Search:

Type: Posts; User: ctrlguy

Page 1 of 11 1 2 3 4

Search: Search took 0.09 seconds.

  1. Replies
    4
    Views
    681

    I'm guessing you need to set the feedback units...

    I'm guessing you need to set the feedback units in the VFD (parameter 21-5) to Deg C.
  2. Thread: Ilon Webserver

    by ctrlguy
    Replies
    1
    Views
    343

    I've used SmartServers for years and never found...

    I've used SmartServers for years and never found a use for the web server functional blocks. I wish they'd dump them and give me more alarm generators.
  3. Thread: ilon email

    by ctrlguy
    Replies
    2
    Views
    351

    Never tried. I use outbound.mailhop.org from...

    Never tried. I use outbound.mailhop.org from dyndns.
  4. I have since installed several 50 series...

    I have since installed several 50 series controllers. Every point can be accessed and adjusted/overridden and it displays network variables from other controllers (haven't tried the BACnet version...
  5. Replies
    44
    Views
    6,415

    First choice for Lonworks would be Distech gfx. ...

    First choice for Lonworks would be Distech gfx. For BACnet, it would be Distech gfx.
  6. Replies
    4
    Views
    678

    Another option would have been to use an LNS tool...

    Another option would have been to use an LNS tool (Lonmaker, etc) and the Honeywell plugin.
  7. I've had one on order for a couple of weeks -...

    I've had one on order for a couple of weeks - still no sign. I was disappointed to hear the schedule can't be edited through the display - yet - they're working on it. We use a lot of Distech too...
  8. Replies
    49
    Views
    6,754

    Not to dig up a fossil, but I have a project with...

    Not to dig up a fossil, but I have a project with Data Aire units with LON cards and it appears they still haven't figured out how to build a proper Lonworks interface or gateway for an LNS system. ...
  9. I know better than that. I was referring to the...

    I know better than that. I was referring to the segment. There are 3 routers.
  10. Thanks for the reply. The wire is 22-2 LON...

    Thanks for the reply.

    The wire is 22-2 LON wire (non-shielded). The network segment is double terminated daisy-chain with a Loytec FT-10/FT-10 router. I have 160 devices communicating fine on...
  11. Control Techniques Commander SK VFDs with LON Card

    As part of a large job, I need to integrate 14 domestic water pressure booster pumps with Emerson / Control Techniques (how many business names do those people need??) Commander SK VFDs into an LNS...
  12. Assuming there are 2-way valves on the job and...

    Assuming there are 2-way valves on the job and the pumps were designed for a 100% call on all valves, the proper procedure would be to open all the valves, run the pump at 60 Hz, measure the...
  13. Replies
    4
    Views
    511

    I'm using Lonwatcher. Echelon sent a replacement...

    I'm using Lonwatcher. Echelon sent a replacement and I have the same problem. I have other 4.04.119 units out there working fine. I think my database is possessed.
  14. Replies
    4
    Views
    511

    SmartServer Schedule Problem

    I have an iLON SmartServer (4.04.119) which continuously reboots if I apply an exception schedule (like a holiday) to the scheduler. Echelon has acknowledged that it's a bug that will be addressed...
  15. Replies
    5
    Views
    1,780

    American made thermostat

    I'm doing a job with Obama bucks involved that requires "Buy American" products. Does anyone know of an American made line voltage thermostat and remote bulb temperature controller?
  16. Replies
    30
    Views
    3,645

    Maybe I'm misunderstanding what you're trying to...

    Maybe I'm misunderstanding what you're trying to do, but if you're trying to use a temperature from a hardware input on one device as a temperature in a gfx device, you're going about this the wrong...
  17. Replies
    6
    Views
    1,037

    From the user guide:

    From the user guide:
  18. Replies
    4
    Views
    840

    I've used a variety of sensors with Distech and...

    I've used a variety of sensors with Distech and yeah, I just create a translation table. In gfx, you can save them as a code snippet.
  19. Replies
    2
    Views
    431

    I set up the forwarding on the remote end and I...

    I set up the forwarding on the remote end and I know that works. The LAN was set up by others, but I'm assuming since Config Server can communicate over 1629 and I can access the RNI on 1628, that...
  20. Replies
    2
    Views
    431

    IP852 Network Problem

    I have an LNS 3.02 Lonworks IP852 network consisting of an iLON100e3 with IP852 enabled and two iLON600s (version 1.06.01). The iLON100 and one of the 600s are on the LAN. Another 600 is connected...
  21. I've had a problem - had to change it manually...

    I've had a problem - had to change it manually and at least on some computers or browsers, I get a time error (PC and iLON don't match). I haven't had time to trace it down.
  22. Replies
    2
    Views
    625

    Your connection is fine, but there's no program...

    Your connection is fine, but there's no program in the controller. There may be a backup in the memory of the controller which you can restore using the XI582. Otherwise, you'd need to have the...
  23. Thread: JCI plugins

    by ctrlguy
    Replies
    2
    Views
    721

    I've used the Johnson LXs because Distech was...

    I've used the Johnson LXs because Distech was unacceptable to an engineer. I loaded them with the Distech .apb or .nxe and used the Distech plug-ins (or wizards) because I had them.
  24. If the original programmer did his job correctly,...

    If the original programmer did his job correctly, there is a copy of the program written to the non-volatile memory in each controller. Use the restore function in the FreeProg plug-in (or wizard)...
  25. Replies
    3
    Views
    802

    What software are you using?

    What software are you using?
  26. Replies
    9
    Views
    1,173

    It basically can't be done. With regard to...

    It basically can't be done.

