Search:

Type: Posts; User: digo

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. I'd ask for clarification, perhaps they could...

    I'd ask for clarification, perhaps they could provide you with an IP rating instead
    http://www.cctvco.com/NEMA-IP-ingress-protection-explained.html
  2. Replies
    2
    Views
    128

    bingo. I know it sucks, but I bet you won't make...

    bingo.
    I know it sucks, but I bet you won't make that mistake again.
  3. Replies
    14
    Views
    417

    So you're pulling in 15 stations into an existing...

    So you're pulling in 15 stations into an existing supervisor, that was not provided and licensed by you. Is that correct? Are they going into fault?
  4. Replies
    14
    Views
    417

    A single JACE

    A single JACE
  5. Replies
    14
    Views
    417

    No device limit

    No device limit
    <feature name="niagaraDriver" expiration="never" virtual="true" schedule.limit="none" point.limit="none" history.limit="none" device.limit="none"/>

    Small building limited to 3...
  6. Replies
    28
    Views
    5,128

    while Mr. bigguy158 stayed in Controls (Green Bay...

    while Mr. bigguy158 stayed in Controls (Green Bay area?) working with big blue, and occasionally going for bike rides? btw, how's the solar setup at the cabin going?
    Indeed google is scary.
  7. Thread: EC BOS ?

    by digo
    Replies
    4
    Views
    157

    Or the sticker under the cover

    Or the sticker under the cover
  8. Thread: EC BOS ?

    by digo
    Replies
    4
    Views
    157

    License Manager, next to hostid

    License Manager, next to hostid
  9. Did you look in the AxCommunity.jar? In the...

    Did you look in the AxCommunity.jar?

    In the math palette they have an AbsTimeOffset object that can be used to subtract a time offset in seconds

    3.6 and newer will automatically convert the...
  10. Replies
    9
    Views
    504

    To clarify, if designed one way or the other it...

    To clarify, if designed one way or the other it shouldn't matter. I'm not advocating running the wheel opposite from the direction the manufacturer intended.
  11. Replies
    9
    Views
    504

    I'd be willing to bet it doesn't matter....

    I'd be willing to bet it doesn't matter. Regardless of the direction the wheel spins, you still achieve the heat exchange/recovery between EA/OA and RA/SA.
  12. See this thread:...

    See this thread:
    http://hvac-talk.com/vbb/showthread.php?1244511-Trane-BCI-C-(BACnet)-UC400-Questions

    Tracer BACnet Setup Tool 3.0:
    http://software.trane.com/GCC/BST.Setup.3.0.74.exe
  13. Yeah, I'd set them to null and not proxy those...

    Yeah, I'd set them to null and not proxy those points.
    TUNCOS is used to ramp the unoccupied setpoint toward the occupied setpoint based on a specific ramp rate. I know with the CVAHU controller...
  14. Use nviTodEvent for scheduled occupancy. I...

    Use nviTodEvent for scheduled occupancy. I believe the nviOccCmd is meant to share occupancy sensors accross multiple VAVs.
    When the wall module is configured with a bypass button, pressing the...
  15. Thread: BBMD vs VPN

    by digo
    Replies
    43
    Views
    3,535

    When I get back to the office on Tuesday I'll...

    When I get back to the office on Tuesday I'll check on the uptime of my WRT54GL and let you know the last time it rebooted. Monthly reboots aren't caused by crappy hardware, they're caused by buggy...
  16. Thread: BBMD vs VPN

    by digo
    Replies
    43
    Views
    3,535

    I guess I haven't bought on of those in a...

    I guess I haven't bought on of those in a while... I agree with you on Belkin. Anything found on the same isle as monster cables at best buy can't be good.
  17. Thread: BBMD vs VPN

    by digo
    Replies
    43
    Views
    3,535

    Linksys was aquired by Cisco long ago. Most would...

    Linksys was aquired by Cisco long ago. Most would agree they're a reputable manufacturer, albeit sometimes the priciest in the enterprise arena. The WRT54GL model was one the best routers in the...
  18. Replies
    4
    Views
    301

    This is old but it explains the sequence in...

