password
by the007- Replies
- 16
- Views
- 2,128
you can reset the acc count with that procedure...
you can reset the acc count with that procedure but to clear the map requires an admin code.....trust me, been through that with dave saylor up at york factory many a time. to reset some of the run...
-
05-12-2008, 09:02 PM
Thread: YK Optiview Control Panel Password
by the007- Replies
- 16
- Views
- 2,128
would love to give one out, but what is it needed...
would love to give one out, but what is it needed for? i really don't want to be like the factory, but the only real necessity for it is to clear the acc map, and the problems with that need to de...
-
05-11-2008, 08:41 PM
Thread: YK Optiview Control Panel Password
by the007- Replies
- 16
- Views
- 2,128
Yes, it depends on the date and type of panel,...
Yes, it depends on the date and type of panel, one-line micro or the optiview. Careful with date temporary thingy...it may not work...tried it and sometimes it does and sometimes doesn't, haven't...
-
05-11-2008, 07:26 AM
Thread: union or non union
by the007- Replies
- 41
- Views
- 2,936
as a side note, scale for L.U. 43 here about...
as a side note, scale for L.U. 43 here about $23.50, after I pay my own insurance I am still over $30.
Results 1 to 25 of 152