  1. Replies
    4
    Views
    302

    Andrew, Can you try to add the N2 FEC as a...

    Andrew,
    Can you try to add the N2 FEC as a vendor device instead of an FEC ? I think that might solve the problem, but I have been wrong before !
  2. Thread: JCI

    by Cagey57
    Replies
    8
    Views
    826

    just_opinion, As other have said, you do NOT...

    just_opinion,

    As other have said, you do NOT have to replace the field Devices (ASC's/DX9100's).

    My solution is, and has been for a very long time, to keep a XP-Pro Laptop with PMI loaded on it...
  3. Replies
    4
    Views
    324

    38,400 on my side and Chiller Tech assures me the...

    38,400 on my side and Chiller Tech assures me the BCI-C is set to 38,400.
  4. Replies
    4
    Views
    324

    BCI-C and AX on MS/TP

    Trying to connect a Trane Chiller with a BCI-C to an MS/TP trunk on Ax (FX-60 actually).

    Trane Chiller Tech does his setup and it takes 10 minutes to discover the device (BCI-C) itself. Device...
  5. Replies
    2
    Views
    239

    gazoo, The model number would be really helpful...

    gazoo,
    The model number would be really helpful at this point.
  6. Replies
    11
    Views
    674

    Beacon Tech, Why not submit your "question" here...

    Beacon Tech,
    Why not submit your "question" here or even in the Pro Controls forum.
    As long as it's not something to do with a warranty issue or software (buying/fixing/selling) you might be amazed...
  7. kwaichang, First guess is that , in the case of...

    kwaichang,
    First guess is that , in the case of the N2 translation, both BD's are setup as State-0 and State-1 on the N2 side. Based on recent problems with N2 to BACnet translations the Translator...
  8. Replies
    2
    Views
    322

    Delta eBMGR IP Address

    Having almost no exposure to Delta stuff I have a question:

    Can the IP address of an eBMGR be changed without any special software ?

    I have a customer that want to "See" the eBMGR on their Ax...
  9. dave1234, To address a few things that many may...

    dave1234,
    To address a few things that many may not be aware of. These are not "Absolute truth" but based on personal experience.
    1. The AS-CVTPRO100-0 does not work correctly with Win XP-Pro. The...
  10. Replies
    2
    Views
    343

    Aircooled81, We will use 1/4" up to about 250'...

    Aircooled81,
    We will use 1/4" up to about 250' total length. Over 250' we increase to 3/8". Most of the time we will locate the Transmitter (transducer) near the sensing point (and use 1/4") and run...
  11. Replies
    9
    Views
    624

    HenryHub, Do you have a Network Input called...

    HenryHub,
    Do you have a Network Input called "HTG-EN" in your PCV ? It looks like you have "HTG Enabled" mapped as an Enum Writable and it may not be a "Writable" point in the PCV.
    Usually there is...
  12. Replies
    42
    Views
    2,486

    brooke, alaya is doing the same thing but...

    brooke,
    alaya is doing the same thing but offering a referral fee (reward ?).

    Before anyone will dive into this thing you should provide a bit of background on why you chose the HVAC industry and...
  13. tridiumtech, If that is the Niagara Workbench...

    tridiumtech,
    If that is the Niagara Workbench Guide I think you customized (possibly mentioned elsewhere) I would also like a copy. Email in profile.

    Thanks,
  14. Replies
    28
    Views
    1,812

    Not to hijack the thread but... We are getting...

    Not to hijack the thread but...
    We are getting "Twangled up with Ternimology"

    Many times when someone refers to "CT's" they actually mean Current Switches (CS's). Properly applied, CS's can be...
  15. Replies
    62
    Views
    3,155

    Unlike here, when most people ask that question...

    Unlike here, when most people ask that question (people with college degrees) I tell them:

    I have a B of S from SHK (a Bunch of sh!! from School of Hard Knocks), an ME from SOC (Masters Equivalent...
  16. Replies
    12
    Views
    688

    gazoo, You have now learned the lesson the hard...

    gazoo,
    You have now learned the lesson the hard way. Glad you got it back together.
    My motto: Backup first, backup frequently, backup finally. 2nd corollary , Archive in 3 places (minimum).
  17. Replies
    3
    Views
    331

    nocomply65, Go here...

    nocomply65,
    Go here http://cgproducts.johnsoncontrols.com/default.aspx?main.aspx&2 and look up FX Supervisory Controller Installation Instructions for the basics. Most everything is documented there...
  18. Replies
    20
    Views
    975

    C0ntr0ls, Something I just learned about...

