    Sounds like blocked discharge line or supply...

    Sounds like blocked discharge line or supply house gave you wrong voltage replacement? You have checked volts already I assume? Good luck with it!
  2. Replies
    4
    Views
    268

    I was wondering if there were any of those still...

    I was wondering if there were any of those still around working! I too cut my teeth on those and the C models before them. Haven't come across one still working in many years!
  3. Make sure the drain is clear and flowing...

    Make sure the drain is clear and flowing properly, drain line heater (assuming this is a freezer) is installed and functioning. Have seen water left over in drain pan at the end of defrost get kicked...
  4. Replies
    40
    Views
    1,538

    Glad you got it solved! The first one we saw...

    Glad you got it solved! The first one we saw took us several trips over a couple of days to figure out also! I guarantee you'll never forget about it and if you ever see it again you'll go right to...
  5. Replies
    40
    Views
    1,538

    Maybe I'm using the wrong term to describe the...

    Maybe I'm using the wrong term to describe the part I'm referring to.... Refrigeration Research calls it a "subcooling heat exchanger". I've attached a picture... I hope it works...first time posting...
  6. Replies
    40
    Views
    1,538

    Does the system have a heat exchanger installed?...

    Does the system have a heat exchanger installed?

    The more I think about this, the more convinced I am that you probably have a heat exchanger on that system and it is leaking internally, dumping...
  7. Replies
    40
    Views
    1,538

    Is there a heat exchanger mounted in the...

    Is there a heat exchanger mounted in the liquid/suction line? Have seen them leak internally and bleed liquid right into the suction line. Those were fun to diagnose!
  8. Either it is plumbed to a hot water source or hot...

    Either it is plumbed to a hot water source or hot water is migrating over to the cold water side and getting to the machine.
  9. Replies
    48
    Views
    2,413

    Look for oil, look for oil, look for oil!!! This...

    Look for oil, look for oil, look for oil!!! This includes moist looking dirt or dust stuck to some part of the system. Start with a good flashlight and your eyes and brain, spending ample time...
  10. Replies
    13
    Views
    1,303

    Check all switches in the control circuit to the...

    Check all switches in the control circuit to the contactor coil. Usually when we run into this it is either short cycling as already stated, or a problem with a pressure switch where the switch...
  11. Replies
    28
    Views
    3,006

    Yea,thanks!.....I'm glad I made it out of that...

    Yea,thanks!.....I'm glad I made it out of that ordeal ok....I don't know what the concentration of ammonia was by ppm in the room that night, heck I was just a kid at the time! I just know that there...
  12. Replies
    28
    Views
    3,006

    When I was 18 I was working one night in a small...

    When I was 18 I was working one night in a small equipment room on a Vogt P-24 ice machine charged with 800 lbs. of ammonia when there was a sudden release of it's entire charge in liquid form from...
  13. Replies
    7
    Views
    1,336

    I agree.....clean it first....I don't believe too...

    I agree.....clean it first....I don't believe too much in the "dump in cleaner and run the auger a while" type of cleaning. Pull it apart and clean/inspect it. It's not too hard to do. Sure it...
  14. Replies
    14
    Views
    1,802

    Is the water distribution system clean? Make sure...

    Is the water distribution system clean? Make sure evey row of every evap. is getting water flow to make cubes.....Hoshizaki brings in "X" amount of water (enough for one batch of ice) at the...
  15. Replies
    6
    Views
    697

    I'm not sure if this will pertain to your...

    I'm not sure if this will pertain to your problem, but years ago I dealt with a similar problem involving compressor oil loss on a Vogt P-24 ammonia ice maker that caused many sleepless nights and...
  16. Replies
    3
    Views
    1,144

    The Mycoms I am familiar with on Vogt ice...

    The Mycoms I am familiar with on Vogt ice machines use oil pressure to back the unloaders off. When the compressor is off, the unloaders have a spring that keeps them in the unloaded position holding...
  17. Replies
    49
    Views
    2,538

    Ditto that!

    Ditto that!
  18. Replies
    15
    Views
    1,682

    Yea, I'm with you on that....I'm not going to...

    Yea, I'm with you on that....I'm not going to blow up on him over this....he's had a string of needless callbacks recently and needs a stern talking to...maybe if I handle it right he'll get his...
  19. Replies
    49
    Views
    2,538

    If I'm seeing right, it looks like the gasket...

    If I'm seeing right, it looks like the gasket blew out in between the discharge chamber and the suction chamber? I think I saw this once many years ago....couple of questions... where are you taking...
  20. Replies
    15
    Views
    1,682

    We determined yesterday that the drier was...

    We determined yesterday that the drier was definantly at least partially restricted when my guy installed the new compressor. He certainly should've caught that! I'll have to do some more training...
  21. Replies
    15
    Views
    1,682

    Will do.....Thanks!

    Will do.....Thanks!
  22. Replies
    15
    Views
    1,682

    I also doubt they changed the oil. I don't...

    I also doubt they changed the oil. I don't personally know what would happen running 404 with mineral oil? Are cylinder and discharge temps high enough in this scenario to break down the mineral oil...
  23. Replies
    15
    Views
    1,682

    Excellent question! I didn't.....one of my techs...

    Excellent question! I didn't.....one of my techs did.... I would have changed it and he should have changed it....I'll have to thrash him later when I see him! For the record, the drier was...
  24. Replies
    15
    Views
    1,682

    I'm not sure if they changed the oil type or not...

    I'm not sure if they changed the oil type or not yet... I just cut open the old compressor to have a look inside.... had plenty of oil,murky oil of course,upper portion of hermetic can was really...
  25. Replies
    15
    Views
    1,682

    Effects of r-404A on an R-22 compressor?

    What happens when someone uses R-404 on an R-22 compressor? We recently aquired a new customer with a small chain of local convenience stores. We were called out to one of their stores last week on a...
Results 1 to 25 of 27