    Mini Split Question

    A guy I work with just had an Ambiance mini split system installed in a garage conversion. He says the fan runs 7-24 unless the unit is switched off. Cooling or not, the fan runs unless you swith the...
  2. Well, I popped the top for a quick look see....

    Well, I popped the top for a quick look see. There doesn't apear to be any obvious signs of a leak. It's a cap tube system, Copeland compresssor, no ports available so I guess I'll have to go get...
  3. Thanks for the replies. I'll start opening things...

    Thanks for the replies. I'll start opening things up and see about getting some temps and pressures.This may take a while...I'm told it's not the top priority right now...yeah that 'll change quick...
  4. Two Reach-ins, two Temps, neither one great

    We have two "identical" Hobart QF2 R 404a reach-in freezers sitting side by side in a small commercial kitchen. One will reach about 4.2 degrees, the other seems to hang at about 16 degrees. I've...
  5. Replies
    3
    Views
    1,797

    Check the connections at the water level sensors...

    Check the connections at the water level sensors and the sensors themselves. Make sure if you have completed a descale on the unit that the sensors are well rinsed of the descaler. Unless the sensors...
  6. Replies
    7
    Views
    775

    You also might want to check the service...

    You also might want to check the service disconnect to the AHU for a shunt trip circuit. On our panels there is no indication of the trip other than loss of power. a real PITA.
  7. Replies
    19
    Views
    1,391

    I use Simple Green and H2O in whatever dilution...

    I use Simple Green and H2O in whatever dilution it takes to cut the grime. works indoors and out, non-toxic, biodegradable and smells good for evaps.
  8. Thread: Steamer

    by jkochan
    Replies
    3
    Views
    1,377

    Ditto.

    Ditto.
  9. Replies
    24
    Views
    4,206

    Worked on a couple of these. Sand and CLEAN the...

    Worked on a couple of these. Sand and CLEAN the shaft VERY WELL and the new bearing should slide right down the shaft. If you oil the shaft lightly it will help. Too much oil on the shaft will cause...
  10. Replies
    13
    Views
    1,781

    Well, Finally got it figured out. The tech...

    Well, Finally got it figured out. The tech brought in a lap top and hooked it up. It did absolutley nothing. The problem turned out to be that when the pupmped the unit down they used the pumpdown...
  11. Replies
    13
    Views
    1,781

    As far as I know, the only time a laptop was...

    As far as I know, the only time a laptop was hooked up to this chiller was at start-up. I never saw a laptop during the last service call, but I'll make some calls and double check. I can engage the...
  12. Replies
    13
    Views
    1,781

    We use INET 7 for EMS/BAS applications. I have...

    We use INET 7 for EMS/BAS applications. I have reviewed all points in the MCI and PCU relating to chiller operation and there is nothing in manual or test in either controler and the point...
  13. Replies
    13
    Views
    1,781

    Now that the approach problem is solved, I have a...

    Now that the approach problem is solved, I have a problem with the Hot Gas Bypass. This is a PIC II with a CCN network interface. On start-up it says it's calling for HGBP but the solenoid is not...
  14. Replies
    11
    Views
    1,384

    Just for the record.

    The approach on our chiller has returned to normal operational values. The problem WAS non-condensables. Thanks to all for your input.
  15. Replies
    11
    Views
    1,384

    Thanks to all. We are going to have the liquid...

    Thanks to all. We are going to have the liquid recovered and send the vapor off for recycling/destruction, then weigh the recovered liquid charge and add new 22 to make up the differance. Then will...
  16. Replies
    11
    Views
    1,384

    Thanks for the replies. Jacob and hvac: The...

    Thanks for the replies. Jacob and hvac: The readings were taken after transfer from the other chiller under about 3/4 load and after approx. 1 hour of operation.I noticed today that there is a...
  17. Replies
    11
    Views
    1,384

    Thanks for the reply. The presssure sensor...

    Thanks for the reply. The presssure sensor reading matches the gauge reading on the barrel.
  18. Replies
    11
    Views
    1,384

    We have two 23XL 200Ton R-22 three pass screw...

    We have two 23XL 200Ton R-22 three pass screw machines with the economizer. Chiller #2 has always had a higher approach than #1. It recently had the condenser float replaced as well as isolation...
  19. Replies
    10
    Views
    7,691

    A push-pull method of removing refrigerant is...

    A push-pull method of removing refrigerant is accomplished by connecting the liquid line fitting on
    the system to the liquid line fitting on the recovery tank. The suction line of the recovery unit...
  20. Replies
    0
    Views
    471

    Has any one used one of the sonic belt tensioning...

    Has any one used one of the sonic belt tensioning meters?