Search:

Type: Posts; User: ncheatman

Search: Search took 0.00 seconds.

  1. Replies
    13
    Views
    1,499

    [ [/B] It could be a restriction caused...

    [ [/B][/QUOTE] It could be a restriction caused from soidering the screen could be cloged in your TXV. [/B][/QUOTE]

    Not sure why that would cause a rattle? But the txv on Puron systems do not...
  2. They are exactly the same.

    They are exactly the same.
  3. Replies
    8
    Views
    1,135

    (delete) [Edited by ncheatman on 06-24-2005 at...

    (delete)

    [Edited by ncheatman on 06-24-2005 at 10:21 AM]
  4. Replies
    3
    Views
    784

    RPM and CFM are two different things. RPM is how...

    RPM and CFM are two different things. RPM is how fast the motor turns. CFM is determined by the size of the blower wheel and how much air it is designed to move at a given static pressure.

    As Robo...
  5. Replies
    13
    Views
    3,960

    Timing sequence is the same as the old timer....

    Timing sequence is the same as the old timer. Solid state is just the replacement technology. Speed up pin replaces the old screw driver slot used to advance the mechanical timers.
  6. Replies
    17
    Views
    5,286

    Wow! Did I miss that one. I looked at the...

    Wow! Did I miss that one. I looked at the equipment and knew he had said Infinity and didn't even notice the stat (feeling real dumb). I take back what I said...your contractor did not do a good job....
  7. Replies
    17
    Views
    5,286

    This is a good and approved combination of...

    This is a good and approved combination of equipment. This furnace, evaporator coil, condenser and TXV will give you a 13.5 Seer rating.

    As to the dip switches you DO NOT have to set them. The...
  8. Replies
    17
    Views
    5,286

    Please post the model numbers of what was used....

    Please post the model numbers of what was used. If you do have the Infinity control, it will adjust all the air flow settings, the dip switches in the furnace are not used...therefore no need to set....
  9. Replies
    8
    Views
    2,600

    Don't laugh, but the easiest thing to use is...

    Don't laugh, but the easiest thing to use is toilet paper. Tear off a small amount and stuff it around the wire and fill the hole.
  10. Replies
    5
    Views
    1,218

    Auto means the fan only runs during a call for...

    Auto means the fan only runs during a call for heat or cool. The fan will run what ever speed is needed and be off if the unit is not calling for conditioning.
  11. Replies
    5
    Views
    1,218

    It is left off by default because not everyone...

    It is left off by default because not everyone will want the option. For that reason I would not say the tech "overlooked" it but should have consulted with you on the options an set for your...
  12. Replies
    1
    Views
    670

    You do not have a communicating heat pump so you...

    You do not have a communicating heat pump so you will not get those readings. They only work with the Infinity condensing unit which is the 2 speed Puron system.
  13. Replies
    3
    Views
    1,082

    Most people do not go from cooling to immediately...

    Most people do not go from cooling to immediately heating. What is your application?
  14. Replies
    5
    Views
    1,218

    First Programmable Fan option must be enabled,...

    First Programmable Fan option must be enabled, the factory default is off.

    Second, you can not program the fan exactly as you describe. What you can do is program a different CONSTANT fan setting...
  15. Replies
    6
    Views
    812

    It could be any of several dozen things, no way...

    It could be any of several dozen things, no way to tell from here. Call the service company back and have them recheck it. Very possibly you are correct and it is going off on hi pressure due to...
  16. Replies
    4
    Views
    1,838

    This alarm is generated by a couple of different...

    This alarm is generated by a couple of different things. If the EXV is less than 10% and either the suction superheat is less than the EXV Superheat Setpoint minus 10degrees. The control calculates...
  17. Replies
    17
    Views
    2,800

    Apparently you did not understand the book. If...

    Apparently you did not understand the book. If you press the Escape and Enter keys at the same time it will display a complete plain language read out of every point. If you have a fault it will tell...
  18. Replies
    17
    Views
    2,800

    Originally posted by joeywpittman aqua...

    [QUOTE]Originally posted by joeywpittman
    aqua snap SUCKS! this is the year 2005, there is a computer in my shoes for crying out loud. Why can't carrier develop a chiller with a digital readout...
  19. Replies
    16
    Views
    1,751

    I think you are missing the point. The nameplate...

    I think you are missing the point. The nameplate gives the maximum amp draw of the motor, this does not mean that it should or needs to be running at this setting. You should not set the sheeves to...
  20. Replies
    50
    Views
    3,166

    Robo, Send me your email address to {ncheatman...

    Robo,

    Send me your email address to {ncheatman at yahoo.com}
  21. DO NOT use 134A on this job. 134A required POE...

    DO NOT use 134A on this job. 134A required POE oil. POE is a natural detergent, it will free up all the "junk" in the system and wash it back to the compressor and cause the seal to leak. If this was...
  22. 409A and Alkabenzyne oil. Replace the oil and run...

    409A and Alkabenzyne oil. Replace the oil and run for 24 hours with the R12 still in the system. Change the oil again and replace with the 409.

    You can not just "drop" in R22. You would have to...
  23. Replies
    4
    Views
    1,175

    There is really no way to do this. Infinity is...

    There is really no way to do this. Infinity is designed to work with only the FE air handler or the 80% and 90% gas furnaces. It is not a thermostat, it is a communicating interface for those blower...