Search:

Type: Posts; User: ahansen

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Replies
    2
    Views
    328

    I believe this happens when you have a fox/foxs...

    I believe this happens when you have a fox/foxs mismatch (such as the Sup is trying to communicate foxs to the fox port on the Jace).
  2. People know how much Nordstrom or Macy's is...

    People know how much Nordstrom or Macy's is paying for the merchandise in their store?
  3. Replies
    6
    Views
    564

    Yea, you do not understand. Kontrolphreak is...

    Yea, you do not understand. Kontrolphreak is correct, you need a forwarder such as no-ip. Most stats phone "home" (a cloud server), mobile apps hit that "home", not your thermostat.
  4. Replies
    3
    Views
    448

    I don't think the high busy time will slow you...

    I don't think the high busy time will slow you down. At 99%, I think it means it's having trouble polling everything at the configured rate.

    In your tuning policies, make sure max write time is...
  5. Replies
    3
    Views
    448

    Go directly to number 2, without looking at...

    Go directly to number 2, without looking at anything on number 1. Does the data still take a long time? If so, it isn't the Niagara Network.

    You could also add a simple writable point in number...
  6. Replies
    9
    Views
    1,200

    Help -> Help Contents -> Search Tab -> "alarm"

    Help -> Help Contents -> Search Tab -> "alarm"
  7. Replies
    3
    Views
    666

    Tridium ships with a "self-signed" certificate. ...

    Tridium ships with a "self-signed" certificate. You do not need a certificate signed by a top level authority for encryption, those are to prevent man-in-the-middle attacks.

    After the big...
  8. Replies
    2
    Views
    655

    FWIW - the Siemens Systems 600/Apogee HMI is...

    FWIW - the Siemens Systems 600/Apogee HMI is called Insight.
  9. Replies
    8
    Views
    1,027

    Funny, I just saw a demo of it today at a DR...

    Funny, I just saw a demo of it today at a DR conference. Has to do with transactive energy, they were demoing feeder pricing and sub-node load negotiation. Looks ivory tower, I'm not sure you'd...
  10. Replies
    14
    Views
    1,481

    www.controlco.com FWIW - I don't work there...

    www.controlco.com

    FWIW - I don't work there but used to.
  11. Thread: Honywell N4

    by ahansen
    Replies
    21
    Views
    1,572

    No, it's a month old. I never install the latest...

    No, it's a month old. I never install the latest version of anything. I've lost too much hair as it is.
  12. Thread: Honywell N4

    by ahansen
    Replies
    21
    Views
    1,572

    I've upgraded a few vendor's modules from AX to...

    I've upgraded a few vendor's modules from AX to N4 and I've developed a driver from scratch for N4. All-in-all, it's been pretty painless.

    Look, would you prefer they freeze AX with Java7 and...
  13. Replies
    71
    Views
    11,261

    Practically all Java is compiled to bytecode and...

    Practically all Java is compiled to bytecode and all java bytecode is interpreted. There are super rare exceptions to this, but I highly doubt AAM is doing anything different than Tridium. What do...
  14. Thread: Station lockup

    by ahansen
    Replies
    1
    Views
    540

    Go to the alarm service property sheet. You...

    Go to the alarm service property sheet. You should lower the "Capacity" property.

    The Alarm Db Maintenance view on the service will allow you to delete older records, but you'll just run into the...
  15. Replies
    71
    Views
    11,261

    Try pricing the two options, that is probably the...

    Try pricing the two options, that is probably the reason.
  16. I think you have to disable the driver on the...

    I think you have to disable the driver on the Jace before attempting to tunnel. So if you haven't already tried that...
  17. Replies
    6
    Views
    1,082

    oBIX is just another protocol. If your access...

    oBIX is just another protocol. If your access control system doesn't already talk obix, then it isn't going to work for you. FWIW, I wrote Tridium's obix driver.

    If the web interface is html...
  18. Replies
    6
    Views
    1,171

    People can develop, sell and deploy their own...

    People can develop, sell and deploy their own software on Niagara. The software ecosystem is constantly growing.
  19. Find out if your utility provider supports green...

    Find out if your utility provider supports green button (Google it). If so you can get your load profile directly from the source.
  20. I believe Maxline's Apogee driver for AX is P2.

    I believe Maxline's Apogee driver for AX is P2.
  21. Understanding the sequence of operations and...

    Understanding the sequence of operations and doing it "right" is the best way to go. However, it isn't always possible; most flash products are designed to withstand 100,000 - 1,000,000 writes.
  22. Jeremy is correct, it is slow. It takes 2.5s to...

    Jeremy is correct, it is slow. It takes 2.5s to poll a single point.

    If you need to trend 100 points, then your poll cycle is a little over 4 minutes.

    However, if all you need are points for...
  23. Replies
    9
    Views
    1,740

    Serial to ethernet adapter: ...

    Serial to ethernet adapter: http://www.digi.com/products/serialservers/digionesp#overview
  24. Replies
    26
    Views
    4,488

    FM - F'ing Magic

    FM - F'ing Magic
  25. Replies
    10
    Views
    2,937

    http://obix.tridium.com

    http://obix.tridium.com
  26. Replies
    14
    Views
    1,777

    I think Ebonix has one.

