Search:

Type: Posts; User: Chiller Tex

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    3
    Views
    788

    D1 & D2 contacts are the "transition signal". It...

    D1 & D2 contacts are the "transition signal". It is a relay built in the circuit board. Those contacts are on line 36 on the schemattic from the CVHE service guide page 7.14-4. The n.o. contacts...
  2. Replies
    3
    Views
    788

    CVHE wont transition

    I have a CVHE-071 that wont transition the starter. I trouble shot the starter and found the D1 & D2 contacts not closing to send it in the delta mode. This is an '84 model machine. The contacts that...
  3. Replies
    12
    Views
    1,273

    I updated my info. If you found something on the...

    I updated my info. If you found something on the IGV please send it. I like to have that in my library.
  4. Replies
    12
    Views
    1,273

    Yall where right about Carrier Houston rebuild...

    Yall where right about Carrier Houston rebuild shop. They had the exact IGV rebuilt and ready to go. Thanks for the input. That saved me the headach.
  5. Replies
    12
    Views
    1,273

    19DH guide vane rebuild

    Does anybody know what the service guide catalog # is from carrier that explains how to disasemble and reasemble the guide vane section? also does anybody have any pointers on rebuilding the guide...
  6. Replies
    2
    Views
    429

    What soft key? Just kidding, yes l hit it. I went...

    What soft key? Just kidding, yes l hit it. I went back to job site and disconnected the evap refrig sensor from micro. when l wired sensor back in the micro reset. I not sure why, but everything...
  7. Replies
    2
    Views
    429

    19xr pic lll won't clear fault

    I have a 19xr pic lll that won't reset. It went off on low evap temp. The evap sensors were reading 31.4 [actual was 48 ] & the cond read 45 [actual was 62 ]. I somehow got the sensors to read...
  8. Replies
    13
    Views
    1,079

    Thanks guys for the input. This is a cool website.

    Thanks guys for the input. This is a cool website.
  9. Thread: RTAA fault

    by Chiller Tex
    Replies
    44
    Views
    5,794

    Everyone has good suggestions. Also check the oil...

    Everyone has good suggestions. Also check the oil level and the oil switch calibration. A quick way to check oil switch. Turn ckt off, leave the low port hooked up to oil line. Take the high port off...
  10. Replies
    2
    Views
    563

    Call Benshaw. Have the m#, s# of SSS panle and...

    Call Benshaw. Have the m#, s# of SSS panle and chiller. Ask for tech help. They will walk you throu it.
  11. Replies
    28
    Views
    1,902

    It doesn't hurt the chiller to shut off when...

    It doesn't hurt the chiller to shut off when loaded. It's not the best way, but no big deal. Think of it as when the power goes out. It stops.
  12. Replies
    13
    Views
    1,079

    19xr comp o-rings & gaskets

    what do you use on the o-rings & gaskets? 515?
Results 1 to 12 of 59
Page 1 of 2 1 2
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine