Search:

Type: Posts; User: dave2142

Page 1 of 12 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    28
    Views
    3,338

    Stale data issues

    I have 2 sites where we are using the comm4 driver. Everything works fine at times but I get a lot of stale data issues which keep the devices from going into occupancy and such. I have tried...
  2. We do a lot of tracker and varitrac in our office...

    We do a lot of tracker and varitrac in our office and they are not difficult to set scheduling in if you follow the manual. It is just really time consuming setting them up because of the way they...
  3. Replies
    9
    Views
    1,257

    Ok thanks now it makes sense I have been using...

    Ok thanks now it makes sense I have been using the file in the lonTrane module. I will check out making my own.
  4. Replies
    9
    Views
    1,257

    That must only appear on an FX because there is...

    That must only appear on an FX because there is no personality2 or any of the points you mention on a Jace. Unless you have a different module than the lonTrane one.
  5. Replies
    9
    Views
    1,257

    I have never seen those points pull in from a ZN....

    I have never seen those points pull in from a ZN. Am I missing them somewhere?
  6. Replies
    9
    Views
    1,257

    They are inside the proprietary variables. You...

    They are inside the proprietary variables. You can create a switch and use a boolean to turn it off and on I call this thumbwheel enable/disable. Map a numeric remote setpoint and the nvoSetpoint to...
  7. Replies
    12
    Views
    2,110

    I have done several jobs removing the BCUs and...

    I have done several jobs removing the BCUs and using the infocon drivers. Everything went very well and that is the route I would go. I would not replace the few PCM but would leave then in the BCU...
  8. Replies
    30
    Views
    5,061

    Could I get a copy of those also? I had them from...

    Could I get a copy of those also? I had them from my days at JCI but lost them in a computer upgrade. My email is in my profile.

    Thanks
  9. Thread: Tracer SC

    by dave2142
    Replies
    8
    Views
    1,240

    To be honest the SC is still real buggy with a...

    To be honest the SC is still real buggy with a lot of stuff. It will take the number of devices per the license but seems to have a lot of buggy comm and web interface issues. It has gotten 200%...
  10. Replies
    20
    Views
    1,720

    Contact me at the email in my profile. Or send me...

    Contact me at the email in my profile. Or send me the backups and I will see what I can do. I will need to find the program again. Have not been doing much with it for the last year or so.
  11. Replies
    9
    Views
    1,440

    I would agree just remove the CCP and use the...

    I would agree just remove the CCP and use the comm4 driver in Jace. Replicating the CCP software would be very easy it really does not do anything special.
  12. Replies
    26
    Views
    6,994

    Do not know anything about Struxureware but its...

    Do not know anything about Struxureware but its is far from what the AX can do. I am sure in the future it will be a viable front end but for now it still has a lot of work to go. I doubt it will...
  13. Replies
    13
    Views
    1,584

    Not been with JCI in several years but was around...

    Not been with JCI in several years but was around when the FEC first started hitting the market good to see that the adaptive tuning has not gotten any better. What worked for me in the past was to...
  14. Replies
    29
    Views
    5,421

    Should work fine

    Should work fine
  15. Replies
    29
    Views
    5,421

    I would install a large Jace with comm4 driver...

    I would install a large Jace with comm4 driver and remove the BCU with the comm4 devices and go direct into the Jace. The comm4 from Infocon works very well I have used it several times and it works...
  16. Replies
    20
    Views
    4,648

    Trane will not even given those Summit...

    Trane will not even given those Summit proprietary variables out to those of us who work for corp. Trane. We have been doing a lot of Tridium instead of Summit and cannot get that data for our own...
  17. Replies
    7
    Views
    1,083

    Try a Jace with comm4 driver or lontalk driver.

    Try a Jace with comm4 driver or lontalk driver.
  18. Replies
    52
    Views
    4,740

    I am with osiyo 100% on this one. I understand...

    I am with osiyo 100% on this one. I understand cloud computing but not sure how it relates to our world. Are they suggesting that the main cotroller programming reside on a system somewhere outside...
  19. Replies
    52
    Views
    4,740

    Did several big systems back in my days at JCI...

    Did several big systems back in my days at JCI one AHU had 4 maxed out DX9100 controllers and a unt to handle it. The trick was to separate the systems into individual controllers and use direct...
  20. Replies
    2
    Views
    1,255

    Thanks already tried that have set at 1 second I...

    Thanks already tried that have set at 1 second I think the issue might be trunk noise also. Have two trunks on the device and using the dual rs/232/485 card. They had issues with Summit so could be a...
  21. Replies
    2
    Views
    1,255

    Comm4 driver in Jace

    Anyone ever used the infocon comm4 driver in a Jace. I am having some issues with one. It works but a lot of my points are going stale and not updating it get errors like this "Could not post write...
  22. Replies
    57
    Views
    5,336

    Poll: Matrix you are correct in what you say. I work...

    Matrix you are correct in what you say. I work for one of those big boys and the truth is that they all think that if they open up and customers get smart and realize they are not locked in then they...
  23. Replies
    57
    Views
    5,336

    Poll: A majority of the new controllers out on the...

    A majority of the new controllers out on the market use Linux operating system and the kernel core so opeing them up would not be an issue. As for the for the liability some have stated like...
  24. Replies
    30
    Views
    1,969

    You can do a lot of batch changes inside the xml...

    You can do a lot of batch changes inside the xml or px code. Just create one point the way you want it then find the lines of code for that point and do a search and replace in the code to replace...
  25. Replies
    8
    Views
    1,574

    The point limit only applies to RS232 which...

    The point limit only applies to RS232 which hardly anyone uses now anyways. Only limit is really how long you fingers can last to create all the points. The .pdf is very misleading as you need to...