    I think Ebonix has one.
  27. Replies
    14
    Views
    1,777

    http://mlkshk.com/r/1BIF

    http://mlkshk.com/r/1BIF
  28. Replies
    4
    Views
    2,094

    Seimens part # 540-143

    Seimens part # 540-143
  29. Thread: Demand Meters

    by ahansen
    Replies
    8
    Views
    995

    I don't have domain expertise, I don't know what...

    I don't have domain expertise, I don't know what you mean by a 13,800 feed...

    But if you haven't already, check out the class 3000 meters from Emon which can go up to 3200 amps:
    ...
  30. Replies
    19
    Views
    2,461

    http://pub.controls.johnsoncontrols.com/publish/b2...

    http://pub.controls.johnsoncontrols.com/publish/b2b_aa/us/eng/abcs_exchange/facility_explorer/Webcasts.html
  31. Replies
    19
    Views
    2,733

    Tridium AX with the CSI3 System 600 Driver. The...

    Tridium AX with the CSI3 System 600 Driver. The driver is slow because it "screen scrapes" the VT100 MMI port, but it works.
  32. Replies
    12
    Views
    6,751

    CSI Cubed is incorrect / out of date (as is our...

    CSI Cubed is incorrect / out of date (as is our own website):

    Siemens Sys600 / Apogee
    Barber Coleman Network 8000
    Emon meters
    SMA inverters
    Particle Measuring Systems Airnet devices
    Any...
  33. Replies
    5
    Views
    1,029

    Was that a Jace?

    Was that a Jace?
  34. Get any and all software upgrades you can,...

    Get any and all software upgrades you can, especially the JCI modules.
  35. Thread: Salesman....

    by ahansen
    Replies
    8
    Views
    1,265

    Salesman...

    It is my sincere belief that progress is made when the consequences are not well understood. Understanding the human condition is far more important in sales.

    Welcome to the toolbox brother.
  36. Thread: Kw to kW Hours

    by ahansen
    Replies
    23
    Views
    2,385

    You're right. I wrote that formula backwards it...

    You're right. I wrote that formula backwards it should be (time / one hour) which equates to the number of hours.
  37. Thread: Kw to kW Hours

    by ahansen
    Replies
    23
    Views
    2,385

    I believe it's: (oneHour / (duration of poll...

    I believe it's:

    (oneHour / (duration of poll interval)) * (numPulses * pulseValue)

    The hour and interval need to be the same units (ie millis, seconds...)
  38. Thread: Facet help

    by ahansen
    Replies
    5
    Views
    694

    Off the cuff options: 1. Name your point...

    Off the cuff options:

    1. Name your point accordingly. Instead of Damper, how about something like Damper_Closed?
    2. In your graphics you can change the format of your value bindings. Normally...
  39. Digi

    IMHO - this is the best response. It is the only USB adapter that I have found that works with HVAC Pro. If your field-bus depends upon sub-100ms timing, this is the best option that I have found.
  40. Thread: WEB-MON ?

    by ahansen
    Replies
    7
    Views
    991

    And? How'd it work out?

    And? How'd it work out?
  41. Replies
    7
    Views
    812

    Is your AX box Windows? If so, maybe you can run...

    Is your AX box Windows? If so, maybe you can run a local exchange server that accepts smtp (only from localhost) and routes to the primary exchange server?
  42. Replies
    16
    Views
    1,380

    I haven't used this, but I've heard good things...

    I haven't used this, but I've heard good things about it:

    http://www.controlbyweb.com/webrelay/
  43. Replies
    8
    Views
    1,042

    If you can code: http://www.controlbyweb.com

    If you can code: http://www.controlbyweb.com
  44. Replies
    15
    Views
    2,084

    Oops, enforma.com is a mistake. archenergy.com...

    Oops, enforma.com is a mistake. archenergy.com is where you'll find the Enforma product.
  45. Replies
    3
    Views
    601

    In general, 'out' does not necessary mean the...

    In general, 'out' does not necessary mean the last written value. In several of the drivers I'm familiar with (PUP is not one of them), out reflects the last polled value.
  46. Replies
    15
    Views
    2,084

    Here's what I can come up with off the top of my...

    Here's what I can come up with off the top of my head. Not all of these have drivers, but they have all developed software products for Niagara AX:

    quicksilverintegrations.com
    activelogix.com...
  47. Replies
    7
    Views
    960

    http://hvac-talk.com/vbb/showpost.php?p=1861170&po...

    http://hvac-talk.com/vbb/showpost.php?p=1861170&postcount=5
  48. Replies
    5
    Views
    796

    The CSI3 GCM driver connects to GCMs or LCMs, you...

    The CSI3 GCM driver connects to GCMs or LCMs, you can't rip them out. It's a text based driver, it integrates with the VT100 HMI. It is not a speed demon.

    The timeout is two hours. Restart the...
  49. Replies
    2
    Views
    632

    Google "emon modbus point map". You don't need...

    Google "emon modbus point map". You don't need to convert anything, you can get kw directly from the meter.
  50. Replies
    3
    Views
    597

    Oh, sorry, it sounds like a bug in someone's...

    Oh, sorry, it sounds like a bug in someone's BACnet interface.

    Tridium has a System 600 / Apogee driver and while it is slow, if you use it exclusively for writes you'll be fine. I don't know if...