Search:

Type: Posts; User: billcontrols

Page 1 of 8 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    1
    Views
    290

    Well go down to Home Depot and get a WiFi...

    Well go down to Home Depot and get a WiFi thermostat. Put it in the space the chiller serves. And there you go...

    Honestly, you have to provide some details yourself if you want a real suggestion!
  2. Replies
    9
    Views
    508

    I can just imagine the linkage required to pull...

    I can just imagine the linkage required to pull plates in and out as the wheel flips like a coin along its horizontal axis across the diameter. Reminds me of some inlet vane designs!
  3. Replies
    9
    Views
    508

    "I'm curious as to whether it matters which way...

    "I'm curious as to whether it matters which way an energy recovery wheel spins, and why."

    Well if spun at a 90į axis to how they typically are installed, they would likely need much more room in...
  4. Replies
    49
    Views
    1,918

    That is normally all you need to do.

    That is normally all you need to do.
  5. Replies
    12
    Views
    1,204

    The ADX itself can not talk bacnet to the jace. ...

    The ADX itself can not talk bacnet to the jace.

    The Nae can talk bacnet to the jace. Typical Jace proxy points are not bacnet points. You can create bacnet points in the jace. The Nae could then...
  6. Replies
    49
    Views
    1,918

    Yes sometimes the DMO import I mentioned will not...

    Yes sometimes the DMO import I mentioned will not get the points you are after. Then the table will allow you to manually add the point.

    Since the DX is programmable there is no shortcut to learn...
  7. Replies
    49
    Views
    1,918

    Since you have the DXS file, you can make the DMO...

    Since you have the DXS file, you can make the DMO file the FX60 will use to import the points. There are some options for making the dmo file in the file tab of GX9100. It is done the same way as the...
  8. Replies
    49
    Views
    1,918

    yes the reset could be in the DX or the NCM....

    yes the reset could be in the DX or the NCM. Decoding the names in a dx is a PIA if you don't have the config files on the ows. look for *.dxs or *.tag files.

    If no luck finding the files start...
  9. Replies
    49
    Views
    1,918

    The model.und will have the translation from the...

    The model.und will have the translation from the cs object AI_n, BI_n, AD_n, SP_n, AO_n, BO_n used in metasys to the N2 addressing. AIn, BIn, BDn, ADFn, AOn, BOn.

    As far as which points are...
  10. Replies
    49
    Views
    1,918

    A CS-object can map any point in the controller....

    A CS-object can map any point in the controller. It also typically mapped many points in the single object. The "Models" ddl file would reveal the point mapping inside the CS object.

    If there was...
  11. Thread: HVAC Pro

    by billcontrols
    Replies
    44
    Views
    3,237

    The only current device I know for Zone Bus is...

    The only current device I know for Zone Bus is the JCI AS-CVTPRO300-1. Plus a USB to RS232 device.

    I have a CVTPRO but never use it. I use the S2 device.
  12. Replies
    3
    Views
    341

    Try something like this: Notice the Scale on the...

    Try something like this:
    Notice the Scale on the canvas pane is fit ratio.

    540911
  13. I did the work. Make sure you have the correct...

    I did the work. Make sure you have the correct Modbus Mapping table for you revision of the controller. Needed Header sensor hardwired to boiler. It would not allow network input of the header...
  14. Replies
    11
    Views
    1,153

    Clean dry compressed air is 100% required. Tank...

    Clean dry compressed air is 100% required. Tank pressure should be in the 50# to 90# range. Compressor needs to run no more the 50% of the time for reliable operation. I would look for a tank at...
  15. Replies
    8
    Views
    619

    The NAE may or may not allow the BACnet to work....

    The NAE may or may not allow the BACnet to work. Best to allow an integrator who knows something about both NAE and FX visit and check out what you can do.

    You may be able to leave the NAE in...
  16. Thread: HVAC Pro

    by billcontrols
    Replies
    44
    Views
    3,237

    I use the S2 device and like it. Very reliable. I...

