Search:

Type: Posts; User: DaveCR

Page 1 of 13 1 2 3 4

Search: Search took 0.01 seconds.

  1. JSLLC4Life - Thanks for the offer, but my need...

    JSLLC4Life - Thanks for the offer, but my need for the software is past. Long, nine month horror story regarding JCI support...
  2. Distech is apparently going proprietary. They...

    Distech is apparently going proprietary. They have removed the programming tools from their public site. I filled out their software request form, including the name of the distributer we buy from,...
  3. Replies
    5
    Views
    135

    If those points are in a Metasys N30 "program"...

    If those points are in a Metasys N30 "program" then, yes. If those points are in an NCM or NAE then, no.
  4. Replies
    8
    Views
    203

    If the UPC Open was factory installed the point...

    If the UPC Open was factory installed the point mapping should be configured properly. There are several good trouble shooting threads in this forum; search "carrier upc" (with quotes).

    If the UPC...
  5. Replies
    5
    Views
    135

    With M-Tools you will be able to program and...

    With M-Tools you will be able to program and commission: VAV, VMA, DX, TC, AHU and UNT controllers. With the exception of the DX, you will need some form of RS-485 adapter (USB, RS232, N30 pass...
  6. Replies
    7
    Views
    303

    Johnson ABCS distributors will sell just about...

    Johnson ABCS distributors will sell just about everything across the counter. You can become a non-direct ABCS contractor through the distributor; that will give you access to the Tridium Jace...
  7. Replies
    3
    Views
    213

    To my knowledge, the simulator will not work with...

    To my knowledge, the simulator will not work with XM modules nor slave N2 controllers. The former crashes the software, while the latter ignores the slave devices.
    One workaround is to make a copy...
  8. Facility Explorer - 5 year update --FX...

    Facility Explorer - 5 year update

    --FX Controllers--
    History (almost)

    --LX Controllers--
    I have had one nightmare experience with these. Seven months and counting without a resolution.
    ...
  9. Thread: Carel Repair

    by DaveCR
    Replies
    5
    Views
    530

    plccenter.com lists some PCO3 models as stock...

    plccenter.com lists some PCO3 models as stock items and also state they repair them. Having never used their services I can offer no recommendation in that regard.
  10. Replies
    11
    Views
    956

    The discontinuation notice states the DX and ASCs...

    The discontinuation notice states the DX and ASCs will be discontinued this month and when the current stock is gone that is it. However, the notice also states those products will not be...
  11. Replies
    6
    Views
    649

    Cool. It's good to see someone else likes to...

    Cool.

    It's good to see someone else likes to have some fun with controls.
  12. Replies
    2
    Views
    351

    Some ten years ago I was told by our local rep....

    Some ten years ago I was told by our local rep. that it is a proprietary protocol.
    I know we aren't supposed to bash equipment vendors, but around here they are known as Rabid Air.
  13. Replies
    2
    Views
    324

    I don't know of a 10C1 alarm, but OC1 is valid...

    I don't know of a 10C1 alarm, but OC1 is valid (over current when accelerating)
    Here's the manual.

    538311
  14. Replies
    5
    Views
    633

    My observations are for the 5.7" model. Pros It...

    My observations are for the 5.7" model.
    Pros
    It has a bright screen and is nicely finished.
    Many communications options.
    Configuration software is solid.
    Cons
    Touch screen response to taps and...
  15. Lowering the baud rate will be of some help. If...

    Lowering the baud rate will be of some help.
    If there aren't any competing wireless networks, lock the WBTs to a single channel.
    I would guess there are some tuning policies that could be adjusted.
  16. Replies
    2
    Views
    442

    Link a BooleanWritable to StatusBooleanToBoolean...

    Link a BooleanWritable to StatusBooleanToBoolean to EmailService / Enable. You may need to execute a clearQueue action on the OutgoingAccount before email is re-enabled.
  17. The FEC line has no provisions (software or...

    The FEC line has no provisions (software or hardware) to operate the stepper motor on that valve.
  18. Replies
    4
    Views
    717

    The Trane document in this thread may be of help....

    The Trane document in this thread may be of help.
    http://hvac-talk.com/vbb/showthread.php?792662-BCI-R
  19. Option 1 - if you have access to the PID tuning...

    Option 1 - if you have access to the PID tuning parameters and integration can be set to zero (the latter makes some Carriers a no go) try this. On both AHUs: Set the VFD acceleration to five minutes...
  20. Labeling. One is branded Metasys while the other...

    Labeling. One is branded Metasys while the other is Facility Explorer. Both are Distech.
  21. I doubt this controller is up to date regarding...

    I doubt this controller is up to date regarding software and patches. The browser will need to use an older (rel 25) version of java to access the FX20.
  22. Thread: Lon Plug

    by DaveCR
    Replies
    12
    Views
    982

    Mouser.com

    Mouser.com
  23. Thread: DX 9100 Help!!

    by DaveCR
    Replies
    4
    Views
    579

    Johnson still has the manuals on their site....

    Johnson still has the manuals on their site. http://cgproducts.johnsoncontrols.com/default.aspx?topframe.aspx&0
    Metasys System / Hardware / Controllers / N2 Controllers / DX Series Controllers
  24. Replies
    2
    Views
    409

    Thanks for the info. We ended up gutting the...

