Search:

Type: Posts; User: bwood

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    2
    Views
    272

    I figured it out. I had the hyperterminal...

    I figured it out. I had the hyperterminal connection info, my issue turned out to be i had the wrong serial connection. I found a connection on the iComm board and assumed it was the one and i...
  2. Replies
    2
    Views
    272

    Liebert Challenger 3000 IP address

    Looking for some help, I need to change the IP addresses on 2 Liebert units. I have tried to use the web interface and I can see the existing IP, but when I update it per the customer's new IP, I get...
  3. Replies
    20
    Views
    1,207

    Amp was a typo. TGE (Tracer Graphics Editor) is...

    Amp was a typo. TGE (Tracer Graphics Editor) is part of TU

    Sent from my HTC One using Tapatalk
  4. Replies
    20
    Views
    1,207

    That should read Tracer TU Sent from my HTC...

    That should read Tracer TU

    Sent from my HTC One using Tapatalk
  5. Replies
    20
    Views
    1,207

    There is not a graphics editor in ES like there...

    There is not a graphics editor in ES like there is in Summit. You must use Traced TU & TGE to convert your Summit graphics. The newer versions on ES (4.6 & 4.7) supposedly have made the process...
  6. Replies
    20
    Views
    1,207

    This can also be an issue in Windows 7. Sent...

    This can also be an issue in Windows 7.

    Sent from my HTC One using Tapatalk
  7. Replies
    20
    Views
    1,207

    Sorry, SP13 supports Windows 8 Sent from my...

    Sorry, SP13 supports Windows 8

    Sent from my HTC One using Tapatalk
  8. Replies
    20
    Views
    1,207

    Tracer Summit SP13 is available and supports SP13...

    Tracer Summit SP13 is available and supports SP13

    Sent from my HTC One using Tapatalk
  9. Check the dc voltage at the sensor. Green =...

    Check the dc voltage at the sensor. Green = negative, red = supply, black = signal. At 1.5", the signal should be around 1.25-1.5 vdc. Are you getting a SA Pressure sensor failure at the ipak...
  10. Thread: Trane BCI-I

    by bwood
    Replies
    9
    Views
    554

    You are writing to the min, but the damper can...

    You are writing to the min, but the damper can still open more in economizer mode. If there is a call for cooling, economizer is enabled, the damper will modulate for cooling. If the damper goes 100%...
  11. Thread: Trane BCI-I

    by bwood
    Replies
    9
    Views
    554

    The ventilation control for the oa damper is...

    The ventilation control for the oa damper is controlled by the economizer board. Is your feedback 1/2 of the signal or the opposite? Have you field verified that the feedback is off? Is the unit...
  12. Replies
    2
    Views
    481

    How old are the Voyagers? Are they Reliatel? Are...

    How old are the Voyagers? Are they Reliatel? Are you just cycling the RTUs or the Tracker too? Do they all do this at the same time or is it random? There is an issue out there where the issue is...
  13. Thread: Trane BCI-I

    by bwood
    Replies
    9
    Views
    554

    Scrooloose is correct. You have to write to the...

    Scrooloose is correct. You have to write to the min OA setpoint.
  14. Replies
    3
    Views
    344

    New firmware updates are out there to speed it...

    New firmware updates are out there to speed it up. You will need Tracer TU to install.
  15. That is the ecm board for the variable speed...

    That is the ecm board for the variable speed motor. There is more of it in the motor wiring section. That code is not an error, it is short for "Fan Status-Motor 2" the next display will show either...
  16. Replies
    2
    Views
    394

    You should be able to purchase those across any...

    You should be able to purchase those across any Trane parts counter.
  17. Replies
    6
    Views
    692

    We had a customer site where this kept happening...

    We had a customer site where this kept happening on the same unit. There had been about 7 different techs out for the same thing, everything checks out and cycle power, everything is back to normal,...
  18. Replies
    6
    Views
    692

    This has nothing to do with the Tracker. Replace...

