  1. Replies
    4
    Views
    210

    The PXM-AI8 is just a point expansion module that...

    The PXM-AI8 is just a point expansion module that can have up to 8 analog inputs. There are no "points" or application in it. It is just an I/O device with no internal smarts.

    The field panel goes...
  2. Replies
    4
    Views
    232

    The modules you show in the picture are analog...

    The modules you show in the picture are analog output pnuematic. The light on these modules is an actual feedback of the output pressure sensed in the line. If you do not have a supply line hooked...
  3. If you have an integration panel on the site,...

    If you have an integration panel on the site, (modbus, bacnet, etc), then sunrise and sunset are built into the diagnostic point. All you have to do is enter you Lat and Long.

    Otherwise, here is...
  4. Thread: TEC ?

    by Daramoe
    Replies
    2
    Views
    300

    After the tec has been through a calibration...

    After the tec has been through a calibration cycle,
    Then
    (Balancer CFM reading / TEC CFM reading) * Old Flo Coeff
  5. Thread: Siemens PXM10S

    by Daramoe
    Replies
    4
    Views
    463

    What firmware revision is your panel? The PXM...

    What firmware revision is your panel? The PXM display is only supported on some of the new firmware.
  6. Replies
    4
    Views
    331

    Speaking of logic, I missed one in the example....

    Speaking of logic, I missed one in the example. You will need to add the 50, 41 to the end of the last table statement, or you will not get readings between 40 and 50.
  7. Replies
    4
    Views
    331

    Break it into 2 table statements IF (HA08CV...

    Break it into 2 table statements

    IF (HA08CV .GE. 50.) THEN TABLE(HA08CV,HA08GP,50,41,60,53,70,63,80,74,90,75) ELSE TABLE(HA08CV,HA08GP,0,0,10,1,20,7,30,17,40,27)
  8. What I think you are looking for is Slope and...

    What I think you are looking for is Slope and Intercept. Coefficient is the term used to adjust the CFM flow readings to the air balancers readings.

    That being said, while the app you are using...
  9. It's a little to involved to try to explain in a...

    It's a little to involved to try to explain in a forum (IMO). Your best bet would be to get a Apogee Field Panel Users manual. There is a very good chapter in there that explains enhanced alarming in...
  10. Replies
    6
    Views
    424

    More then likely, either there is a name...

    More then likely, either there is a name resolution issue between your client PC and the server (host file not setup if static IPs, or DNS server does not have all of the info properly registered) ,...
  11. If you know how, you can change the alarm to an...

    If you know how, you can change the alarm to an enhanced alarm, and use the schedule point as the mode point in your alarm setup.
  12. Replies
    5
    Views
    873

    The damper command point will stay in OVRD, and...

    The damper command point will stay in OVRD, and the TEC will do the calibration procedure normally, as it doesn't command the damper command. However, as the damper command is a calculated point, the...
  13. Replies
    3
    Views
    1,250

    Chapter 5 of the field panel users manual deals...

    Chapter 5 of the field panel users manual deals with nothing except the point database, and has a table going into detail on each of these points.
  14. Sounds like a trend buffer full upload. I would...

    Sounds like a trend buffer full upload. I would guess that somebody who didn't understand what they are doing, used the trend wizard to add all the points in the system in trend, and one of the...
  15. Replies
    1
    Views
    376

    Just a combination of resolution of the a-d...

    Just a combination of resolution of the a-d converter, and the auto scaling of the commander box. You didn't say what the range of the controlled device is, 0-10, 2-10, 4-20ma, etc). As to it showing...
  16. Replies
    3
    Views
    737

    The 535-741 is an 100K thermistor. The point...

    The 535-741 is an 100K thermistor. The point expansion module only supports 1K RTD (375 type) , 0-10 VDC and 4-20ma for inputs.
  17. Replies
    8
    Views
    1,740

    Are these wireless FLNs?

    Are these wireless FLNs?
  18. Replies
    3
    Views
    733

    I would suspect that it is not that the Point Exp...

    I would suspect that it is not that the Point Exp Block does not support LPACIs, but more that it does not support being on the FLN. The original Point Exp Blocks could only exist on the MEC...
  19. Replies
    5
    Views
    1,041

    If you upgrade your panels to 3.2 firmware, this...

    If you upgrade your panels to 3.2 firmware, this is a BTL certified firmware. The siemens panel at that time is a native bacnet device.
    There will have to be a database conversion done at the same...
  20. Replies
    5
    Views
    1,041

    The PX controllers can be flashed from 2.x...

    The PX controllers can be flashed from 2.x firmware to the bacnet firmware 3.2
    If the MECs and MBCs are Power MECs and MBCs, and are the ethernet variety (they have an ethernet port) then they can...
  21. Replies
    4
    Views
    884

    What revision of Insight What is the panel type...

    What revision of Insight
    What is the panel type and firmware listed in system profile.

    Your slope and intercept calculates out to 125 = 0 volts 0 = 10 volts, so I am assuming you are hooking up a...
  22. Replies
    34
    Views
    11,758

    For the PXC 24: Part Numer PXC24.2-PEF.A or ...

    For the PXC 24:
    Part Numer PXC24.2-PEF.A

    or

    For the PXC 36:
    Base Panel
    Part number PXC36-PE.A
    P2, 36 points
  23. Replies
    34
    Views
    11,758

    For which one? In each of the controllers, the P2...

    For which one? In each of the controllers, the P2 and the bacnet are different part numbers as they are different firmware loads.
  24. Replies
    34
    Views
    11,758

    The PXC Modular, the PXC 36, and the second...

    The PXC Modular, the PXC 36, and the second generation of the PXC 24 ( the one that has both a 485 and an ethernet connection on it) can be used as an AEM with the correct license. That means that...
  25. Thread: Siemens FLN

    by Daramoe
    Replies
    4
    Views
    1,218

    The database of the UCs can be backed up in...

    The database of the UCs can be backed up in system profile. The UCs have an EEprom just like the TECs, so it usually takes physical or electrical damage to get to the point that you need to replace a...