  1. Replies
    20
    Views
    967

    they are r 6.0 ducting but like i said no air...

    they are r 6.0 ducting but like i said no air leaks so far.
  2. Replies
    20
    Views
    967

    Thats the first thing I did. He asked me if the...

    Thats the first thing I did. He asked me if the original installer added any freon. I said no. He checked it with his gauges to see if charge was off and added some freon said the air was not cold...
  3. Replies
    20
    Views
    967

    the ducts are flex ducting R 6.0 so maybe I am...

    the ducts are flex ducting R 6.0 so maybe I am undersized a bit. I checked for leaks everything looks good and ok. The air is coming out of the vents and the furnance is set for 3.0 blower speed...
  4. Replies
    20
    Views
    967

    Yeah the unit runs constantly never shuts down...

    Yeah the unit runs constantly never shuts down and can not cool the house down past 79 degrees with the windows all closed. I highly doubt a smaller unit would do the trick this almost makes me wish...
  5. Replies
    20
    Views
    967

    Thats good because I would rather be oversized...

    Thats good because I would rather be oversized than undersized. I live in california in the los angeles area. The house has an open beam ceiling so most the installers suggested 3 tons because of...
  6. Replies
    20
    Views
    967

    Do you think I maybe undersized? I had 5 bids 3...

    Do you think I maybe undersized? I had 5 bids 3 out of 5 told me a 3 ton system. Only one said 4 ton the other said 2.5 ton. So I dont know who to call.
  7. Replies
    20
    Views
    967

    help with system possible ducting.

    Hello I have a 3 ton goodman system. Its cooling aprox 1200 square feet. My contractor has his duct work set up with 2 main branches. The main branch whiches goes to the bedrooms is 12 inch round...
  8. Replies
    38
    Views
    2,949

    You guys where right about the blower speed it...

    You guys where right about the blower speed it was set to high which is 4 ton cooling. How does this effect my system. The manual says for 3 ton cooling set blower speed to medium low.
  9. Replies
    38
    Views
    2,949

    Thanks for the reply yes I am sure. What effect...

    Thanks for the reply yes I am sure. What effect would this have on the system your right about the tvx just screwing on under it is the orrifice. Should I have it removed right away? Or can it wait?
  10. Replies
    38
    Views
    2,949

    Help with Goodman Unit TVX / ORRIFICE?

    Hello I have a 14 seer 3 ton goodman unit that has a 4 ton blower and 4 to 5 ton coil. My installer installed a TXV on the unit but didnt not take out the factory oriffice flow rater from the unit....
Results 1 to 10 of 10