Search:

Type: Posts; User: HeatXfer

Page 1 of 6 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    6
    Views
    798

    A 4ton air handler will move about 1600cfm;...

    A 4ton air handler will move about 1600cfm; through a 20"x25" filter that's about 460fpm. PD for a new merv 10 is about .23" to .25"wc at approx 480fpm. Typical recommended pd change point is .75"...
  2. Replies
    6
    Views
    798

    Rhino32713: Please don't cut-n-paste Google...

    Rhino32713:

    Please don't cut-n-paste Google searches, it's like that joke about teaching pigs to sing.

    Anyway, the closer a filter is to the fan intake, the cleaner your system will be; less...
  3. Replies
    8
    Views
    1,121

    Did you reboot the JACE? Changes won't take if...

    Did you reboot the JACE? Changes won't take if you don't reboot. Also it might be the DNS. Use the host's IP address or you can set up the JACE with a DNS server.
  4. Where do you live, or want to work? What city &...

    Where do you live, or want to work? What city & state?
  5. Replies
    26
    Views
    2,726

    'Yer cold

    'Yer cold
  6. Replies
    4
    Views
    716

    You can buy a new, warrantied, properly...

    You can buy a new, warrantied, properly engineered Donaldson brand for anywhere from $1500 to $6,000. 'Plug-n-Play'.

    You could probably wing-it, but the minute someone gets sick, and sues you and...
  7. Replies
    134
    Views
    27,161

    "Hello, I'm Rick" probably would have been a...

    "Hello, I'm Rick" probably would have been a better introduction. Plus:

    1)What you do for a living.
    2)State & City where you work?
    3)What your professional experience is.

    Please read THIS
  8. Replies
    4
    Views
    1,062

    Follow Chiller Man's directions. But here's a tip...

    Follow Chiller Man's directions. But here's a tip for the older (mid 90's) chillers: the first 30GXs didn't have O-rings on the oil level sensor fittings and tended to leak there (among other...
  9. Replies
    28
    Views
    3,099

    Brilliant!

    Brilliant!
  10. Replies
    28
    Views
    3,099

    You've just sold me. I'm going to try SG for...

    You've just sold me. I'm going to try SG for everything now.
  11. Replies
    28
    Views
    3,099

    I did a quick search and it looks like your plan...

    I did a quick search and it looks like your plan to use simple green is a good one. I didn't think it would dissolve dried ink, but many people have used it with success.

    I've heard "Gonzo" works...
  12. Replies
    28
    Views
    3,099

    What type of ink? You'll probably need some kind...

    What type of ink? You'll probably need some kind of solvent.

    Nice clean removal BTW
  13. Replies
    7
    Views
    870

    That's very cold, even for a data center. Despite...

    That's very cold, even for a data center. Despite what the IT guys say, the best environment for electronics is a steady 70° - 72°f at about 50% RH. Too cold and you can get condensation forming...
  14. Replies
    12
    Views
    1,661

    What is the nature of the noise? Is it a 'sound',...

    What is the nature of the noise? Is it a 'sound', or is it vibration felt inside the building? Is it a mechanical or an 'air' sound? Is it steady, rythmic, rattling, rumbling, thumping, whooshing,...
  15. Thread: fan law

    by HeatXfer
    Replies
    7
    Views
    750

    Yes to the traverse. Can you see condensation...

    Yes to the traverse. Can you see condensation overflowing the pan and running down the duct, or condensation being pulled off the coil by high air velocity?

    What it is design CFM and what are the...
  16. Replies
    6
    Views
    594

    I can never remember the exact wording of all...

    I can never remember the exact wording of all those alarms, anyway, glad to you got it worked-out.
  17. Replies
    6
    Views
    620

    The software for the touch screen should be on...

    The software for the touch screen should be on the cpu's flashdrive. A quick way into the system without using the touch screen is to get a regular keyboard: with either a usb or the old PS2...
  18. Replies
    6
    Views
    594

    I haven't seen any lit on this either, but if...

    I haven't seen any lit on this either, but if you're familiar with the machine you should be able to discern whether or not you're leaking-by by reading the line pressures at the lube box while you...
  19. Replies
    6
    Views
    620

    Drivers for the Windows CE OS touch screen can be...

    Drivers for the Windows CE OS touch screen can be found here. Or you can get them from McQuay. Is your chiller a new MicroTech II or has it been upgraded with a new MicroTech II control panel with...
  20. Replies
    15
    Views
    2,722

    I don't recommend bypassing the oil level switch;...

    I don't recommend bypassing the oil level switch; if there isn't enough oil to maintain lubrication the damage to an 06N can be catastrophic, and compressor replacement is inevitable. Carrier's...
  21. Replies
    32
    Views
    1,079

    Don't knock it 'till you've tried it! Originally...

    Don't knock it 'till you've tried it! Originally from S.E. Ohio, just down river from Amish country.

    We should really go back to the gold standard, eliminate the Federal Reserve Bank, re-institute...
  22. Replies
    32
    Views
    1,079

    Depends on what you mean by "too bad"

    Depends on what you mean by "too bad"
  23. Replies
    123
    Views
    2,949

    Now these are all verifiable facts without the...

    Now these are all verifiable facts without the rhetoric.
    - Citation needed

    None of the items on my list are rhetorical; he did those things. My statements manipulative? I'm certainly not trying...
  24. Replies
    123
    Views
    2,949

    Opinions and facts...there's an interesting thing...

    Opinions and facts...there's an interesting thing about facts: everyone is entitled to learn them, but many prefer not to let them interfere with their preconceived notion of the world.

    Besides,...
  25. Replies
    123
    Views
    2,949

    "The worst technicians are the brand bashers of...

    "The worst technicians are the brand bashers of the world. Not because they are bad techs, but because they have bad attitudes.
    Professional technicians have no overall problems with any brand and...