    Have you played with AutoHotKeys app. I posted...

    Have you played with AutoHotKeys app. I posted about using it for a Siemens kiosk awhile back

    http://hvac-talk.com/vbb/showthread.php?926502-Siemens-Apogee-PPCL-OIP-Command
  2. Replies
    3
    Views
    196

    The QFA3001.BU is a 3 wire device. (1) is DC+,...

    The QFA3001.BU is a 3 wire device. (1) is DC+, (2) is DC-, and (9) is RH 4-20mA or 0-10V
  3. Replies
    3
    Views
    196

    You can till order a 2 wire version. Its...

    You can till order a 2 wire version. Its QFA3001.WU-2W
  4. LonWorks RS-485 to Fiber - Fiber to RS-485?

    I'm not very versed with Lon so bear with me. We have a building with a Lon network (6 devices) and then a RS-485 to fiber going out to another location with a fiber to RS-485. This second building...
  5. Noticed you said you were setting up the page as...

    Noticed you said you were setting up the page as A4 can you change this to Letter and try again? Tried it as a test and the A4 does leave a lot of "White Space" were the Letter was not to bad.
  6. can you post an example, one of the live graphic...

    can you post an example, one of the live graphic and one of the print preview?
  7. If its on windows 7 use the snipping tool to do a...

    If its on windows 7 use the snipping tool to do a screen shot. May give you better results then the print function in graphics.
  8. Switch print layout to landscape before you...

    Switch print layout to landscape before you preview.
  9. Replies
    19
    Views
    1,702

    whart or bonzai . It was user configured

    whart or bonzai . It was user configured
  10. Replies
    19
    Views
    1,702

    Using this on a laptop or android phone? Setup...

    Using this on a laptop or android phone?
    Setup on phone was load aDosBox update config file. Load DOS CIS files onto phone. Connect to Air Console XL WiFi. Log into the web interface for the Air...
  11. Replies
    19
    Views
    1,702

    you can't use serial bot. Load aDosBox from...

    you can't use serial bot. Load aDosBox from Google Play. Add the config line to the aDosBox .cong file. Did you buy an Air Console XL device?
  12. Replies
    19
    Views
    1,702

    serial1=nullmodem server:192.168.10.1 port:2167...

    serial1=nullmodem server:192.168.10.1 port:2167 transparent:1
  13. Replies
    19
    Views
    1,702

    Itís not really a Siemens App but I've been able...

    Itís not really a Siemens App but I've been able to connect to a TEC with a Droid 4 phone. You have to load aDosBox and the old Siemens dos CIS software. Then use a WI-FI to serial device for the COM...
  14. Replies
    2
    Views
    404

    Try here for...

    Try here for manualhttps://www.hqs.sbt.siemens.com/gip/general/dlc/data/assets/us/APOGEE-Heat-Pump-Controller---Multi-Stage-Owner-s-Manual_A6V10308419_us-en.pdf
  15. Replies
    3
    Views
    539

    Well I figured I'd do a follow up. So I've...

    Well I figured I'd do a follow up. So I've managed to us the ICC xltr-1000 to pull the BACnet points from a Carrier 30MPW system (after the Carrier rep put in the CCN to BACnet card) and export them...
  16. Replies
    3
    Views
    539

    ICC xltr-1000 BACnet MSTP to FLN?

    Have a customer that wants to use an ICC xltr-1000 to bring a Carrier chiller BACnet MSTP points into a Siemens FLN. I looked over the manuals and it's kind of vague on the Siemens FLN side. Sounds...
  17. Thread: Siemens node

    by Merkas
    Replies
    10
    Views
    838

    Monitor "your own node" APOGEE Powers Process...

    Monitor "your own node"

    APOGEE Powers Process Control Language (PPCL) Userís Manual

    Syntax
    LINK
    Use
    This resident point indicates the condition of communications.
    Depending on the...
  18. Ok don't laugh too much at this. 1) Go into...

    Ok don't laugh too much at this.

    1) Go into report builder and create a new Trend Definition Report. Click the Add button and in the object selector window enter * as the point name and do a find...
  19. Replies
    8
    Views
    866

    357551

    357551
  20. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    611

    I know, Just checking that gazoo knows that....

    I know, Just checking that gazoo knows that. Should be able to do it from the front end even if its never had telnet enabled before. I do it all the time.
  21. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    611

    Is this PXCM on a PII hard wired trunk or on...

    Is this PXCM on a PII hard wired trunk or on ethernet?
  22. Thread: Siemens

    by Merkas
    Replies
    7
    Views
    611

    Is there an Insight front end? Go to system...

    Is there an Insight front end? Go to system profile and double click on the panel you want to enable telnet. Find the button "Terminal Definitions" a config window will open with a check box to...
  23. Replies
    15
    Views
    2,087

    "You all agree/disagree using two different...

    "You all agree/disagree using two different BACnet netowrk numbers on the same network is going to cause trouble like this?"

    Not sure? Anyone?

    Can you move you "BACnet/IP 47808" port to another...
  24. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,175

    Formulas for a 4-20mA input on a UC Slope = (V2...

    Formulas for a 4-20mA input on a UC
    Slope = (V2 - V1) / 2602
    Intercept = V1 - (Slope x 650)

    Sensor 0-65
    V1 = 0
    V2 = 65

    Slope = (65 - 0) / 2602
    Slope = 0.024981
  25. Thread: siemens uc ?

    by Merkas
    Replies
    8
    Views
    1,175

    From the Book table B-3; Range Slope ...

    From the Book table B-3;
    Range Slope Intercept
    0 - 100 0.038435 -25.0