    It's interesting you brought up the bridge...

    It's interesting you brought up the bridge comment for that was something I questioned. Your instructions said to set the mode to bridge. The option under mode was temporary bridge, under type there...
  2. Replies
    23
    Views
    2,210

    When in the configured router mode I was able to...

    When in the configured router mode I was able to discover and commision both Honeywell spyders and XL10 products but all downloads failed. I tried everything I could think of but could not get...
  3. Replies
    23
    Views
    2,210

    After restarting the platform the router was able...

    After restarting the platform the router was able to register with the station. I was than able to discover new devices and commision them but was unable to download to anything. I set the dip...
  4. Replies
    23
    Views
    2,210

    I got back in town today and was exited to find...

    I got back in town today and was exited to find my loytec LIP-3333ECTB had arrived. The Jace 700 is not here yet so I tried to set it up running the station on my PC. The instructions form Lane where...
  5. Replies
    23
    Views
    2,210

    After a lot of research I have decided to use the...

    After a lot of research I have decided to use the loytec LIP-3333ECTB as Digo sugested. I am strugling to find instruction on proper setup of the Lon/Ip for the Jace. If anyone has tips on the loytec...
  6. Replies
    23
    Views
    2,210

    I have a couple jobs where I have about 100 VAV...

    I have a couple jobs where I have about 100 VAV spyders running on Jace 600's with on lone card and a router configured as a repeater. They are working great, the 700 has way more memory and a much...
  7. Replies
    23
    Views
    2,210

    There is a limit of 64 per lon segment with a...

    There is a limit of 64 per lon segment with a repeater you can get 128(less 1 for the local lon device) per Lon card. I am not sure how it works if I where to install a 4 segment router.
  8. Replies
    23
    Views
    2,210

    Jace 700 with large lon network

    I have a job with 200 van boxes and 6 trane intellipaks. I am planning to use a tridium jace 700 with Lon spyders for the 200 boxes. This will make for a larger Lon system than I am used to working...
  9. Replies
    14
    Views
    2,054

    I went to the Honeywell Bacnet spyder training...

    I went to the Honeywell Bacnet spyder training class when they first came out a couple of years ago. This contributed to my confusion on this project. Honeywell did some things with the spyder that...
  10. Replies
    14
    Views
    2,054

    I was able to get the Poll frequency turned down...

    I was able to get the Poll frequency turned down and it seems to have resolved much of my resource issues.
    I am struggling with shared points. In the workbench if you have a Lon network you can...
  11. Replies
    14
    Views
    2,054

    Bacnet Bindings

    I am in the middle of my first Bacnet integration. Bear with me for I am new to bacnet. I am installing a Jace 700 on an existing Alerton system of approximately 90 VLC controllers(1/4 load each)
    I...
  12. Thread: York Elink

    by kempkerr
    Replies
    9
    Views
    1,826

    The chiller is supposed to have a Lon Elink card...

    The chiller is supposed to have a Lon Elink card factory installed. The chiller is a few weeks out. What I was hoping to find is a AX jar file to allow me to progam the job.
  13. Thread: York Elink

    by kempkerr
    Replies
    9
    Views
    1,826

    I was hoping to get this programmed and ready...

    I was hoping to get this programmed and ready when the chiller arrived. This is a smaller chiller but it does have an option for connecting to a remote optiview pannel. I didnt know if that allowed...
  14. Thread: York Elink

    by kempkerr
    Replies
    9
    Views
    1,826

    York Elink

    I am needing to connect to a York YLAA chiller supplied from factory with a LON card. I understand York calls there comm board "ELINK". I am using Niagara-ax. There is a jar file under the York...
  15. Replies
    109
    Views
    9,771

    The blunt of my work leans toward comfort as...

    The blunt of my work leans toward comfort as apposed to energy savings. I seldom reset the static pressure but I do believe there is savings to be had. For comfort I reset the discharge air...
  16. Replies
    1
    Views
    437

    In the points folder of the venom apps ther is a...

    In the points folder of the venom apps ther is a String writable block labeled "graphic tag" this is linked to all histories extentions within the folder. If you change the history name at the...
  17. Replies
    1
    Views
    437

    Jace History Name change

    I have two sights I have programed using John Hutchy's Vav Venom Apps. They seem to work great my only problem is after I get all the controllers added to the program I find the history extentions...
  18. Replies
    4
    Views
    477

    Thats the thing I am not, I have some logic that...

    Thats the thing I am not, I have some logic that is linked to this nci. About twice a year the value will change. Is this the only time the nci will update or will it update continuosly becouse I...
  19. Replies
    4
    Views
    477

    webs ax nci and flash memory

    On the lon network in AX, if you link to a NCI point will the program write to this point periodically or only on a change in value . The lonworks documentation claims you have to initiate an action...
  20. Thread: Bacnet spyder

    by kempkerr
    Replies
    12
    Views
    1,871

    Just got back from the training class. Great...

    Just got back from the training class. Great course!
    Same spyder programming a few differences in how you handle network points, all in all very little diference.
  21. Thread: Bacnet spyder

    by kempkerr
    Replies
    12
    Views
    1,871

    Bacnet spyder

    I am going to a training class on honeywell's new bacnet spyders. I have done a lot of work on Lon controls but very little bacnet. I was hopeing to start a discussion about advantages and...
  22. Replies
    7
    Views
    556

    Thanx guys I am sure this will resolve the problem

    Thanx guys I am sure this will resolve the problem
  23. Replies
    7
    Views
    556

    Yes it is setup as a VAV unit, the reference...

    Yes it is setup as a VAV unit, the reference sensor is space temp, and no alarm message.
  24. Replies
    7
    Views
    556

    I have a space temperature bound to the unit. The...

    I have a space temperature bound to the unit. The intellipak will enter and leave the warmup mode when I raise and lower the setpoint, it just wont start the strip heat. I am not even sure it worked...
  25. Replies
    7
    Views
    556

    Intellipak integration

    I have a sight with two intellipak units and 16 VAV boxes. I have installed a jace 600 and brought everything in. Everything was going well until I attepted to start the warmup heat in the...