  1. Replies
    19
    Views
    620

    Open inlet valve, close outlet. Turn the machine...

    Open inlet valve, close outlet. Turn the machine on and within 30 seconds it should reach high pressure cutout and shut off. I believe its around 500 psig.
  2. Replies
    7
    Views
    587

    Is cap. tube on inlet or air leaving side of...

    Is cap. tube on inlet or air leaving side of coil? All the ones I have seen are on air leaving side of coil you are trying to protect.
  3. Replies
    7
    Views
    1,036

    If I had access to Pro Press that is the route I...

    If I had access to Pro Press that is the route I would take over sharkbite fittings. Although I agree with HVAC Marc, we have used both in situations where we could not fire up a torch due to fire...
  4. Replies
    10
    Views
    973

    Comfort alert code 3?? I ran into same problem a...

    Comfort alert code 3?? I ran into same problem a month or so ago. Code 3 means four consecutive cycles of less than 3 minutes each. I put 5 minute delay into Focus Pro 5000 stat and have not been...
  5. Replies
    1
    Views
    401

    Edge Pro stat question

    Anyone know what bulletin SMB13-0010 is all about?? Appears there is now a metal oxide varistor (mov) across "G" and "C" terminals of stat when you buy one today. What issue did this resolve?
    ...
  6. Replies
    2
    Views
    413

    Whilpool undercounter ice maker experts

    Anyone have a service manual for a md# GI15NDXTB3,
    ser #E00807755? Clean light is staying on, will run through the flush cycle and then does nothing.
    Thanks in advance!
  7. Replies
    9
    Views
    1,162

    Which meter to use to check amp draw

    Need some input on which one of my meters would be most accurate to check amp draw on control circuits. My fluke 333 amp clamp or my fluke 87 (using leads in series with the load)? Was playing around...
  8. Thread: GPS products

    by chill67
    Replies
    2
    Views
    604

    GPS products

    Anyone using GPS ( Global Plazma Solution) products for indoor air quality? Any thoughts on performance?
    Thanks!
  9. Replies
    3
    Views
    525

    Just what I needed, thanks a bunch!

    Just what I needed, thanks a bunch!
  10. Replies
    3
    Views
    525

    Low voltage terminals on a Bard unit

    Md.# WA5S1-A0ZBPXXXJ, ser. # 268N062274712-01

    Can anyone tell me what the E and F terminals are used for on low voltage terminal strip? Schematic shows no internal wires but I have field installed...
  11. Thread: Proper cfm

    by chill67
    Replies
    27
    Views
    3,545

    York air handler md.# AHE30B3XH21A with X13...

    York air handler md.# AHE30B3XH21A with X13 motor. At the time I ran my test air conditioner was not running and had not been running for days prior. Since I was not familar with the X13 motor I...
  12. Thread: Proper cfm

    by chill67
    Replies
    27
    Views
    3,545

    Same fan speed and entire system is only a year...

    Same fan speed and entire system is only a year old, no lint blanket on coil. I was shocked as to my findings as well. Wonder why there are no numbers calculated for air flow with wet coil??????
  13. Thread: Proper cfm

    by chill67
    Replies
    27
    Views
    3,545

    Good point bigtime. My air handler delivers 1202...

    Good point bigtime. My air handler delivers 1202 cfm (checked at supply registers with Flow hood) with dry coil, 672 cfm with wet coil. Manufacture's air flow data is for dry coil condiitons and...
  14. Replies
    2
    Views
    705

    How about using a universal guard that just fits...

    How about using a universal guard that just fits over stat? Install base between junction box and stat.
  15. Yes, 13 seer heat pump. Vision Pro TH8320u1008...

    Yes, 13 seer heat pump. Vision Pro TH8320u1008 (For example), programmed for 2 cool \ 3 heat heat pump works as follows as I understand it. 1st call for heat makes Y, 2nd call for heat makes Y2, 3rd...
  16. Thanks, I knew there was a thermostat manufacture...

    Thanks, I knew there was a thermostat manufacture that had something that would do what I wanted.
  17. Spoke to honeywell this week and they advised me...

    Spoke to honeywell this week and they advised me that do not have thermostat capable of staging my 5kw and 10 kw seperately. Although 54regcab suggestion is a simple wiring change, I would still like...
  18. Help with maximizing efficiency of new heat pump system

    Just moved into new home with York heat pump md#YHJR30S41S3A, air handler md#AHE30B3XH21A, 2 stage heat strip kit #HK16501506A. Stat is a Braeburn 3200 series, 1 cool, 2 heat. Both stages of strip...
  19. Replies
    73
    Views
    6,884

    Look at the opposing end of condenser and if you...

    Look at the opposing end of condenser and if you see cable ties around return bends condenser must be split in order to clean correctly,
  20. Replies
    13
    Views
    1,652

    Have you verified your equipment will pull below...

    Have you verified your equipment will pull below 1200 microns?????
  21. Thread: Fuse question

    by chill67
    Replies
    29
    Views
    3,486

    Fuse question

    Suppose you find one blown fuse in 3 phase disconnect, repair problem that caused fuse to blow. I have always just replaced the fuse that was blown. Coworker said all three need to be replaced...
  22. Replies
    13
    Views
    1,737

    Google Rite Site inspection mirror, bought one a...

    Google Rite Site inspection mirror, bought one a while back and has saved me from a lot of frustration.
  23. Replies
    2
    Views
    415

    Exactly what i was looking for, thanks!