    I use the S2 device and like it. Very reliable. I use the old B&B RS232 to RS485 on my old laptop with the built in serial port. I am sure the B&B USB to RS485 works well, but I have never used it. I...
  17. Replies
    21
    Views
    1,673

    The problem is the JCI branches sell their "open"...

    The problem is the JCI branches sell their "open" BACnet system but then install a system that breaks the BACnet by duplicating the device IDs. It is quite simple in the software to do it properly,...
  18. Replies
    37
    Views
    12,303

    Real world check here. Doesn't really matter if...

    Real world check here. Doesn't really matter if you calibrate to 5,6,7,8,or 9# air pressure at the stat. Just always do it the same. I always use 9# because the midrange of the JCI stat in the...
  19. I think there is a terminal interface on the mig...

    I think there is a terminal interface on the mig with a null modem cable to your computer. I think you can see and modify some configuration information. I don't think you can see live data. Though...
  20. The TC-9100 program was selected by the part...

    The TC-9100 program was selected by the part number and some parameters set with HVACPRO. It looks like the SC-9100 has the same programs, but you can select the program from the display on initial...
  21. Out of curiosity I googled a few things. Check...

    Out of curiosity I googled a few things.

    Check out google "Application notes for SC-9100 JCI"

    One of the sheets I got talked about address jumpers under the cover.
    ...
  22. You are using the Enum point type in the Jace? I...

    You are using the Enum point type in the Jace? I think you need to drag it from the Modbus pallet and set the register address in the properties. It has been a while since I did this, and never with...
  23. Now I have to eat my post. I had not loaded...

    Now I have to eat my post.

    I had not loaded the JCI release 6.0 (AX 3.8) on the laptop yet. I had a failed FX60 (Release 4.1) to replace with a FX70 (release 6.0). With no access to internet I...
  24. Why is the serial method better or easier than...

    Why is the serial method better or easier than just using the ethernet? I know how to do both, but I haven't used the serial cable to a Jace in a long time. I usually set the primary JACE LAN port to...
  25. Not quite sure what you are asking. You can set...

    Not quite sure what you are asking. You can set the Nic for DHCP in the platform TCP/IP configuration property sheet. You can set the http port to 81 in the services/webservices property sheet....
  26. Replies
    2
    Views
    372

    You still have a DC-9100 that works? The DC-9100...

    You still have a DC-9100 that works? The DC-9100 (also known as a LCP) and the early DX-9100 Ver 1 controllers had a problem of the AIs failing after about 10 years, in my experience. All of these I...
  27. Replies
    28
    Views
    1,993

    If you are going 500' with #18 you may want to...

    If you are going 500' with #18 you may want to homerun the power to the transformer for every controller. This is not a bad practice for any distance. Those extra connections at each controller tend...
  28. The whole operation is pretty high class for a...

    The whole operation is pretty high class for a Barn. I think the science in the Lab may be way over my head. They do not share a lot of info about the details of their product. You don't get much...
  29. Funny thing. This morning I went to a job with a...

    Funny thing. This morning I went to a job with a no cooling call. This is a Barn full of Bulls that serves the Dairy industry. (Get the picture!) The pressure switch that proves the AHU fan was not...
  30. I would suggest a Pressure switch with a Pitot...

    I would suggest a Pressure switch with a Pitot tube pickup and a CT wired so both must prove fan operation before the direct fired unit can start. I would also suggest someone put a CO monitor in the...
  31. Replies
    17
    Views
    1,502

    I like the system I worked on yesterday. Works...

    I like the system I worked on yesterday. Works like a fan powered box but without the fans. 1969, I think, the office building was built with a large High Static air handler in the basement. Terminal...
  32. Good Tip!

    Good Tip!
  33. The out.value needs to go into the text line....

    The out.value needs to go into the text line. Click the 3 dots to modify the text.
  34. Replies
    8
    Views
    705

    Likely still works better than a Nest.

    Likely still works better than a Nest.
  35. What seminar did the consulting engineer take...