    With regard to configuring W7750C, if I recall correctly, you can configure them as B models using the pulse width modulation setting and the controller will output...
  27. Replies
    24
    Views
    2,060

    The I/O is Lonworks, so you need something with a...

    The I/O is Lonworks, so you need something with a lot of network variables and some control logic capability to replace the XCL5010s. Sounds like a job for Loytec or possibly a JACE.
  28. Would you be located anywhere near Mt. Desert...

    Would you be located anywhere near Mt. Desert Island? Just an informed hunch. You don't have to answer.
  29. Replies
    27
    Views
    2,621

    What's the point of trying to heat with...

    What's the point of trying to heat with superheated steam? You won't get any significant BTUs without condensing the steam and you won't condense the steam until it wends its way through the coil a...
  30. Replies
    8
    Views
    1,581

    I've had similar trouble with those Honeywell...

    I've had similar trouble with those Honeywell UNVTs on iLONs. It's been a while, but I remember having to tweak the XIF file before it would work.
  31. Replies
    7
    Views
    747

    It's on the Distech site for registered users.

    It's on the Distech site for registered users.
  32. Replies
    7
    Views
    747

    Londisplay isn't a great product, but it's...

    Londisplay isn't a great product, but it's serviceable. Your problem is not with Londisplay, but with your network, a device on the network or your network interface. Below is some info on the...
  33. Replies
    92
    Views
    5,501

    Oh, but about the gray market thing, hey, I...

    Oh, but about the gray market thing, hey, I service my customers. If they have stuff I'm not authorized to sell and have no training in, I'm damn well gonna try to get it anyway and make it work...
  34. Replies
    92
    Views
    5,501

    I'm not sure I understand why a manufacturer's...

    I'm not sure I understand why a manufacturer's requirement that their products be sold only through resellers with whom they have a contractual relationship, i.e. "authorized", is so controversial. ...
  35. Replies
    72
    Views
    6,051

    So you're asking the government to help you. ...

    So you're asking the government to help you. What could go wrong?
  36. Replies
    9
    Views
    2,021

    Funny, I'm just finishing a job where I submitted...

    Funny, I'm just finishing a job where I submitted Distech (I'm authorized) but was rejected because it wasn't specified. I told them Johnson private labeled Distech, but that wasn't good enough so I...
  37. Replies
    9
    Views
    2,021

    LX is Distech's LON product rebranded for...

    LX is Distech's LON product rebranded for Johnson. Great stuff. It's as open as controls get. There are wizards for all the controllers for Tridium (FX) and free plug-ins for LNS. The graphical...
  38. Thread: E-Bus

    by ctrlguy
    Replies
    1
    Views
    534

    It's Honeywell's name for a lonworks TP-FT bus.

    It's Honeywell's name for a lonworks TP-FT bus.
  39. Replies
    11
    Views
    801

    You're missing the Echelon javascript entries in...

    You're missing the Echelon javascript entries in the header of your page. Try using one of the example pages in the demo folder as the basis for your page.
  40. Replies
    16
    Views
    1,810

    What you need is in this document...

    What you need is in this document.

    Basically, AvgRmTemp_F= FAN_IN_AV /10*18/10+320. The result is F*10 so you get resolution down to 1/10th degree (Distech basic uses integers only) so if the...
  41. Thread: recommandation

    by ctrlguy
    Replies
    16
    Views
    1,554

    Distech has it all, but you're probably not gonna...

    Distech has it all, but you're probably not gonna get it in Brooklyn.
  42. Replies
    9
    Views
    1,677

    I regularly use Honeywell plug-ins with Distech...

    I regularly use Honeywell plug-ins with Distech Lonwatcher without problems. How did you create the Honeywell devices in your test database? If you loaded from XIF rather than using a template,...
  43. Thread: Distech

    by ctrlguy
    Replies
    15
    Views
    2,371

    You don't need to enter anything. Just hit...

    You don't need to enter anything. Just hit cancel or OK and the software will run for the 30 days or longer if you back date.
  44. Replies
    7
    Views
    1,272

    "Permanent secure access mode" just means the...

    "Permanent secure access mode" just means the check box on the Setup: Security web page is checked. It's not a problem - if you uncheck the box, that page will be disabled unless you boot up in...
  45. Replies
    29
    Views
    2,735

    The LNS plug-ins for XL10s have to be launched...

    The LNS plug-ins for XL10s have to be launched from the LMObj functional block (not from the controller graphic). Drag a functional block onto the screen, select the XL10 you're trying to configure,...
  46. Replies
    2
    Views
    626

    I had a bad batch of VAVs a couple of years ago...

    I had a bad batch of VAVs a couple of years ago (like 8 out of 40 were bad) and needed replacements in a hurry. They found some at a US distributor (avoiding the customs delay) and had them shipped...
  47. Thread: iLON600 redo

    by ctrlguy
    Replies
    1
    Views
    560

    You say you restored the root/lonworks directory...

    You say you restored the root/lonworks directory and the .sys file, but my iLON600 images folder doesn't contain a lonworks directory or a .sys file. There is an iLONsystem file, a web folder, a...
  48. Replies
    1
    Views
    1,386

    Lonworks Bandwidth Calculation

    I have a spec that calls for submitting a bandwidth usage calculation (it's a single segment TP/FT10 bus topology with about 32 devices). Anyone have a tool for this purpose?
  49. Replies
    2
    Views
    893

    I've done it lots of times and it works fine with...

    I've done it lots of times and it works fine with the default PID parameters. Recheck your settings.
  50. Replies
    109
    Views
    11,025

    I've experimented successfully on a small job...

    I've experimented successfully on a small job summing all the flow setpoints and all the flows. If the sum of the flows is lower than the sum of the setpoints, I increment the fan speed periodically...