  1. Replies
    7
    Views
    1,595

    The Common to Start winding was 2.1 ohms, the...

    The Common to Start winding was 2.1 ohms, the common to Run was .7 ohms. Run to Common was 2.8,2.9..The Run winding bounced around some each time I ohmed it out. The rated RLA was 24Amps. I cant...
  2. Replies
    7
    Views
    1,595

    compressor analyzer

    Thanks. I appreciate your input. Ill look into getting a compressor analyzer. I've only been using a meter to check compressors.
  3. Replies
    7
    Views
    1,595

    relay/compressor

    It doesn't necessarily matter which took out which, they were bad and i replaced them. My main question was can compressor windings be bad but yet not give a definitve open winding when ohmed out? Is...
  4. Replies
    7
    Views
    1,595

    Danfoss 1/4HP Compressor

    Im looking at a Walk-in cooler condensing unit that has a Danfoss 1/4hp compressor. The condensing unit is outside and the crankcase heater blew. It took out the contactor and starter relay as well....