Search:

Type: Posts; User: Balibe

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    31
    Views
    961

    Your FXWorkbench should be licensed for...

    Your FXWorkbench should be licensed for everything [all drivers/protocols]. I have never had an issue hooking up directly to lon networks with FXWorkbench and a USB Lon adapter.
  2. Replies
    35
    Views
    2,425

    +1 Getting old seeing this guy resurrecting...

    +1

    Getting old seeing this guy resurrecting all these threads that are over a year old .... each with a PDF attachment??
  3. Thread: Orion Controls

    by Balibe
    Replies
    1
    Views
    188

    http://orioncontrols.wattmaster.com/literature-new...

    http://orioncontrols.wattmaster.com/literature-new.html
  4. Replies
    7
    Views
    288

    Johnson Controls also has a wireless system that...

    Johnson Controls also has a wireless system that works well.
  5. I have one jobsite with this same issue, works...

    I have one jobsite with this same issue, works fine on my Verizon hot spot and all hardwired connections but will not connect with the customers AT&T hot spot. I always thought the issue was with...
  6. Replies
    10
    Views
    408

    I did some research with a v4.2 and v6.0. I will...

    I did some research with a v4.2 and v6.0. I will try to make this easy to understand, but there is no formula/logic (decoder ring) that will easily get you the info you want. You will need to have...
  7. Replies
    10
    Views
    408

    So you are looking at the points on the IP side...

    So you are looking at the points on the IP side of the Router and trying to figure out which VAV the BACnet points are assigned to?

    If so I can look at one of my sites on the IP side to see if...
  8. Replies
    10
    Views
    408

    You wil not see the address under network points...

    You wil not see the address under network points with a factory control program. All point address's under the network points tab will be ccn:\\link\point_info, the "link" can be changed to the...
  9. Replies
    3
    Views
    295

    Snap has a programming block for lead/lag under...

    Snap has a programming block for lead/lag under Misc\Proof. It does rotation based on runtime and failsafe if the lead does not proof. It will also generate fail & hand alarms if needed. If you have...
  10. Replies
    6
    Views
    281

    The 4th digit of the model number is the...

    The 4th digit of the model number is the Development Sequence. F = Sixth & G = Seventh. The breakdown is in one of the PDF's I emailed you.
  11. Replies
    6
    Views
    281

    Model Number: SXHFC6040M56C79D6001BELRT8PK Job...

    Model Number: SXHFC6040M56C79D6001BELRT8PK
    Job Name: Concord Park
    Shipped: 10-16-1997

    The original model number breakdown does not show an LCI. The unit documents only go back so far. I found...
  12. Replies
    6
    Views
    281

    From my understanding is the older panels do not...

    From my understanding is the older panels do not support the LCI. I don't know when the change occurs. Not 100% but think you can replace the panel with a newer version that works with an LCI. That...
  13. Replies
    11
    Views
    592

    When you right click the VAV graphic and edit...

    When you right click the VAV graphic and edit UCM, you are in the UCM. You can use Summit to modify the settings. They are live settings in the UCM versus a local saved database.
  14. Replies
    11
    Views
    592

    UCM address of 1 on the dipswitch will be VAV...

    UCM address of 1 on the dipswitch will be VAV address 65 in Tracer. Address 2 will be 66, etc .....

    There should be a sticker inside one of the VAV's showing the dipswitch address scheme ....
  15. Thread: CCN Issue

    by Balibe
    Replies
    10
    Views
    315

    How are you changing the broadcast acknowledger...

    How are you changing the broadcast acknowledger [BA]?

    These are Gen2 VVT?

    Older Gen2 VVT will not talk CCN without a Gateway. Only Gen3 and up will talk CCN.

    If they have a display and 4...
  16. Replies
    7
    Views
    241

    The controller files are separate. The v1.4 you...

    The controller files are separate. The v1.4 you want will only work with FieldLoader v3.3 or v4.2. If you have NSTV and want to use the USB converter you will need FieldLoader v4.2
  17. Thread: FX PCV

    by Balibe
    Replies
    4
    Views
    248

    The issue with 3113 is it has around a 10,000...

    The issue with 3113 is it has around a 10,000 write limit. Not an issue if only used for balancing.
  18. Thread: Carrier Ivu

    by Balibe
    Replies
    11
    Views
    1,737

    Drac is correct, you will need v4.2 tools. The...

    Drac is correct, you will need v4.2 tools. The program was ApplicationBuilder, not EquipmentBuilder. This issue also applies to View Graphics. The tools were shipped with the i-Vu v4.2 if the...
  19. Replies
    7
    Views
    241

    The current version is 1.4. You will need...

    The current version is 1.4. You will need FieldLoader v3.3 or v4.2 and the translator files. If you don't have a physical com port on the computer you will also need Network Service Tool so...
  20. Replies
    1
    Views
    183

    That is a Comfort Controller 1600, you will need...

    That is a Comfort Controller 1600, you will need Network Service Tool V to access it.
  21. Replies
    8
    Views
    295

    Trane Tracker talks Trane Comm3/Comm4 to the RTU....

    Trane Tracker talks Trane Comm3/Comm4 to the RTU. You will not talk to a Carrier Open RTU. Your only option is to add the RTU card to the Tracker panel. This will allow R,G,Y,W to the RTU.
  22. Replies
    3
    Views
    148

    If the chiller has the CH530 controls you will...

    If the chiller has the CH530 controls you will need Trane's chiller software as the Comm Cards need to be added before you will get data.
  23. Thread: Service tool 5

    by Balibe
    Replies
    7
    Views
    545

    These part numbers are for older NST and...

    These part numbers are for older NST and obsolete. For NSTV the part number is 33CNNSTKIT-01.
  24. Thread: ivu 6 ccn

    by Balibe
    Replies
    4
    Views
    286

    That driver is the original fix in IOB14003, I...

    That driver is the original fix in IOB14003, I would apply that driver. Carrier just released a new fix yesterday [03/18/2014] in IOB14003A. It is the same driver but has another step to the...
  25. Replies
    5
    Views
    405

    Which version are you installing? If v2.0 or...

    Which version are you installing? If v2.0 or v2.1, believe you will need to upgrade to v2.2 for Windows 7. There is an v2.2 update .exe on havcpartners.com. If you have an older usb converter at...