    Exactly what i was looking for, thanks!
  24. Replies
    2
    Views
    415

    question on energy star rated home

    What is minimum seer rating and HSPF on air source heat pump with electric backup heat for energy star rated home? All info I have seen states 14.5 seer and 8.5 HSPF, although builder is installing...
  25. Thread: code question

    by chill67
    Replies
    7
    Views
    726

    Funny you shoud say that, meet local inspector at...

    Funny you shoud say that, meet local inspector at our new home being built and she didn't have a clue!
  26. Thread: code question

    by chill67
    Replies
    7
    Views
    726

    code question

    Anyone know the code on max. length of flex duct run on new construction in kentucky?

    Thanks!
  27. Replies
    9
    Views
    868

    Thanks for the replies, looking at new homes (all...

    Thanks for the replies, looking at new homes (all electric) and was entertaining the thought of upgrading the hvac equipment. Only do commercial work so i rarely deal with heat pumps.
  28. Replies
    9
    Views
    868

    seer rating on heat pumps

    What is the highest seer rating you can get on heat pump these days?

    Thanks!
  29. Replies
    2
    Views
    888

    Large freezer in food processing plant

    Customer has freezer, r22 refrigerant that as we all know was a mistake from the get go. Freezer currently has two evaporators (electric defrost), one condensing unit for each evap. They are wanting...
  30. Replies
    3
    Views
    981

    Manufacturer of the motor\compressor should be...

    Manufacturer of the motor\compressor should be able to provide you this info.
  31. Replies
    9
    Views
    1,192

    Thanks for the replies! cperk, ever make it to...

    Thanks for the replies! cperk, ever make it to Guntersville lake???
  32. Replies
    36
    Views
    3,201

    If I were in your shoes I would consider hooking...

    If I were in your shoes I would consider hooking a garden hose to the inlet of the condenser & hook it up to city water, dump the outlet to a drain somewhere & see if your delta t across condenser...
  33. Replies
    36
    Views
    3,201

    Closed loop, ditch the water regulators.

    Closed loop, ditch the water regulators.
  34. Replies
    36
    Views
    3,201

    Any check valves on outlet line from...

    Any check valves on outlet line from condensers????
  35. Replies
    36
    Views
    3,201

    One regulator common to all four condensers? I...

    One regulator common to all four condensers? I assume water is being dumped down drain. Sounds like ya might need to post equipment models, cooler sizes, etc.. to have someone a lot smarter than me...
  36. Replies
    36
    Views
    3,201

    Don't understand your statement about water temp....

    Don't understand your statement about water temp. to compressor coil????
    Condenser fowled? Water regulator all the way open? Interesting a customer would let there walkin run warm for six years. Was...
  37. Replies
    36
    Views
    3,201

    What is inlet & outlet water temp. to condenser? ...

    What is inlet & outlet water temp. to condenser? Does water line to condenser have regulating valve? If so, is it adjusted correctly?
  38. Replies
    9
    Views
    1,192

    Trane RAUCC40GBG13ABD1

    Compressor mds #CSHA093R0B00 twinned together, one of which has mechanically failed. Why does Trane recommend replacing both??? I understand there can be cross contamination, nothing an oil change...
  39. Replies
    6
    Views
    1,228

    Equipment 6 months old, but good thought

    Equipment 6 months old, but good thought
  40. Replies
    6
    Views
    1,228

    Sounds like I need to modify filter racks to...

    Sounds like I need to modify filter racks to 22x25 filters, I can gain approx. 300 sq. in. of return air if I do this. Have to figure a way to remove existing 16x25 racks, the way the return box was...
  41. Replies
    40
    Views
    4,483

    :LOL Funny stuff

    :LOL Funny stuff
  42. Replies
    6
    Views
    1,228

    low airflow on York twinned furnaces

    Md# GY9S120D20UP11J, furnaces are twinned together (5 ton evap. on each furnace) & sit on return box. Total cfm (checked with flow hood) with merv 7 filters, fan on high speed is 2458. Manual states...
  43. Replies
    40
    Views
    4,483

    13 pieces of equipment on roof, gas packs &...

    13 pieces of equipment on roof, gas packs & splits. Anybody seen these cages before? Copperguard.net
  44. Replies
    40
    Views
    4,483

    That was my thought but customer was concerned...

    That was my thought but customer was concerned about gritters setting it off. Couldn't motion detector be set as to not detect small animals?
  45. Replies
    40
    Views
    4,483

    alarm for copper thieves on rooftop equipment

    Got a customer that wants some type of alarm on his rooftop equipment in case copper bandits arrive. Not interested in pressure switches for obvious reasons. Building does have alarm system, should...
  46. Thread: new to forum

    by chill67
    Replies
    4
    Views
    807

    Appears there are only a couple post on Fenji...

    Appears there are only a couple post on Fenji that I can find, & one of them

    is yours Westechpro. Good luck!
  47. Replies
    11
    Views
    1,358

    I could be mistaken but I am pretty sure you can...

    I could be mistaken but I am pretty sure you can only do averaging with four

    or nine sensors.
  48. Replies
    5
    Views
    536

    HEY!!!!!!!!!! Was that a holler? Have fun...

    HEY!!!!!!!!!!

    Was that a holler?

    Have fun on the site!
  49. Replies
    26
    Views
    1,828

    :oops: Update - We will be installing VFD on...

    :oops: Update - We will be installing VFD on pump, was not on plans & was

    never questioned by installer.
  50. Makes sense rundawg, would this also apply to an...

    Makes sense rundawg, would this also apply to an old stove with pilot. I

    remember as a youngster dad having to clean the white stuff off the pilots.