Search:

Type: Posts; User: ntech64

Page 1 of 5 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    3
    Views
    899

    CAREFUL! Older MMI cables had a RJ11 (phone)...

    CAREFUL!

    Older MMI cables had a RJ11 (phone) end on them that accepted only 4 pins. The PXC series requires a RJ11 end that accepts 6 pins. There isn't any wires in the pin slot on each end, but...
  2. Replies
    37
    Views
    3,719

    ::DD:

    ::DD:
  3. Replies
    4
    Views
    626

    If you don't already know programming (or...

    If you don't already know programming (or scripting) from being in IT, then take a basic programming course to get the concepts down. Other than that, you'll have at least a passing familiarity with...
  4. Check for a receive light at a TEC. If you...

    Check for a receive light at a TEC.

    If you have one, then check your FLN baud rates.

    If not, make sure your FLN wires didn't get cut.

    Otherwise, you may have a bad MEC. There's only one UART...
  5. Replies
    4
    Views
    2,018

    This one is essential: TLA - Three Letter...

    This one is essential:

    TLA - Three Letter Acronym
  6. Replies
    2
    Views
    607

    How is server virtualization going to help system...

    How is server virtualization going to help system performance?
  7. Replies
    18
    Views
    3,906

    That version of the AEM Configuration Tool does...

    That version of the AEM Configuration Tool does not support the new AEM 2100. Manually configure the AEM using HyperTerminal.
  8. Replies
    18
    Views
    3,906

    What are the errors? What are you using to...

    What are the errors? What are you using to "download" to the AEM?

    :confused:
  9. Replies
    18
    Views
    3,906

    AEMs are just configured with a 9 pin to 9 pin...

    AEMs are just configured with a 9 pin to 9 pin null modem cable and Hyperterminal.

    Follow the Getting Started for "Setting Up APOGEE Ethernet Microserver". It should be darn close to seting up the...
  10. This virus attacks Siemens Industrial Control...

    This virus attacks Siemens Industrial Control Systems software. The Building Automation Software is safe... for now.
  11. Replies
    20
    Views
    3,240

    ????? :eek2: ?????

    ????? :eek2: ?????
  12. Replies
    9
    Views
    1,437

    Some systems index the device's information using...

    Some systems index the device's information using the device instance number. He may be running into an issue like that. I also have to agree with BACnet that unique instance numbers should be used...
  13. Replies
    4
    Views
    723

    Microsoft SQL Server also requires less...

    Microsoft SQL Server also requires less administration. A huge point of contention for me is that Oracle doesn't have the ability to auto-increment a table index without using sequences... which is a...
  14. Replies
    5
    Views
    1,307

    When you say "configuration" are you talking...

    When you say "configuration" are you talking about the different applications? (2023 = VAV with Hot Water Reheat)

    I'm pretty sure there's a different PDF for each TEC application. What application...
  15. Replies
    15
    Views
    2,427

    As BSunday21 noted, there are sometimes issues...

    As BSunday21 noted, there are sometimes issues with older firmware revisions co-existing with newer revisions. Generally, Siemens can provide a firmware build upgrade (not a major revision upgrade)...
  16. Replies
    37
    Views
    3,719

    The MicroTech II's are finicky devices... Make...

    The MicroTech II's are finicky devices...

    Make sure the devices have consecutive MAC addresses.
    I've sometimes had trouble writing setpoints at any priority other than 8.
  17. Thread: Daikin BACNet

    by ntech64
    Replies
    13
    Views
    1,903

    I've definitely done it before. It was a couple...

    I've definitely done it before. It was a couple of years ago and I don't remember the specifics, but I'll call BS on the Daikin rep.
  18. Replies
    6
    Views
    2,087

    Found this in the BACstac Installation Guide (see...

    Found this in the BACstac Installation Guide (see attached). I was only able to make sense of some of them... but it looks like there might be some settings buried in there that could help.
  19. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,244

    RENO provides the ability to dial a prefix (ex....

    RENO provides the ability to dial a prefix (ex. dial 9 to get an outside number), so that part isn't a problem. However, I've heard of problems when people try to use something other than a pure...
  20. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,244

    Default dipswitch settings should be fine. No...

    Default dipswitch settings should be fine. No modem programming... just Plug-and-Play.
  21. Default: 9600, 8, None, 1, None The speed may...

    Default: 9600, 8, None, 1, None

    The speed may have been changed... 38400 is the next one I would try.
  22. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,244

    This should be all you need:...

    This should be all you need:
    http://www.belkin.com/IWCatProductPage.process?Product_Id=65387
  23. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,244

    I don't think so... but it's been a little while...

    I don't think so... but it's been a little while since I've opened a new box.
  24. Thread: Siemens Apogee

    by ntech64
    Replies
    5
    Views
    1,258

    Contract customers get priority service... so it...

    Contract customers get priority service... so it might be worthwhile to get a contract if you think you may be requiring Siemens' services several times a year. Otherwise, you may be stuck with an...
  25. Thread: Apogee/Reno

    by ntech64
    Replies
    38
    Views
    4,244

    Reno likes external serial modems best... US...

    Reno likes external serial modems best...
    US Robotics V.92 External 56K Faxmodem - USR5686E
Results 1 to 25 of 117