    This has nothing to do with the Tracker. Replace the economizer board and motor. I have been through this before, cycle power and it's good for a little while and then happens again. There was an...
  19. Replies
    8
    Views
    738

    I would go with the bacnet. The UC400s mount in...

    I would go with the bacnet. The UC400s mount in the same hole the ZN (comm 5) controllers mounted, and should come with a canned wshp program. The points that you need exposed can be discovered in...
  20. Replies
    4
    Views
    839

    I don't have the program to give, but it is out...

    I don't have the program to give, but it is out there. I don't believe it will run on windows 7 without a virtual XP enviroment or DOSBox (or something similar). As far as the sensors/controls, they...
  21. Replies
    21
    Views
    1,691

    If I remember correctly you shouldn't have any...

    If I remember correctly you shouldn't have any voltage, and if any it would be extremely low, close to zero. A good scan with rover will bring in a device every 2-4 seconds. I could see it being a...
  22. Replies
    21
    Views
    1,691

    Is the resistance steady? or does it fluctuate?

    Is the resistance steady? or does it fluctuate?
  23. Replies
    21
    Views
    1,691

    My thought is that it may be necessary to do a...

    My thought is that it may be necessary to do a "Rebuild" on the LON link through the BCU. There is no guarantee that this would resolve the issue, but if the site has had issues for a long period of...
  24. Replies
    21
    Views
    1,691

    I believe that image would be equivalent to...

    I believe that image would be equivalent to summit ver 17 sp 8. I believe this should be a solid image as far as LON improvements go. Does the site have a tremendous amount of bindings (sensors...
  25. Replies
    21
    Views
    1,691

    These numbers sounds decent. Check the BCU image,...

    These numbers sounds decent. Check the BCU image, as newer firmware is introduced they have made improvements to how the BCU handles itself. There have been LON enhancements through the years also....
  26. Replies
    10
    Views
    948

    Yes, there is, I forgot about it. The LCI-V.

    Yes, there is, I forgot about it. The LCI-V.
  27. Replies
    10
    Views
    948

    I checked into it last night before I posted,...

    I checked into it last night before I posted, BCI-R is Relitel only. The UC400 is a programmable BACNet controller that can be used for anything, but with a firmware change it can be BCI-I for...
  28. Replies
    10
    Views
    948

    BCI-R is for Relitel only, it sounds like he has...

    BCI-R is for Relitel only, it sounds like he has the old Voyager Micro boards. BACNet Communications Interface - Relitel

    I don't have an answer for the issue at hand, do you have any documentation...
  29. Replies
    21
    Views
    1,691

    Also, check the BCU firmware image and see what...

    Also, check the BCU firmware image and see what version it is running and what version of Summit is onsite.
  30. Replies
    21
    Views
    1,691

    Take readings at both EOLs (should be the same)...

    Take readings at both EOLs (should be the same) and then one in the middle. The middle reading will be higher, you wouldn't think so, but when the link is so long you can see fluctuations.

    It can...
  31. Replies
    21
    Views
    1,691

    With 4000' (assuming 22ga and the max of 18...

    With 4000' (assuming 22ga and the max of 18 ohms/1000') of wire and 105 EOLs at each end, your resistance is going to be ~88.5 ohms, and that doesn't take each termination into account. Trane best...
  32. Replies
    3
    Views
    549

    Disconnect the sensor at the board and...

    Disconnect the sensor at the board and temporarily install a 10000 ohm resistor. The reading should be approx 77 degrees. If it is still way off, it is more than likely a board issue.
  33. Replies
    5
    Views
    686

    The Tracker panel is slow no matter what you do....

    The Tracker panel is slow no matter what you do. The modem exists for a remote connection. The VPN should work in theory, I wonder if there is an issue with how the VPN is set up? Is it possible to...
  34. Replies
    6
    Views
    828

    The hospital I worked for back in the day had the...

    The hospital I worked for back in the day had the same problem. All of the starters were Square D with built in transformers and the control relays were in the cabinet. About 9 months after the...
  35. Thread: VFD go bad???

    by bwood
    Replies
    10
    Views
    780

    I would think that a drive that ran for 17 years...

