Search:

Type: Posts; User: The Reaper

Page 1 of 20 1 2 3 4

Search: Search took 0.06 seconds.

  1. Replies
    11
    Views
    578

    Hi Dave. Glad it worked out. Happy New Year!

    Hi Dave. Glad it worked out. Happy New Year!
  2. Replies
    3
    Views
    441

    Thanks. I tried everything and the problem...

    Thanks. I tried everything and the problem remained. I did a clean dist and that took care of it.
  3. I've done several jobs with the MicroNet VAV's....

    I've done several jobs with the MicroNet VAV's. They discover just like any other controller, but it is through the integrator which hangs on the ASD bus. No problems at all.
  4. Replies
    3
    Views
    441

    Niagara AX SSL Question

    I have to change a non ssl station to ssl. I went into the Web Service and set http to false, set https to true and https only to true. The Jace didn't like that and wouldn't allow the changes to...
  5. Replies
    11
    Views
    578

    I'm thinking it's the addresses 1,2,&3. I would...

    I'm thinking it's the addresses 1,2,&3. I would try changing them as a test.
  6. Replies
    11
    Views
    578

    The address 3 is the same address that the...

    The address 3 is the same address that the bluetooth uses. Address 1, 2, and 3 are reserved addresses with PCG's. I wonder if that could be causing issues. The fact that the Jace can be used as a...
  7. Replies
    11
    Views
    578

    What is the MAC of the controller?

    What is the MAC of the controller?
  8. Replies
    7
    Views
    439

    The only way I've ever done it is through the...

    The only way I've ever done it is through the software tool. Do you have a copy of XPSI?
  9. Replies
    7
    Views
    439

    I believe that there is a point that resides in...

    I believe that there is a point that resides in the controller that is a "clear override" point. That point needs to be toggled in order to release the override.
  10. Replies
    1
    Views
    537

    Update. I ended up making Network Inputs for the...

    Update. I ended up making Network Inputs for the setpoints and bound them into the logic. That worked for now.
  11. Replies
    1
    Views
    537

    PCV-1630 To NCE

    I'm having issues with some PCV's that I pulled into an existing NCE. Whenever I try to adjust or override a setpoint, I get an access denied error message. Has anybody seen this before? TIA.
  12. Replies
    4
    Views
    534

    Try changing the ping type from Version 8 to...

    Try changing the ping type from Version 8 to FF00;ID. The older pup controllers are not Version 8 compatible. This is only if they are bouncing offline randomly. If they just won't talk at all, start...
  13. Replies
    4
    Views
    534

    Are these controllers talking to a Jace?

    Are these controllers talking to a Jace?
  14. Replies
    9
    Views
    1,285

    I've done it with BACnet and Lon before. N2...

    I've done it with BACnet and Lon before. N2 should work fine.
  15. Thread: DMS 3500

    by The Reaper
    Replies
    1
    Views
    334

    You will need the DMS software to upload/download...

    You will need the DMS software to upload/download these controllers.
  16. Replies
    11
    Views
    926

    Hi Matrix. Back in the early FX days, they came...

    Hi Matrix. Back in the early FX days, they came out with a little hand held loader tool that could back up any legacy FX device. The program would be stored on the tool, but could not be edited by FX...
  17. Replies
    2
    Views
    356

    You will need a copy of FX Builder and FX CommPro...

    You will need a copy of FX Builder and FX CommPro for the protocol it is. These controllers cannot be uploaded, so if there are no backups onsite you are screwed. I've been in that spot before and...
  18. Replies
    5
    Views
    733

    Thanks

    Thanks
  19. Replies
    5
    Views
    733

    Change Station Name Tridium AX

    I hope there is an easy solution for this. My customer wants to change the name of the station on his system. This is WEBS 3.8. Will I have to rebind all of the graphics and redo all the trends or...
  20. Replies
    6
    Views
    433

    That's OK. Thanks for the help!

    That's OK. Thanks for the help!
  21. Replies
    6
    Views
    433

    Thanks. I'll give it a shot. Is it compatible...

    Thanks. I'll give it a shot. Is it compatible with Honeywell workbench?
  22. Replies
    6
    Views
    433

    Add Multiple Alarms in AX

    I need to add an out of range alarm extension to 200 points. I've been messing with the program service to no avail. Any suggestions? TIA.
  23. Replies
    7
    Views
    937

    I'm not a Siemens guy, but I have been AX...

    I'm not a Siemens guy, but I have been AX certified for 7 years and am fluent with a dozen different systems. I'm looking to relocate to the NC area. Shoot me an email with details. It's in my...
  24. Replies
    2
    Views
    425

    You just doubled your pay! Thanks JCIman!

    You just doubled your pay! Thanks JCIman!
  25. Replies
    2
    Views
    425

    Metasys ADS Display

    I logged into my customers site and I can't see any of the graphics. I have attached a screen shot. Any Ideas? TIA.
  26. Replies
    3
    Views
    453

    I have replaced the old MicroLite panels with the...