    What seminar did the consulting engineer take most recently? Or did the salesman for a particular type of equipment visit recently? :yes::yes::yes:

    Seriously, the type of equipment must match the...
  36. Replies
    30
    Views
    1,489

    My Dell Vostro with i5 32 bit processor, 4GB ram...

    My Dell Vostro with i5 32 bit processor, 4GB ram just got new life in it when I upgraded the hard drive from 500GB HDD to a 1 TB SSD. I have multiple VM for various different configurations to handle...
  37. Replies
    12
    Views
    821

    I think the confusion here is because the...

    I think the confusion here is because the original post is a little vague. If the connection to the DDC controller is a shield connection, the wiring shown should work. The green conductor that is...
  38. Short term try a UPS on the Gateway power supply?...

    Short term try a UPS on the Gateway power supply? Or a sensitive power monitor that drops power for a little longer when the transfer switch Flips. I like the UPS idea. I am guessing the very brief...
  39. Replies
    21
    Views
    1,796

    I guess I am not hard enough on my meter. I had a...

    I guess I am not hard enough on my meter. I had a Fluke 73 many years ago that I wanted to upgrade to a Fluke 179. I did not blatantly try to break it, but I was very "uncareful" for a long time and...
  40. Replies
    5
    Views
    329

    There is also a Sliding window demand Calc in the...

    There is also a Sliding window demand Calc in the Energy folder and a totalizer in the ext folder of the kitControl palette. I am not sure what BTU signal you are starting with.
  41. Replies
    11
    Views
    8,649

    I decided to expand on the misconception that a...

    I decided to expand on the misconception that a proportional actuator is better than a floating actuator. Some users think that a % on the computer screen means that is how much the device is...
  42. Replies
    11
    Views
    8,649

    Now we are mixing in another device. A valve...

    Now we are mixing in another device. A valve actuator (or any actuator) and a controller are different things in my head. This thread has covered the differences in a floating and a proportional...
  43. Replies
    11
    Views
    627

    I don't think the diagram you are thinking of is...

    I don't think the diagram you are thinking of is really a T-tap. Yes a repeater can be used to create a T, but that is because the repeater actually splits a network into two separate segments that...
  44. Replies
    11
    Views
    627

    That is exactly how not to do it. Pull two cables...

    That is exactly how not to do it. Pull two cables the 67 feet and maintain the daisy chain. Up from the NAE to the UNT. Then Up from the UNT to the Upper floors. Do not put Tees in RS485 networks.
    ...
  45. Replies
    6
    Views
    319

    http://cgproducts.johnsoncontrols.co...

    http://cgproducts.johnsoncontrols.com

    Just searched "N30". User manual right there in the middle of the list.
  46. Replies
    10
    Views
    685

    In my Experience, the S/W systems I have worked...

    In my Experience, the S/W systems I have worked on usually had a separate Night Thermostat on the wall. Or the unit would sometimes just shutdown at night and separate pneumatic stats would control...
  47. Replies
    26
    Views
    1,434

    I have always thought the neighbor's bug Zapper...

    I have always thought the neighbor's bug Zapper did a fine job of luring the critters away from my yard.

    Plus I seem to attract fewer of the biting insects than my wife. I won't have noticed any...
  48. Replies
    7
    Views
    699

    I would go with a Tridium solution. The JCI FX...

    I would go with a Tridium solution. The JCI FX comes with the N2 from JCI. You can get a N2 for the Honeywell Webs. With the Fieldserver you will still need a workstation to give the Web interface....
  49. Replies
    7
    Views
    699

    It is likely the Nae does more than just put data...

    It is likely the Nae does more than just put data on the ethernet. The NAE may be doing scheduling, trending and contain control logic to make the system work. The NAE may also be providing the...
  50. Replies
    2
    Views
    461

    Opinion here... I prefer cascade control. Zone...

    Opinion here... I prefer cascade control. Zone loop resets the DA setpoint. The DA loop controls the valves.