    Thanks for the info. We ended up gutting the electronics from the unit and installed a wall thermostat and some relays. Had to do this some years back with a Tadiran ductless when parts weren't...
  25. Replies
    2
    Views
    409

    Haier minisplit parts source?

    Any one know of a parts source for these units. Local "rep" has sold just a few of these things and is not bothering to return calls. TIA
  26. Thread: best lap top

    by DaveCR
    Replies
    30
    Views
    1,663

    I check brand reliability at Consumer Reports...

    I check brand reliability at Consumer Reports before I make a purchase. For Windows laptops Toshiba, Acer, Gateway, HP are the most reliable (in the order listed). My work HP has been solid for 5+...
  27. Replies
    11
    Views
    1,255

    Google "niagara ax user guide" (it is a 20mb...

    Google "niagara ax user guide" (it is a 20mb download)

    First though on the warm classrooms is they are not occupied.
  28. Replies
    3
    Views
    524

    Here's the JCI Flash Sheet. 486011

    Here's the JCI Flash Sheet.
    486011
  29. Replies
    3
    Views
    524

    If the controllers are at version 5.3, lock ups...

    If the controllers are at version 5.3, lock ups are a known issue; here is the body of the tech bulletin.
    -------
    Problem
    FX-PC Series Programmable Controllers running FX Programmable Controller...
  30. Replies
    2
    Views
    397

    The product pages for their bacnet to modbus...

    The product pages for their bacnet to modbus devices don't mention auto discovery. Try manually adding a point to the jace and see what happens.
  31. Replies
    9
    Views
    463

    This machine, if it has an option card installed,...

    This machine, if it has an option card installed, can have its set point and demand limit controlled by 4-20mA (2-10Vdc) signals. The card was a popular option; most of the machines I've run across...
  32. Replies
    9
    Views
    463

    I think that A series machine is Trane Comm3/4...

    I think that A series machine is Trane Comm3/4 only. To be sure, give Trane a call and make sure you have the serial number handy.
  33. Replies
    8
    Views
    581

    Those boards need an option card to do Lon.

    Those boards need an option card to do Lon.
  34. Replies
    2
    Views
    255

    Put a 10k resistor in series with the slider....

    Put a 10k resistor in series with the slider. Make the AI point a 10k thermistor. Use a SPAN block to get your set point range.
  35. Replies
    2
    Views
    421

    We have done a few of these machines and Tranes...

    We have done a few of these machines and Tranes as well. The controllers have been Johnson programmables (DX9100, FX15, PCG26). To date we haven't had to deal with an EXV, but would probably use an...
  36. Replies
    4
    Views
    594

    The points, all of them, should come in off of...

    The points, all of them, should come in off of the .prn file. Try manually adding a device to the N2 network and, in the Resource File selection, browse to the appropriate .prn file. If the...
  37. Replies
    6
    Views
    623

    Usually an extra rung or two can be had by...

    Usually an extra rung or two can be had by condensing simple OR blocks. A Or B = C (two rungs) has an equivalent: Not A And Not B = Not C (one rung). If that isn't available, a Timer configured as...
  38. Thread: Niagara Facets

    by DaveCR
    Replies
    1
    Views
    538

    I messed around with the facets approach a little...

    I messed around with the facets approach a little bit and got the same results you did. Since I generally like easy and brute force is OK, I'd simply append the units via an additional bound label....
  39. Thread: CASCADING

    by DaveCR
    Replies
    2
    Views
    607

    google variable frequency drive cascading....

    google variable frequency drive cascading. Danfoss has an outline that covers this control subject among others.
  40. Replies
    12
    Views
    1,181

    Around here, it's "get out the chalk"

    Around here, it's "get out the chalk"
  41. Replies
    12
    Views
    1,181

    Hmm, and all this time I thought we were all...

    Hmm, and all this time I thought we were all independently wealthy and did this for fun...
  42. Replies
    12
    Views
    1,181

    Find a suitable wire sheet and drop in the...

    Find a suitable wire sheet and drop in the following components from the kitControl pallet: Util/MinMaxAvg and Math/Reset. Set up the MinMaxAvg block for the number of inputs required and link the...
  43. Replies
    29
    Views
    4,600

    This set up works for me with a JCI branded jace...

    This set up works for me with a JCI branded jace at 3.6.xx

    457311

    And CryptoService installed.

    457321
  44. This label works for me on JCI branded jaces....

    This label works for me on JCI branded jaces.
    456241
  45. This guide...

    This guide http://orioncontrols.com/literature/OR-PTLNK2BTL-TGD-01G.pdf may be of help. Search it for hot gas...
  46. Replies
    4
    Views
    621

    Have google search for condenser fan speed...

    Have google search for condenser fan speed controller.
  47. Replies
    11
    Views
    831

    Ditto

    Ditto
  48. Replies
    4
    Views
    862

    Old thread, current problem, right answer (com

    Old thread, current problem, right answer (com < 10). Thanks.
  49. Replies
    4
    Views
    916

    You can use the Martin-Hou equation of state to...

    You can use the Martin-Hou equation of state to generate refrigerant properties for use in your simulations. DuPont lists the coefficients in their literature....
  50. Replies
    4
    Views
    496

    48AK should be a VAV unit - is this correct?...

    48AK should be a VAV unit - is this correct?
    What are your SFS.M and SFS.S settings?