  1. Thread: Solidyne

    by GregF
    Replies
    8
    Views
    1,734

    Drivet

    I have not used it my self but I know someone that has. Said it worked ok
  2. Thread: Solidyne

    by GregF
    Replies
    8
    Views
    1,734

    Solidyne

    Yes there is a driver for these things. You can call them and they will direct where to buy it.
    Greg
  3. Replies
    5
    Views
    365

    License

    Talon is OPEN. Any time you see a * in a license file it means it will take any thing.
  4. Replies
    3
    Views
    867

    Ilon

    Just use the LonIP Network.

    G
  5. Replies
    6
    Views
    1,021

    Raptor

    It depends on the version, but there is a Talon block that was used a lot. Howevere it has a bug in it. You could power it down but DO NOT DO THIS untill you change the battery to a new one. The Lon...
  6. Replies
    9
    Views
    1,617

    Boolean Switch

    Ha Steve
    There's not a strait up way to do what your looking to do. I use them alot and I'll send you on in the morning.

    Greg
  7. Replies
    30
    Views
    3,116

    Jace I/O

    Well I use them all the time. If you follow the rules its as solid as any thing else. Have a few Chiller Plants with no problem. Lots of Boilers and AHU's.

    G
  8. Replies
    6
    Views
    1,021

    Staefa

    Thats an older Talon Raptor. You would need the Raptor Block Programmer, and hope the debug file is in it.
    G
  9. Thread: Distech EC-GFX

    by GregF
    Replies
    12
    Views
    1,555

    gfx Tool

    opps told you wrong, I've always have a station running in th backround. I just checked it out and to have to have AX, Lonmaker, Lonwatcher or other tool running to.

    Greg
  10. Thread: Distech EC-GFX

    by GregF
    Replies
    12
    Views
    1,555

    GFX Tool

    All you need is the EC-gfx Programming Tool. Launch that and you don't have to use the AX.

    G
  11. Replies
    15
    Views
    1,644

    Ram Disk

    This is a Jace 7?? Are you using the JCI appliance? What do you have on the thing??

    Greg
  12. Replies
    15
    Views
    1,644

    Ram

    checkvalve

    What you are saying I mostly agree, however I was trying to point out how little memory we work with. If he has the flash disk space he could increase the ram disk. The other side is...
  13. Replies
    15
    Views
    1,644

    Ram Disk

    Clean up, I could not tell you without seeing the station. The % ram is set out of the box at 10%, you could lower tha to say 4 or 5 %. It will fix the problem for a short time and can fix it all...
  14. Replies
    15
    Views
    1,644

    Ram Disk

    Questionz
    Theres more to it than Histories and trends. The whole station loads up into ram disk, this saves flash disk writes. Now what ever you have on the Jace loads into ram disk, Operating...
  15. Thread: Java and Niagara

    by GregF
    Replies
    6
    Views
    1,271

    Java

    Good question, first its Tridium Niagara so it is the same.

    Second, if you are talking jar files or drivers it is Java, you just have to use Tridium imports.

    Third, Niagara AX has program...
  16. Replies
    28
    Views
    2,228

    T Box

    All that works and works well, It will route lon to. Twisted to Ip no problem.

    Greg
  17. Opps

    Sorry I just saw 275 devices, I would still do it. That would be about 70 devices a trunk.

    Greg
  18. Jace 7

    Shockwave
    A Jace 7 is about 4times a Jace 6, you are good for 150 devices.

    Greg
  19. Replies
    6
    Views
    940

    Bql

    hvac69
    The problem you are having is the slot is not exposed, now you could expose the slots but you have to open each point to do it.
    You might as well just do the conversion one at a time.

    Greg
  20. Points

    The super is a device under the NiagaraNetwork, hit the plus sign and double click the point folder, do a discover add points. Link points to the graphic.

    Greg
  21. Graphics

    Any points you want to display in on sup, bring in the points under the station under the niagaranetwork. Then like linking with the bacnet side you would link from the niagaranetwork.
    Greg
  22. Thread: Novar JACE Help!

    by GregF
    Replies
    4
    Views
    683

    Novar

    Well good luck getting Novar's jar files, they are tighter than TAC. If you can't get them check the tridium base license and if it has what you need delete the Novar one reboot and you should be...
  23. Niagara

    Ok now you have all three sup's on the network, all set 81, 1911, 3011 and yes you will have to put the 81 at the end to browse.

    Double click the Niagara Network and do a discover, now this is a...
  24. Log In

    Well I still don't get the 3 sup's but it is what it is. First forget the 80, each IP is its own. Think about your LAN, do you think thats how they do it??
    Now each sup has its own IP, done, they...
  25. Access

    You can't make this work and don't need to. If you change port 1911 the jace's will have to be changed, if you change the jace's the server will not be able to see them. Example Jace 1 port 1912,...