Search:

Type: Posts; User: im_in_control

Page 1 of 3 1 2 3

Search: Search took 0.00 seconds.

  1. Replies
    3
    Views
    689

    Personally if the sensor is 10F out of...

    Personally if the sensor is 10F out of calibration I would be replacing the sensor. The Barber Colman sensors are usually not that far off and if they are it usually means its failing or failed.
  2. Replies
    3
    Views
    657

    As already stated you could go with Signal XP but...

    As already stated you could go with Signal XP but the problem is that your Signal 98 graphics are probably 640x480 or 800x600 which means you have to get Windows XP to run at the lower resolution...
  3. Thread: flat lon

    by im_in_control
    Replies
    10
    Views
    1,734

    Actually as stated you can use the Jace as your...

    Actually as stated you can use the Jace as your network management tool. I have in the past setup my laptop to be a Jace and have a running station. I then add all of my nodes (Lon Devices) make my...
  4. Replies
    17
    Views
    2,763

    I agree with softtail .... In my opinion, the...

    I agree with softtail .... In my opinion, the privately owned independant companies are better to work for ... The management of a private company are usually thinking about what is best for their...
  5. LonMaker is rather expensive if you only need it...

    LonMaker is rather expensive if you only need it for this one project.

    What vendor's product line do you currently use and do they have a Lon Network Management Tool ?? You may be able to use it.
  6. Replies
    6
    Views
    874

    I responded to you question in the other post ...

    I responded to you question in the other post

    http://www.hvac-talk.com/vbb/showthread.php?t=132755&page=2

    The post above is incorrect in telling you that you will find the neuron ID in the LNC...
  7. Well your in for a ride on this one. You will...

    Well your in for a ride on this one.

    You will have to use a Network Management Tool such as LonMaker in order to replace the Trane Controllers. If you don't have the original LNS database you...
  8. Replies
    2
    Views
    543

    You can use WorkPlace Pro to manage pretty much...

    You can use WorkPlace Pro to manage pretty much all of the various Lon Devices. Tridium has JAR files for most of the different vendors and if a JAR file doesn't exist then you can use a Dynamic...
  9. Replies
    10
    Views
    1,894

    Unforunately, the programs in the LNC and the...

    Unforunately, the programs in the LNC and the Microzone II's would have to be changed to make this work. It could be alot of work depending on how the system is currently programmed.
  10. Replies
    10
    Views
    1,894

    drafty888 I think you meant to say that...

    drafty888 I think you meant to say that Datatalk/Signal was developed by Datatalk (out of New Mexico). The ASD protocol was actually developed by Barber Colman back in the late 80s early 90s....
  11. Replies
    0
    Views
    480

    Stupid Barber Colman GCM question

    Hello All,

    I am having a mind fart and can't remember how to disable the beeping you get every time you hit the <enter> key when programming a GCM. I thought it was the CTRL key and another key...
  12. Replies
    27
    Views
    1,948

    I don't know anything about AX but with R2 when...

    I don't know anything about AX but with R2 when you keep the graphics on each individual JACE instead of having all the graphics reside on the supervisor when you click a link to each JACE you have...
  13. Replies
    10
    Views
    3,115

    Unfortunately you will not be able to get that...

    Unfortunately you will not be able to get that version of signal to run under Windows XP. I believe the only way you will be able to get signal to run in Windows XP is to purchase Signal XP.

    And...
  14. Replies
    5
    Views
    1,131

    Okay I will try to answer a few of your...

    Okay I will try to answer a few of your questions.

    If you have the programs in Version 3.2 and open them in 4.0 (they will get converted when you open each file) this will not affect the...
  15. Replies
    5
    Views
    1,131

    I agree with jlcontrols that there is no need to...

    I agree with jlcontrols that there is no need to upgrade the WPTech unless you want to take advantage of all of the new imporvements. The UNC (Jace) and the Invensys controllers are completely...
  16. Replies
    5
    Views
    605

    Why not do supply air static pressure control to...

    Why not do supply air static pressure control to maintain the fan speed ?
  17. Replies
    5
    Views
    605

    Well unfortunately with the Siebe/Invensys...

    Well unfortunately with the Siebe/Invensys LonMark VAVs they do not have an input to indicate damper position so therefore there is no SNVT associated with it.
  18. Replies
    4
    Views
    564

    That product line requires either the DMS...

    That product line requires either the DMS software or DCT software. I believe both versions of software are DOS based. You also need a special adapter from Invensys once you get the software.

    And...
  19. Replies
    13
    Views
    1,997

    Yup you definately would be able to still use the...

    Yup you definately would be able to still use the S-Link Sensors ... and you would still be able to see the actual zone temperature and setpoints via LonMaker ...
  20. Replies
    13
    Views
    1,997

    If you are just looking at being able to...

    If you are just looking at being able to manipulate the Invensys LonMark certified program (Setpoints and whatnot) then yes you only need LonMaker to do this ... (you would do this the same way you...
  21. Replies
    13
    Views
    1,997

    jimmyj, not sure what you mean by non-LNS devices...

    jimmyj, not sure what you mean by non-LNS devices but they do have LonMark compliant programs and profiles in their MNL controllers (they are also fully programmable if you want to make custom...
  22. Replies
    13
    Views
    1,997

    Unfortunately, all of the Invensys I/A LonWorks &...

    Unfortunately, all of the Invensys I/A LonWorks & BACnet Controllers require you to have Workplace Tech. For the BACnet MNB controllers you will definately need the latest version of WPTech which I...
  23. Replies
    7
    Views
    962

    I am glad I was of help

    I am glad I was of help
  24. Replies
    7
    Views
    962

    Have you tried accessing the schedule from a web...

    Have you tried accessing the schedule from a web browser to see if you get the same results.

    It could be that the Jace has a different time zone setting then your computer running WP Pro. Open up...
  25. Replies
    7
    Views
    962

    It doesn't sound like you have a time...

    It doesn't sound like you have a time synchronization problem since the next event is indicating an off at 4:00pm and not 5:00pm ...

    I would check to make sure the holiday calendar is not in some...