    C0ntr0ls,

    Something I just learned about recently is problems related to tuning policies. Check to see what your "Default Policy" is. Create your own that look something like attached and see what...
  19. Replies
    7
    Views
    620

    apprentice3, Recommended way to "Scan" for...

    apprentice3,
    Recommended way to "Scan" for devices is to Use HVAC-Pro and connect directly to the N2 bus and do a "Controller Information"/ "All Devices".

    You should not have any issues with the...
  20. Thread: Malware

    by Cagey57
    Replies
    217
    Views
    8,869

    Robb M, Dad (Lusker, I still like that better) ...

    Robb M, Dad (Lusker, I still like that better)

    Tons of thanks. Tell the Big boss you should get a raise !
  21. Replies
    6
    Views
    556

    ::DD: LMHO, It always is .....until we prove...

    ::DD:

    LMHO, It always is .....until we prove otherwise !
  22. Thread: Malware

    by Cagey57
    Replies
    217
    Views
    8,869

    Win7/32 Firefox 37.2. Login goofy earlier...

    Win7/32 Firefox 37.2.
    Login goofy earlier (before noon), works now.
    No like /Dislike buttons. Don't use much of the embed pictures and other frills.
    Keep getting the "Badware" due to Google...
  23. Replies
    18
    Views
    1,374

    NSSF, I could be totally wrong here but I don't...

    NSSF,
    I could be totally wrong here but I don't ever remember being able to command DO's in a DX9100 directly. To do so the DO had to be connected to a DCO in the program (in the DX9100) and they...
  24. Thread: HVACPro Help

    by Cagey57
    Replies
    14
    Views
    640

    smakdown61/s2sam, I am a bad example. My Win7...

    smakdown61/s2sam,
    I am a bad example. My Win7 laptop has a 9pin serial port and I am running 3 or 4 XP machines. All I can offer is that every other (not my own) laptop I have used the Edgeport/1 on...
  25. Thread: HVACPro Help

    by Cagey57
    Replies
    14
    Views
    640

    smakdown61, As I remember it 8.08 AND the "B"...

    smakdown61,
    As I remember it 8.08 AND the "B" patch addressed all of the issues with XP-Pro as well as the USB-Serial converters.

    There will never be another version after 8.08B so might as well...
  26. Thread: HVACPro Help

    by Cagey57
    Replies
    14
    Views
    640

    smakdown61 Pretty sure you need HVAC-Pro 8.08...

    smakdown61
    Pretty sure you need HVAC-Pro 8.08 with the "B" patch to make a connection via the Zone Bus. Leave the speed at 9600 on your 'Serial' setting, software will adjust itself for proper...
  27. We did some work at one of the Vestas Blade...

    We did some work at one of the Vestas Blade Plants. I asked how much a Wind Mill/Turbine cost and was enthuiastically told "Only about a Dollar a watt". The smallest one they made was 1.3 mega watts....
  28. nocomply65, Welcome. Now then, let me say that...

    nocomply65,
    Welcome.
    Now then, let me say that the single most difficult (and frequently omitted) concept to learn in "Controls" is that a complex controls system is supposed to operate a typically...
  29. Replies
    2
    Views
    247

    LY9100, Ask the Moderators to move this to...

    LY9100,
    Ask the Moderators to move this to controls. You'll get answers there for sure.
  30. yongyi, Here are a couple items for you, 1....

    yongyi,
    Here are a couple items for you,
    1. Integrate Voice to text into a point of sale invoice with Credit card swipe for on the spot payment.
    2. Get the utility companies to offer rebates for...
  31. Replies
    9
    Views
    755

    maliswa, JCI has a document on how to use 4...

    maliswa,
    JCI has a document on how to use 4 sensors in a "Series-Parallel Wiring" method. go here http://cgproducts.johnsoncontrols.com/met_pdf/244034107.PDF. It is on the bottom of page 5. It...
  32. Replies
    15
    Views
    1,087

    fisha, Dumb question, do you have a 3-wire or a...

    fisha,
    Dumb question, do you have a 3-wire or a 2-wire communication line ? If you have a 3-wire and you connected the Ref/Common at the PT link-2 try disconnecting it from the terminal on the...
  33. Replies
    11
    Views
    1,156

    Andrew, The biggest issue, in my mind, with...

    Andrew,
    The biggest issue, in my mind, with using the pid-preprocessor is that it only provides the 2 things I strive for (predictability and repeatability) about 70% of the time. See the attached...
  34. just_opinion, I would suggest contacting your...

    just_opinion,
    I would suggest contacting your distributor and purchasing the Upgrade version (since you already have 8.04) of the MTOOLS software. The part number for the "Upgrade" is MW-MTOOL-6....
  35. Replies
    17
    Views
    3,502

    Wrenchspinner, See notes above in red. I...