    I would think that a drive that ran for 17 years should have paid for itself multiple times if it was set up properly ( and I can only assume that it was ). The new drive will be able to do the same...
  36. Replies
    2
    Views
    596

    If you need TU, it is already BACNet/MSTP. The...

    If you need TU, it is already BACNet/MSTP. The BACNet setup tool allows you to set baud rates, program/soft address and the units.
  37. Thread: old varitrac ccp

    by bwood
    Replies
    4
    Views
    455

    The baud rate should be 1200, 8, none, 1,...

    The baud rate should be 1200, 8, none, 1, xon/xoff, try also changing the text format (I can't remember to what). If you are truly connected and can't get the menu screen to pop up, it has got to be...
  38. Replies
    3
    Views
    405

    No sweat. I usually end up beatin on one of these...

    No sweat. I usually end up beatin on one of these old panels about once a year.
  39. Replies
    3
    Views
    405

    Yes, plc edit will restore to your backup. Make...

    Yes, plc edit will restore to your backup. Make sure you cycle the building control on once it is up and running.
  40. Thread: Trane Rover 7.1

    by bwood
    Replies
    26
    Views
    5,117

    Tracer SC/SC controller are replacing Tracer...

    Tracer SC/SC controller are replacing Tracer Summit and the BCU.
  41. Thread: Trane Rover 7.1

    by bwood
    Replies
    26
    Views
    5,117

    Rover is designed to configure Trane devices. It...

    Rover is designed to configure Trane devices. It has the ability to assign the DSN on non Trane devices and that is about it. Non Trane devices will show up in a discovery, but will show that "Rover...
  42. Thread: Trane Controls

    by bwood
    Replies
    12
    Views
    1,494

    Hyperterminal can be used to interface with old...

    Hyperterminal can be used to interface with old Tracker, Old CCP, T100. BMN is also used with T100s. New Tracker V12 uses Tracker V12 software, Varitrac also it's own software for the CCP III panels.
  43. Thread: Trane Controls

    by bwood
    Replies
    12
    Views
    1,494

    Here is a quick run down of Trane devices and...

    Here is a quick run down of Trane devices and their service tool software. There is more, these are the biggies.
    CH530/1 Chiller Interface=Tech View/Kestrel View
    UC800/AdaptiView Chiller...
  44. Replies
    18
    Views
    1,734

    The LCI-R/I/C cards are basically simple bridges,...

    The LCI-R/I/C cards are basically simple bridges, there is no configuration required. They are just taking the Trane IMC to LON. Tech/Kestrel View is required to bind the LCI-C card to the CH530, you...
  45. Replies
    3
    Views
    525

    The Eschelon adapter is for comm 5/Lon. Plug in...

    The Eschelon adapter is for comm 5/Lon.
    Plug in the comm 4 adapter
    Go to Device Manager and see what port Windows has assigned to the adapter. Fire up comm 4 Rover and go to options and set the...
  46. Replies
    2
    Views
    716

    CH530 uses Tech View. Tracer TU is for the...

    CH530 uses Tech View. Tracer TU is for the Adaptiview chillers (large color touch screen and UC800 inside the panel).
  47. Replies
    16
    Views
    1,133

    80-85 degrees into the chiller, 90-95 out. Does...

    80-85 degrees into the chiller, 90-95 out. Does the tower have some type of bypass?
  48. Replies
    16
    Views
    1,133

    60 degree condenser water sounds pretty cool. The...

    60 degree condenser water sounds pretty cool. The chiller will shutdown if the water gets too cool. Been there.
  49. Replies
    4
    Views
    551

    Rover is a licensed product and the different...

    Rover is a licensed product and the different modules of Rover can be purchased and are tied to the product serial number.
  50. Thread: Trane Questions

    by bwood
    Replies
    6
    Views
    831

    These vav controllers have no comm chip...

    These vav controllers have no comm chip whatsoever on them. They used to be sold on jobs that had no BAS. There my be wiring between the boards and the hi, it should just be a BO that occupies the no...
Results 1 to 50 of 57