    I have replaced the old MicroLite panels with the Triatek lighting panels. I did an upgrade of an old NCM-200 and the MicroLite's wouldn't work. They are a proprietary N2. The Triatek's were very...
  27. Replies
    1
    Views
    547

    Barber Coleman Micro Net Room Sensor

    I got a call today for a Micro Net space sensor display being blank. I removed the sensor and metered it. There was no DC voltage. I traced the wire back and found it wired to the comm bus?? Has...
  28. I just use a B&B 232 to 485 convertor right to...

    I just use a B&B 232 to 485 convertor right to the ASD bus. Works every time.
  29. Replies
    2
    Views
    384

    You will need a licensed copy of Honeywell...

    You will need a licensed copy of Honeywell Workbench and the proper Spyder tool. Are these things stand alone or are they wired into a Jace?
  30. Replies
    6
    Views
    2,213

    Sorry! Just saw the date on this! Talk about...

    Sorry! Just saw the date on this! Talk about digging up an old thread!
  31. Replies
    6
    Views
    2,213

    Where in the Northeast are you? I have one in my...

    Where in the Northeast are you? I have one in my bag of tricks. I'm in CT.
  32. Replies
    6
    Views
    518

    Thanks for all the replies. This is for a VAV...

    Thanks for all the replies. This is for a VAV system with hot water reheats. I think ASHRE has something out there about this. I'll do some more digging.
  33. Replies
    6
    Views
    518

    Percentage Of Performance

    I have a customer that wants to calculate a percentage of system performance on individual heating zones. I am at a loss as to how to do this. Has anybody done something similar? TIA.
  34. Replies
    3
    Views
    822

    NAE Point Summary

    I'm upgrading some older NAE's to FX and I was wondering if there was a way to get a summary of all the points in the system with their mappings? This place has a lot of DX's and nobody left the tag...
  35. Replies
    1
    Views
    406

    I figured it out. I needed to put the file name I...

    I figured it out. I needed to put the file name I was transferring on the destination as well.
  36. Replies
    1
    Views
    406

    American AutoMatrix Sage Question

    I'm trying to use the Sage to copy a .plb out of a controller. I go to utilities, remote copy and set all the port/peer info and I keep getting an access denied error. Any ideas? Thanks in advance.
  37. Replies
    9
    Views
    2,366

    Email sent.

    Email sent.
  38. Replies
    1
    Views
    495

    Disregard. Blonde moment is resolved. I forgot...

    Disregard. Blonde moment is resolved. I forgot that you can use a switch with analog and boolean values.
  39. Replies
    1
    Views
    495

    Alerton BACtalk Programming

    I'm having a blonde moment! I'm trying to use a BV in the BTI to hit a bunch of BV's in different controllers. When the global BV is true, I need to write a false and when the global BV is false, I...
  40. Give this a try. I've had to do this a couple of...

    Give this a try. I've had to do this a couple of times.
  41. Replies
    3
    Views
    622

    Thanks alot Cagey!!

    Thanks alot Cagey!!
  42. Replies
    3
    Views
    622

    AX User Name = 2000:00

    I see the time changing in an FX70 and it logs the change under the user name 2000:00. Anybody know what that means? TIA
  43. Replies
    2
    Views
    592

    I think you're going to have to run it in a VM....

    I think you're going to have to run it in a VM. I'm pretty sure it's not compatible with Windows 8. The cheapest adapter I found is a B&B 232/485 convertor. They are less that 100 bucks and can be...
  44. Replies
    1
    Views
    461

    AutoMatrix Emailing Alarms

    I just took over a site with 8 SageMax controllers and an AutoPilot/WebPilot front end. The customer would like to receive alarms via email. Can this be done? I haven't worked on AutoMatrix since the...
  45. Replies
    1
    Views
    522

    Station Tunnelling

    I have a customer that has 6 Jaces and a supervisor. The supervisor IP isn't exposed to the outside world, but the first Jace ( pre supervisor ) is. Can I use the exposed Jace to tunnel to another...
  46. Replies
    1
    Views
    497

    I found out that I need a USB to SD convertor to...

    I found out that I need a USB to SD convertor to properly back these up. Does anybody know the proper size SD card? I remember that older operating systems such as these will not recognize anything...
  47. Thread: AAM GC1

    by The Reaper
    Replies
    1
    Views
    410

    Here is the GC manual. You are going to need a...

    Here is the GC manual. You are going to need a copy of SoloPro and a 232/485 converter to do anything with this controller. If there is a Sage onsite, you can do everything through that. If you can...
  48. Replies
    9
    Views
    870

    Thanks for the replies. The customer wants this...

    Thanks for the replies. The customer wants this live on his graphics continually displaying usage in his central plant. This is Workbench 3.8.38.
  49. Johnson Controls does have a BACnet TEC that does...

    Johnson Controls does have a BACnet TEC that does this. The part number is TEC2613-4.
  50. Replies
    9
    Views
    870

    AX History Pie Chart

    I had a customer ask me if I could display several central plant Kw's in a pie chart on a px. Any idea if this is possible? Thanks in advance.
Results 1 to 50 of 983
Page 1 of 20 1 2 3 4

Related Forums

Plumbing Talks | Contractor MagazineThe place where Electrical professionals meet.
Comfortech 365