is this a scroll? if it is its gone. it does...
is this a scroll? if it is its gone.
it does say 3 phase check rotation if it is a scroll. -
09-02-2004, 12:18 AM
Thread: Trane compressor question
by pgl1950- Replies
- 12
- Views
- 2,002
In most semi herm. comp. there are intenal...
In most semi herm. comp. there are intenal winding temp safetys.
-
09-01-2004, 11:41 PM
- Replies
- 14
- Views
- 1,112
oil loss
Everyone on this site has been extremly helpful. Ihave used this info and have checked this info earlier but sometimes machines have amind of there own.
I have babysat this thing and have... -
08-30-2004, 09:23 PM
- Replies
- 14
- Views
- 1,112
I have double risers with traps. I can get oil...
I have double risers with traps.
I can get oil back when system loads up but when it runs unloaded ( 2 cylinders are always loaded) the level drops and trip oil safety.
I have fixed and confirmed... -
08-30-2004, 07:12 PM
- Replies
- 14
- Views
- 1,112
new copressor oil loss
I have three unloaders controlled by the suction pressure and staged.
The condenser is above the evap.
I have verified that it's not my TXV's.
The problem occurs when the system runs in a partial... -
08-30-2004, 06:30 PM
- Replies
- 14
- Views
- 1,112
I replaced a 6 cylindes york compressor and now I...
I replaced a 6 cylindes york compressor and now I am having trouble with oil leaving and not coming back.
No hot gas by-pass, 3 unloaders 6 txvs with solinoid valves, and no oil seperator.