  1. Rather the dip switches, not jumpers.

    Rather the dip switches, not jumpers.
  2. The jumpers need to be set for 2 volts and temp...

    The jumpers need to be set for 2 volts and temp to read that sensor. That controller will read 250DegF when the sensor circuit is open and -50 when shorted. Wire a sensor directly to the AI. See if...
  3. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    875

    WTF?

    WTF?
  4. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    875

    Thanks. I am bidding on taking out some Carrier...

    Thanks.
    I am bidding on taking out some Carrier and planning on putting in somenew JCI stuff, likely on Bacnet. Do you think the comm wire will be sufficient? I am kinda doing this estimate blind...
  5. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    875

    Carrier CCN

    Anybody know what comm protocol the Carrier CCN network is? Modbus maybe or some proprietary thing like JCI N2.
  6. Replies
    6
    Views
    862

    Dang, I should proofread for grammar. I think...

    Dang, I should proofread for grammar. I think much faster than I type.
  7. Replies
    6
    Views
    862

    Froz is right. In PMI and override creates...

    Froz is right.

    In PMI and override creates and SWO condition on the point. It is released with an "Auto" command. "Release all" will not release an SWO, it will however release process commands...
  8. Replies
    6
    Views
    862

    What is the site terminal? Is it a PC running PMI?

    What is the site terminal? Is it a PC running PMI?
  9. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    This job is FX10 OEM style boards factory...

    This job is FX10 OEM style boards factory programmed supplied in water water source heat pumps. It is the FX10 that is in question. All I would do is map them up and do some S/S and setpoint control....
  10. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    I am open to suggestions. I am not the king of...

    I am open to suggestions. I am not the king of this stuff but I need to be in the face of my customer. That is why I am on here looking to learn and chat with the folks who have taken the...
  11. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    CCIKelly, I have an FX20 in the building right...

    CCIKelly, I have an FX20 in the building right now, with an FX07 on N2 doing some small tower work. (I plan to get started with that) I will certainly have to add numerous additional FX20/60/70...
  12. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    Sam is right that the FX05,7,14,15,16 line is...

    Sam is right that the FX05,7,14,15,16 line is being discontinued. But it is on a sales basis. I am not sure if the FX10 is inclusive of this, as it seems to be a OEM type product. I could not buy one...
  13. Replies
    1
    Views
    637

    York service valve question

    I have to pump down and change out a York h2cb036s06a. I found at the service valves are not the allen type I am used to seeing. they had deep caps on them and when I took one off, there was a pin...
  14. Thread: PID wound up?

    by prostock
    Replies
    14
    Views
    1,382

    Remember that the IT in ASCs are in seconds so...

    Remember that the IT in ASCs are in seconds so you should have a big number for room control, like +/-600.
  15. Replies
    4
    Views
    503

    dude this is not hard to do but a SOB to explain....

    dude this is not hard to do but a SOB to explain. I am at the desk today and I will help you through it if you send me your base file. (.dxs)
  16. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    I found the full FX10 .pdf today and plan to read...

    I found the full FX10 .pdf today and plan to read it tomorrow. I hope that the program written and installed in these factory boards is sufficient and easy to map up and control. I hope that the...
  17. Replies
    8
    Views
    3,788

    Bill and retube are right. Move it if you have...

    Bill and retube are right. Move it if you have to, but you could just change the setpoint until you get what you need where you need it. If it is that critical, them someone ought to be putting some...
  18. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    Hey Sam, Its been awhile. Go Capitals! So...

    Hey Sam, Its been awhile. Go Capitals!

    So maybe I advise Lon on this project?
  19. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    LOL. I doesn't matter. Jci controls group...

    LOL. I doesn't matter. Jci controls group historicly is carried
    by auto and battery. They will never go away! I am an old asc / gpl /dx /pmi guy so I can make their stuff work. Now doing the fx...
  20. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    Only 40 per trunk. I have 60 per floor. 19200...

    Only 40 per trunk. I have 60 per floor. 19200 baud. I was reading on here about folks having a hard time with the BACNET being very slow and communication issues with the FX10. If it were bacnet/IP...
  21. Thread: FX10

    by prostock
    Replies
    28
    Views
    1,949

    FX10

    Got a client looking to install a bunch (over 500 eventually) new heat pumps. They are available with the FX10. Literature says Bacnet is 19200 and folks on here say to stay away. I have an FX20 in...
  22. Replies
    2
    Views
    605

    Thanks for the help. It seems to have fixed my...

    Thanks for the help. It seems to have fixed my problem, halfway. I can now open hvacpro files if I double click on them from windows explorer, but I still get the same "invalid file format" if I try...
  23. Replies
    2
    Views
    605

    HVACPRO "Invalid file format"

    I have been using hvacpro for years (ex JCI guy). I have some files from a few months ago that I need to get opened so I can do my asbuilts that are way overdue. Now I get the "invalid file format"...
  24. Replies
    3
    Views
    480

    I would second all that phreak said. I have used...

    I would second all that phreak said. I have used the Veris stuff alot, and had very little difficulty with it. I have done everything from single breaker apps to whole buildings with it. 27 pieces of...
  25. Replies
    11
    Views
    1,399

    hockey puck, viceman? Do you have a part name or...

    hockey puck, viceman? Do you have a part name or number?Maybe I can look at it to use.

    I usually use the Veris MX-1. Works great with DDC BI points. Needs power. Does the puck need power to work?...