Search:

Type: Posts; User: kcrabill

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Thread: LX-Prog300-1

    by kcrabill
    Replies
    3
    Views
    638

    thanks found the .nxe file in...

    thanks found the .nxe file in C:\Lonworks\Import\JCI LX\PRG GPI, did an app download inside of tridium and it is build and send to device action in the GPI interface is now working.
  2. Thread: LX-Prog300-1

    by kcrabill
    Replies
    3
    Views
    638

    thanks for the reply, how would I go about...

    thanks for the reply, how would I go about getting the latest .nxe file and then loading it onto the controller.
  3. Thread: LX-Prog300-1

    by kcrabill
    Replies
    3
    Views
    638

    LX-Prog300-1

    I am experiencing an issue when I build and send the program to the Lx-Prog300-1 device from JCI using the LX GPI interface. The error I am getting is "device and application runtime version...
  4. Replies
    119
    Views
    16,063

    I have heard of aic wireless using sedona for...

    I have heard of aic wireless using sedona for street lighting, but we have only seen the easy io. They are two more devices, don't know what company they are, that we are going to be testing on...
  5. Replies
    119
    Views
    16,063

    we used only two of them as a test on in the...

    we used only two of them as a test on in the office and didn't have any proplems with the sedona communication. Overall, we are really high on them but no real sites yet. I heard there was a new...
  6. Replies
    16
    Views
    1,556

    another thing to think about is that calibration...

    another thing to think about is that calibration will no longer take place so the damper and the air flow could get offline over time without the front end
  7. Replies
    16
    Views
    1,556

    It will maintain all of the settings from the...

    It will maintain all of the settings from the last command and will still work normally.
  8. Replies
    8
    Views
    1,047

    kcrabill at cochranesupply.com

    kcrabill at cochranesupply.com
  9. Replies
    8
    Views
    1,047

    I haven't worked with FlexSerial, saw it at the...

    I haven't worked with FlexSerial, saw it at the summit in florida but after looking at the website, it looks like it has a crc at the end of it but overall it still looks really simple since they...
  10. Replies
    8
    Views
    1,047

    krac, I have already done about 7 different...

    krac,

    I have already done about 7 different Tridium drivers. You can send any questions to <removed> if you get stuck on any of the java. It could probably be done in a few hours if the...
  11. Replies
    11
    Views
    2,239

    Matt, I understand, They will need the TCI card...

    Matt, I understand, They will need the TCI card on the rooftops and they should be able to bring in 3 diag per compressor. Did some ccp apps use the com3 version 1 vav's. I have seen a site already...
  12. Replies
    11
    Views
    2,239

    I assume the rooftops are com4, if not, the board...

    I assume the rooftops are com4, if not, the board on the voyager can be rotated to make it a com4 device since I know the com3 driver doesn't talk to them yet. The vav's could be brought on as...
  13. Replies
    11
    Views
    2,239

    I think there is a Tridium solution. If I...

    I think there is a Tridium solution. If I remember correctly, The VariTrac(CCP) keeps track of the heating and cooling votes for a trunk of Vav's and then relays that info to the RTU so provide...
  14. Replies
    6
    Views
    1,394

    more info is that it is uses the same protocol as...

    more info is that it is uses the same protocol as BMN uses to talk to a trane tracer panel so it must have been some kinda of open protocol people were adapting but in the eighties.
  15. Replies
    6
    Views
    1,394

    I have two big binders of information on ensemble...

    I have two big binders of information on ensemble but not in pdf form, is there a particular piece of info you might want to look up for you so I don't have to scan a thousand pages. typically you...
  16. Replies
    1
    Views
    398

    PCM and Tracer 100 programming

    I was on a site earlier this week where I created two new points in the PCM using PCMEdit for analog setpoint 7 and 8. I noticed in the tracer 100 menu system, it only allows me to reference points...
  17. Replies
    10
    Views
    1,942

    The R2 integration was using a later version of...

    The R2 integration was using a later version of ISN, because the packets are very close in nature but slightly different. The unit is a central link unit. The issue I am having is that the unit is...
  18. Replies
    10
    Views
    1,942

    The device I am trying to talk to is central linc...

    The device I am trying to talk to is central linc unit that is connected to a computer that has a software on it called york facility manager. The version on the central linc says it is 4.1A. We...
  19. Replies
    2
    Views
    1,081

    you have two options, a string object or a...

    you have two options, a string object or a BStatusString object. The difference being that one also has the status property in it. You set up a new slot that is of type statusString and then do
    ...
  20. Replies
    10
    Views
    1,942

    York ISN Driver

    I am looking into the possibility of using a driver to connect york linc devices to Tridium which I believe is their ISN protocol version 4.0. Has anyone been able to intregrate tridium and their...
  21. Replies
    31
    Views
    2,096

    freddy-b, I am also a programmer. The slot he...

    freddy-b, I am also a programmer. The slot he will add is a BStatusBoolean so you will be able add it to an add block or any other object that uses BStatusBoolean. you can tell the types by...
  22. Replies
    31
    Views
    2,096

    My point is that with a boolean, you have only...

    My point is that with a boolean, you have only two possible outputs. One for the true command and one the false command. You can use and, or, not blocks to get different boolean values based on the...
  23. Replies
    31
    Views
    2,096

    yellowfrog is right, you are propably looking for...

    yellowfrog is right, you are propably looking for a booleanSelect instead of a booleanSwitch
  24. Replies
    7
    Views
    970

    tuncos makes a good point, if the graphics are...

    tuncos makes a good point, if the graphics are slightly different I would create one for each AHU, but it they look the same, relative is the way to go since you have one Px file. You will only have...
  25. Replies
    7
    Views
    970

    Your first problem needs to be solved through...

    Your first problem needs to be solved through relativizing of the ords on your Px Page. If you go to the Px editor of your Px Page, you will notice a window on the top right hand side called "Bound...
Results 1 to 25 of 29
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event