    Wrenchspinner,
    See notes above in red.

    I haven't done the PCA3611 yet, they put them on engineering hold so I had to use a PCG2611/PCX4711. I have also replaced AS-VAV1xxx's, AP-VMA1400's,...
  36. Replies
    31,522
    Views
    1,828,370

    Poll: Bret is so tough, he probably just laugh's when...

    Bret is so tough, he probably just laugh's when they show up with a needle. He would probably fall asleep while they were inking his noggin' !

    Doug's post said something about "shaved head, tattoo...
  37. Replies
    6
    Views
    732

    Igotworms, Can you set the VFD input to 0-10VDC...

    Igotworms,
    Can you set the VFD input to 0-10VDC and then change the Output from the Controller to 0-10 VDC ?

    To run both drives from a single 4-20mA signal I think you may have to wire in series...
  38. Replies
    31,522
    Views
    1,828,370

    Poll: Kojack (Bret), How about this design ? Still...

    Kojack (Bret),
    How about this design ? Still praying !!!!!!!

    http://40.media.tumblr.com/7bdb70a4da83f6288a1f99250b4ab489/tumblr_nqhrvag77g1s13c11o1_540.jpg

    Or This one for Karen,...
  39. Replies
    31,522
    Views
    1,828,370

    Poll: Bret, Still praying for you and your family. Too...

    Bret,
    Still praying for you and your family. Too far to drive to mow your lawn or trim the trees :D
    Don't forget, next time you (and your family) are in Colorado you gotta punch this lunch ticket....
  40. Replies
    14
    Views
    999

    amigo, I haven't worked with the VRV components...

    amigo,
    I haven't worked with the VRV components yet. I'll do some research and see what I can find out.
  41. Replies
    14
    Views
    999

    Based on past experience: The Microtech III...

    Based on past experience:
    The Microtech III RTU's and Chiller work well on BACnet IP. You have to have the Tech Lit with the point definitions to decipher the names after you discover the points....
  42. Thread: Leaky Pipes

    by Cagey57
    Replies
    7
    Views
    719

    ROTFLMHO ! Now that's funny ! As far as...

    ROTFLMHO ! Now that's funny !

    As far as failure in one area and not another. Look at water chemistry and electrolisys, just sayin.
  43. Replies
    5
    Views
    678

    stanbyyourword, That is not a uncommon...

    stanbyyourword,

    That is not a uncommon situation. I usually refer to "extract" as Exhaust but on many systems that do not have building pressure control that is a typical application. It is not...
  44. Replies
    13
    Views
    1,894

    TheOne447, Welcome to the forum. Maybe add an...

    TheOne447,
    Welcome to the forum.

    Maybe add an email to your profile, contribute to 1 or more discussions on the forum, possibly apply for pro membership and you will likely get welcomed and some...
  45. Replies
    13
    Views
    1,894

    dapper, Just saw this. The Part Number/Order...

    dapper,
    Just saw this. The Part Number/Order code MW-MTOOL-6 specifies an Upgrade to the most current version (rather than a new, first time order) at the time of the order. I have MTOOL-6 for...
  46. Replies
    1
    Views
    377

    oxford, If I remember correctly the TMZ1600...

    oxford,
    If I remember correctly the TMZ1600 communicates on the Zone Bus and if you try to command or override the "Setpoint" for the VMA you create a conflict. First clear any Fallback in the point...
  47. Replies
    9
    Views
    1,614

    hueyman, Interesting question that I never...

    hueyman,
    Interesting question that I never considered.
    As reaper mentioned, I can see where BACnet (via an IP to MS/TP router) would work and LON via an FTT (?) adapter would also. I couldn't tell...
  48. fisha, Based on recent experience with AAON and...

    fisha,
    Based on recent experience with AAON and the Orion PT-Link 2 those point are dependent on how the OEM controls are actually setup by the Start up Tech.

    Do a search for "Orion PT-Link 2"...
  49. Replies
    10
    Views
    984

    Tameda, To add to billcontrols comments, a Good...

    Tameda,
    To add to billcontrols comments, a Good Contractor is the key element in this adventure. PMI runs correctly on XP-Pro 32bit.

    As an interim measure I suggest you obtain an XP-Pro machine...
  50. Gamecocksc, First you have to establish if it is...

    Gamecocksc,
    First you have to establish if it is a "Thermostat" or a "Sensor" for us.
    If in fact it is a thermostat you should be able to run up to 100' of stranded 18 gauge multi-conductor plenum...