Drivet
I have not used it my self but I know someone that has. Said it worked ok
-
Solidyne
Yes there is a driver for these things. You can call them and they will direct where to buy it.
Greg -
03-01-2013, 08:20 PM
Thread: Talon Network Manager on FX Workstaion
by GregF- Replies
- 5
- Views
- 167
License
Talon is OPEN. Any time you see a * in a license file it means it will take any thing.
-
01-25-2013, 09:19 PM
Thread: Tridium to iLon integration
by GregF- Replies
- 3
- Views
- 404
Ilon
Just use the LonIP Network.
G -
09-20-2012, 10:43 PM
Thread: Landis Staefa Controller?
by GregF- Replies
- 6
- Views
- 497
Raptor
It depends on the version, but there is a Talon block that was used a lot. Howevere it has a bug in it. You could power it down but DO NOT DO THIS untill you change the battery to a new one. The Lon...
-
09-20-2012, 10:26 PM
Thread: Niagara AX Boolean switch?
by GregF- Replies
- 9
- Views
- 940
Boolean Switch
Ha Steve
There's not a strait up way to do what your looking to do. I use them alot and I'll send you on in the morning.
Greg -
09-19-2012, 10:01 PM
Thread: AX Boiler Controling
by GregF- Replies
- 30
- Views
- 2,135
Jace I/O
Well I use them all the time. If you follow the rules its as solid as any thing else. Have a few Chiller Plants with no problem. Lots of Boilers and AHU's.
G -
09-19-2012, 09:53 PM
Thread: Landis Staefa Controller?
by GregF- Replies
- 6
- Views
- 497
Staefa
Thats an older Talon Raptor. You would need the Raptor Block Programmer, and hope the debug file is in it.
G -
08-05-2012, 08:35 AM
Thread: Distech EC-GFX
by GregF- Replies
- 12
- Views
- 732
gfx Tool
opps told you wrong, I've always have a station running in th backround. I just checked it out and to have to have AX, Lonmaker, Lonwatcher or other tool running to.
Greg -
08-04-2012, 07:05 PM
Thread: Distech EC-GFX
by GregF- Replies
- 12
- Views
- 732
GFX Tool
All you need is the EC-gfx Programming Tool. Launch that and you don't have to use the AX.
G -
05-12-2012, 05:22 PM
Thread: Platform running low on RAM disk space
by GregF- Replies
- 15
- Views
- 894
Ram Disk
This is a Jace 7?? Are you using the JCI appliance? What do you have on the thing??
Greg -
05-12-2012, 09:48 AM
Thread: Platform running low on RAM disk space
by GregF- Replies
- 15
- Views
- 894
Ram
checkvalve
What you are saying I mostly agree, however I was trying to point out how little memory we work with. If he has the flash disk space he could increase the ram disk. The other side is... -
05-11-2012, 08:09 PM
Thread: Platform running low on RAM disk space
by GregF- Replies
- 15
- Views
- 894
Ram Disk
Clean up, I could not tell you without seeing the station. The % ram is set out of the box at 10%, you could lower tha to say 4 or 5 %. It will fix the problem for a short time and can fix it all...
-
05-10-2012, 09:48 PM
Thread: Platform running low on RAM disk space
by GregF- Replies
- 15
- Views
- 894
Ram Disk
Questionz
Theres more to it than Histories and trends. The whole station loads up into ram disk, this saves flash disk writes. Now what ever you have on the Jace loads into ram disk, Operating... -
05-08-2012, 10:56 PM
Thread: Java and Niagara
by GregF- Replies
- 6
- Views
- 668
Java
Good question, first its Tridium Niagara so it is the same.
Second, if you are talking jar files or drivers it is Java, you just have to use Tridium imports.
Third, Niagara AX has program... -
05-06-2012, 09:12 PM
Thread: Lonmaker Questions
by GregF- Replies
- 28
- Views
- 1,305
T Box
All that works and works well, It will route lon to. Twisted to Ip no problem.
Greg -
04-19-2012, 09:43 PM
- Replies
- 4
- Views
- 516
Opps
Sorry I just saw 275 devices, I would still do it. That would be about 70 devices a trunk.
Greg -
04-19-2012, 09:40 PM
- Replies
- 4
- Views
- 516
Jace 7
Shockwave
A Jace 7 is about 4times a Jace 6, you are good for 150 devices.
Greg -
04-08-2012, 12:11 PM
Thread: AX program service bql query
by GregF- Replies
- 6
- Views
- 524
Bql
hvac69
The problem you are having is the slot is not exposed, now you could expose the slots but you have to open each point to do it.
You might as well just do the conversion one at a time.
Greg -
03-15-2012, 01:04 PM
- Replies
- 22
- Views
- 747
Points
The super is a device under the NiagaraNetwork, hit the plus sign and double click the point folder, do a discover add points. Link points to the graphic.
Greg -
03-15-2012, 12:12 PM
- Replies
- 22
- Views
- 747
Graphics
Any points you want to display in on sup, bring in the points under the station under the niagaranetwork. Then like linking with the bacnet side you would link from the niagaranetwork.
Greg -
03-14-2012, 10:24 PM
Thread: Novar JACE Help!
by GregF- Replies
- 4
- Views
- 421
Novar
Well good luck getting Novar's jar files, they are tighter than TAC. If you can't get them check the tridium base license and if it has what you need delete the Novar one reboot and you should be...
-
03-12-2012, 10:24 PM
- Replies
- 22
- Views
- 747
Niagara
Ok now you have all three sup's on the network, all set 81, 1911, 3011 and yes you will have to put the 81 at the end to browse.
Double click the Niagara Network and do a discover, now this is a... -
03-12-2012, 10:07 PM
- Replies
- 22
- Views
- 747
Log In
Well I still don't get the 3 sup's but it is what it is. First forget the 80, each IP is its own. Think about your LAN, do you think thats how they do it??
Now each sup has its own IP, done, they... -
03-12-2012, 09:16 PM
- Replies
- 22
- Views
- 747
Access
You can't make this work and don't need to. If you change port 1911 the jace's will have to be changed, if you change the jace's the server will not be able to see them. Example Jace 1 port 1912,...
Results 1 to 25 of 258