    This is old but it explains the sequence in detail: http://support.microsoft.com/kb/124036
  19. Replies
    2
    Views
    306

    Exchange 2013?...

    Exchange 2013?
    http://blog.kloud.com.au/2013/11/22/exchange-2013-dns-settings-cause-transport-services-to-crash/
  20. Replies
    299
    Views
    32,012

    Any protocol at layer 2 (data link layer) is...

    Any protocol at layer 2 (data link layer) is inherently non-routable. ARCnet, ATM, Controller Area Network (CAN), Ethernet, Fiber Distributed Data Interface (FDDI), Frame Relay, LocalTalk,...
  21. Replies
    32
    Views
    4,109

    What up Kirk! So you're saying you don't miss...

    What up Kirk! So you're saying you don't miss working with spudders? [emoji1]
    Hope all is well with you man.
  22. Replies
    32
    Views
    4,109

    wow, if their panel looks like this, imagine the...

    wow, if their panel looks like this, imagine the wire sheet on those spyders... definitely wall of shame contender.
  23. Replies
    1
    Views
    196

    Use the file transfer client to copy it from the...

    Use the file transfer client to copy it from the modules folder in the JACE to your 3.7.106 modules
  24. Thread: AX Histories

    by digo
    Replies
    2
    Views
    349

    Start indicates the time it began collecting,...

    Start indicates the time it began collecting, like after a reboot
  25. Replies
    2
    Views
    396

    Strykers are configurable (ASC), Spyders are...

    Strykers are configurable (ASC), Spyders are fully programmable. Either way, you have to proxy your points and create your own graphic template before duplicating them. Both are licensed products. ...
  26. Assuming you dragged...

    Assuming you dragged WeatherService/WeatherReport/Current to a Px page, change the "tempFont" property to 0.0pt, then use a separate bound label to display your own temperature value.
  27. Yes, it's called fox tunneling.

    Yes, it's called fox tunneling.
  28. Thread: Niagara AX?

    by digo
    Replies
    2
    Views
    331

    Paste special gives you the option to retain...

    Paste special gives you the option to retain existing links
  29. Thread: 24vac signal amp

    by digo
    Replies
    5
    Views
    414

    Never

    Never
  30. Thread: 24vac signal amp

    by digo
    Replies
    5
    Views
    414

    Take a picture of it... any chance it's...

    Take a picture of it... any chance it's mislabeled?
    I can see an IDF room having of those CATV signal amplifiers in it. Maybe the 24V transformer is powering the signal amplifier?
  31. Take a look at the property sheet for the...

    Take a look at the property sheet for the LonNetwork, under Monitor you can disable the "Alarm on Failure" property which is a baja:Boolean slot. If you're running 3.6 or newer you shouldn't need a...
  32. Replies
    5
    Views
    635

    ":p" translates to a smiley on the forums :p

    ":p" translates to a smiley on the forums
    :p
  33. Replies
    12
    Views
    523

    Yeah, you're adding a slot, but you're supposed...

    Yeah, you're adding a slot, but you're supposed to edit the facets for the point.
    EDIT: you can get to it from the property sheet
  34. The rule is don't set it any higher than what you...

    The rule is don't set it any higher than what you need. We're talking physical memory here, not disk space. I can't imagine you have that much RAM on this machine. I've never needed to go higher...
  35. niagaraInstallfolder\lib\nre.properties (edit...

    niagaraInstallfolder\lib\nre.properties (edit with notepad while station is stopped)

    java.options=-Xmx256M -XX:MaxPermSize=128M -Dfile.encoding=UTF-8 -Xss256K

    Depending on what version you're...
  36. Replies
    4
    Views
    389

    It appears Honeywell sets these with a...

    It appears Honeywell sets these with a modifyFlag=mfgOnly
    I think these were meant to be modified via either their free LNS plug-in, or the lonhoneywellAXWizards (licensed module) only.
    In AX, the...
  37. Replies
    14
    Views
    1,314

    avoid spaces and dashes in component names, among...

    avoid spaces and dashes in component names, among others

    CTRL + L in workbench, paste this
    module://docUser/doc/aComponentNaming.html
  38. Replies
    4
    Views
    389

    I smell bull****... time to give them a call. ...

    I smell bull****... time to give them a call.

    The flow values you are referring to are stored in the W7751H as SCPTs, (Standard Configuration Properties)
    MinFlow = SCPT 54, offset 8, lenght 2...
  39. Thread: Lon Plug

    by digo
    Replies
    12
    Views
    825

    The ASP043 part number is for the spring clamp...

    The ASP043 part number is for the spring clamp version (SP04302VBNN)
    http://www.onlinecomponents.com/ria-connect-sp04302vbnn.html?p=43130834
  40. Replies
    17
    Views
    1,897

    Sorry guys, I've been MIA (or missing in the...

    Sorry guys, I've been MIA (or missing in the field) for a while.

    Here are the notes I have from the last time I had to set this up.
    Disclaimers: This is not a soup to nuts guide, but contains...
  41. Replies
    299
    Views
    32,012

    If you enjoy reading these long threads, this one...

    If you enjoy reading these long threads, this one is for you http://hvac-talk.com/vbb/showthread.php?t=134016
  42. Replies
    6
    Views
    612

    Might be 15 or more JACEs, he said 15 power...

    Might be 15 or more JACEs, he said 15 power supplies at each rack, which sounds like more than one rack.
    Anything industrial grade sounds ages better than the wall pack.
    Not to mention the cheap...
  43. Replies
    8
    Views
    705

    Home automation system from 1985

    Saw this post and wanted to share.
    http://imgur.com/a/Jb6jW

    Sent from my XT1058 using Tapatalk
  44. %out.value% Search niagara-central for help on...

    %out.value%
    Search niagara-central for help on Bformat, it's not very intuitive unless you dig into the API for a Bcomponent

    Sent from my XT1058 using Tapatalk
  45. Thread: best lap top

    by digo
    Replies
    30
    Views
    1,489

    Pretty sure all 4th gen core-i5 processors can...

    Pretty sure all 4th gen core-i5 processors can handle 64-bit instructions, I think you meant to say you are running a 32-bit OS. Upgrading the OS would allow you to address more than 4GB of RAM,...
  46. Thread: best lap top

    by digo
    Replies
    30
    Views
    1,489

    I did really well with my Dell D820 then. ...

    I did really well with my Dell D820 then. Purchased in early 2007 (about $1500 with docking station), retired in early 2014. During that time, I upgraded from the original 100GB HDD drive to a...
  47. Replies
    8
    Views
    804

    Which network management tool/front end? ...

    Which network management tool/front end?

    Niagara AX - lonhoneywellAXWizards (if your brand is Webs or Vykon)
    Echelon LonMaker - LNS Plugin (free, but requires an LNS database)
    HW Lonspec -...
  48. Replies
    21
    Views
    1,794

    I've been using the HVACR Fluke 116 + infrared...

    I've been using the HVACR Fluke 116 + infrared kit and with the T5-1000 (amp probe) for the last 9 years, and I feel it more than covers my needs for controls. Then again, I'm not responsible for any...
  49. Replies
    2
    Views
    289

    Wireshark...

    Wireshark

    http://layer3.wordpress.com/2009/11/29/tshootingwithwireshark/
    http://wiki.wireshark.org/CaptureFilters
    http://wiki.wireshark.org/Protocols/bacnet...
  50. Replies
    11
    Views
    650

    See this thread:...

    See this thread:
    https://community.niagara-central.com/ord?portal:/discussion/DiscussionThread/9398

    Also, see this one, it explains how the charging cycle/battery test is done:...
Results 1 to 50 of 1000
Page 1 of 20 1 2 3 4

Related Forums

Plumbing Talks | Contractor Magazine