Search:

Type: Posts; User: rikenz

Page 1 of 5 1 2 3 4

Search: Search took 0.01 seconds.

  1. Thank you, Daikin came through yesterday and...

    Thank you, Daikin came through yesterday and emailed me the pdf. They did however say that it was Tridium who was supposed to provide this information.

    R
  2. Niagara AX Mcquay OPM Driver Open Protocol Data Information Packet

    Hello,
    I have a Mcquay RFS135CLY Rooftop Air Handler that I'm trying to integrate into Niagara AX. I have a JACE with the Mcquay OPM driver and I'm setting up the station. As points needs to be...
  3. Replies
    1
    Views
    261

    [QUOTE=t-reck;17564591]Does anyone have a hex...

    [QUOTE=t-reck;17564591]Does anyone have a hex code table for the McQuay OPM data for WSHPs? I'm migrating the system from using a JCI MIG in between a Jace and the OPM. The HPs have microtech-I...
  4. Replies
    8
    Views
    396

    I'm sure you've done this but right click on the...

    I'm sure you've done this but right click on the MSTP port in the tree and make sure it's enabled. I spent an hour one time trying to figure out why I wasn't communicating and BINGO. As this was a...
  5. Thread: Cheap Training?

    by rikenz
    Replies
    13
    Views
    814

    RSD Total Control has Metasys and Niagara based...

    RSD Total Control has Metasys and Niagara based classes in San Jose and Sacramento. Classes are good, really condensed over 3 days, a good start. If you don't currently have any control systems you...
  6. Replies
    4
    Views
    624

    I like the Acromag RS-485 repeater. Seems like a...

    I like the Acromag RS-485 repeater. Seems like a well made unit.
  7. Thread: Cheap Training?

    by rikenz
    Replies
    13
    Views
    814

    Where do you live?

    Where do you live?
  8. Replies
    11
    Views
    1,042

    I figured it out. Changing Maximum Global...

    I figured it out.
    Changing Maximum Global Override Time
    Station/config/sysinfo add facets: maxOverrideDuration/Reltime/3hrs- or whatever you want max to be
    just write in maxOverrideDuration as...
  9. Replies
    11
    Views
    1,042

    CB, Can you walk me through how to do this...

    CB,
    Can you walk me through how to do this globally? I tried to follow the Niagara Central post but was not successful.

    Thank you!

    Sean
  10. Replies
    24
    Views
    2,372

    I would love a copy of this as I've yet to get it...

    I would love a copy of this as I've yet to get it to work...
    My email is in my profile. Thank you!

    R
  11. Replies
    23
    Views
    1,388

    Cagey57- Thank you for the correction. I just...

    Cagey57- Thank you for the correction. I just read through the N2 Communications Bus Technical Bulliten Lit# LIT-636018

    On page 19 it states :
    "Figure 5 shows an NCU in the middle of the single...
  12. Replies
    23
    Views
    1,388

    If you have two trunks going off in two...

    If you have two trunks going off in two directions with an End Of Line setting at the the two ends you have two n2 trunks and need to hook them up to two separate RS-485 connections on the FX60. It...
  13. Replies
    23
    Views
    1,388

    Each FX-60 that you install will come with an N2...

    Each FX-60 that you install will come with an N2 driver and embedded workbench. You can do whatever you want with the existing station on the unit.

    With embedded workbench you cannot create a new...
  14. Replies
    24
    Views
    2,481

    Where are you located? I'm sure there are a...

    Where are you located? I'm sure there are a number of people on this site that can help you out. Tridium Niagara is a widely used platform that your contractor must not be accustomed to. DGlux is a...
  15. Replies
    19
    Views
    2,087

    It worked! Wow what a great tool! Thank you! I...

    It worked! Wow what a great tool! Thank you!
    I had to set the UDP port to 47808 as it wouldn't let me enter 0xBAC0 into PCT for some reason. I also had to set my network number to 2 which is the...
  16. Replies
    12
    Views
    1,431

    Yes

    Yes
  17. Replies
    12
    Views
    1,431

    I'm still trying to make this work. Is there a...

    I'm still trying to make this work. Is there a place in the manual with the configuration parameters needed?
  18. Replies
    19
    Views
    2,087

    Can anyone walk me through how to do this?

    Can anyone walk me through how to do this?
  19. Replies
    33
    Views
    2,592

    Thanks guys, I'm taking your advice on this and...

    Thanks guys, I'm taking your advice on this and going the Rover route. I contacted Echelon and the sales guy in reference to my question
    "Do you know if I can use this software to configure Trane...
  20. Replies
    33
    Views
    2,592

    Thanks Dapper! I'm new to Trane LON and trying to...

    Thanks Dapper! I'm new to Trane LON and trying to figure this all out. Check out this link https://www.echelon.com/products/tools/integration/lns-plugins/pluginShow.asp?pluginManID=61
    It shows a...
  21. Replies
    33
    Views
    2,592

    "You can however use any of these software...

    "You can however use any of these software packages to configure Trane comm 5 controllers.[/QUOTE]"

    Dapper,
    Is this true? If I purchase Lonmaker and install the Trane LNS Plugins can I configure...
  22. Replies
    10
    Views
    602

    How do you "open the platform of your local...

    How do you "open the platform of your local machine"?
    I haven't tried this.

    Thanks!
  23. I use it all the time and love it.

    I use it all the time and love it.
  24. Replies
    281
    Views
    43,942

    Do you have XPSI software? The pumps are...

    Do you have XPSI software?
    The pumps are probably connected to a Microzone II field controller. You could try resetting the controller, they are pretty bulletproof, maybe you lost a relay somewhere....
  25. Sorry I should have given more information. I...

    Sorry I should have given more information. I have a SIM-Mtech GCM that has one ASD bus communicating to 2 MZ2's then it has a second bus communicating with a rooftop Mcquay air handler and chiller....