  1. If it's 2002, it's a Reliatel board and not a...

    If it's 2002, it's a Reliatel board and not a UCP. Simply disconnect the BAYSENS from terminals 1,2,3,4 etc., hook up your new stat on the conventional thermostat connections R,Y,G,W etc. If there...
  2. Replies
    1
    Views
    186

    You want to use the Comm4 tool. Observe proper...

    You want to use the Comm4 tool. Observe proper polarity, and switch if necessary. I don't remember anything about the PCMCIA card, I've always used a Black Box Comm4 adaptor. If the polarity isn't...
  3. I would personally hw and not do the comm unless...

    I would personally hw and not do the comm unless it is in the spec. Regardless of mfg or protocol.
  4. RTAC software is Techview which is free to any...

    RTAC software is Techview which is free to any and all to download. TU is not required or necessary to configure anything. It'll be very hard for you to purchase a copy of TU yourself. Your best...
  5. Replies
    1
    Views
    235

    I'll take a shot in the dark here. The...

    I'll take a shot in the dark here.

    The sensor accuracy is +/- .25C. Which means if your factory calibrated test instrument is measuring 19C, the sensor would read anywhere between 18.75C and...
  6. Replies
    2
    Views
    196

    You'll need Rover. I'm about 99% sure. There will...

    You'll need Rover. I'm about 99% sure. There will be some configuration available through Summit, but I don't believe that you can change the unit type.
  7. Replies
    13
    Views
    405

    You tell me. Is your JACE using DSN B? I'm...

    You tell me. Is your JACE using DSN B? I'm guessing it's not, but I don't work with the JACE platform. Making a config change in Rover won't change anything on the Lon network. You have to tell...
  8. Replies
    9
    Views
    523

    The +1.5 is shown in the VAV, it's called the...

    The +1.5 is shown in the VAV, it's called the "occupied offset". This makes the UC vav setpoint logic similar to the vv550, or Lon in general, where the "setpoint" is the median and the offset is...
  9. Replies
    13
    Views
    405

    If you don't know your domain, connect Rover,...

    If you don't know your domain, connect Rover, service pin a device. You'll see a message in Rover stating something like "a service pin press was received on a different domain than the discovery...
  10. You should only need to command the Multi-State...

    You should only need to command the Multi-State Output - 7 for occupancy (1=occupied, 2=unoccupied). The other Binary Outputs that you mentioned are to enable/disable heating or cooling etc. not an...
  11. Replies
    8
    Views
    427

    I'm old fashioned, I still use the 0-10vdc/4-20ma...

    I'm old fashioned, I still use the 0-10vdc/4-20ma and dry contacts to VFD's so I don't connect comm to them unless specified in the job requirements. However, Trane TR200 drive= Danfoss VLT6000 if...
  12. I've never done this, however I believe that I...

    I've never done this, however I believe that I can provide some insight...

    Yes, you will need to create BACnet points inside the BCU. This is done by going to setup>inputs/outputs>"point type...
  13. You don't need Trane to do anything. What is the...

    You don't need Trane to do anything. What is the unit reporting back for active status, occupancy, etc.? Do they match what you're sending? Are there any field installed safties (duct detector,...
  14. Replies
    2
    Views
    284

    You are correct, MWU is only available through...

    You are correct, MWU is only available through the local HI. The Day Time Warmup points should be available through the LCI-I, but I'm not certain of the exact point names.
  15. Replies
    2
    Views
    555

    It doesn't appear that serialspy is available for...

    It doesn't appear that serialspy is available for download. The download center link was hidden, however serialspy isn't listed.
  16. Thread: Trane Rover

    by roadgear16
    Replies
    3
    Views
    522

    Summit and Rover are two different programs. ...

    Summit and Rover are two different programs. Rover is a configuration tool for unit controllers (AHU's, vav's, programmable controllers, etc.), and can be password protected separately from Tracer...
  17. Hopefully they're not using the data to actually...

    Hopefully they're not using the data to actually bill the tenant. I know I'm not paying an electric bill from the utility company unless they can prove to me that it's accurate (unless they under...
  18. Replies
    8
    Views
    460

    You can not do bindings manually between the IPAK...

    You can not do bindings manually between the IPAK and the BCU.

    I typically leave the RTU econ decision in auto unless I'm trying to coordinate multiple RTU's. Depending on the configuration from...
  19. Replies
    7
    Views
    258

    It appears that there is a TOD calendar patch. ...

    It appears that there is a TOD calendar patch. Do you have access to mytranecontrols or comfortsite? I vaguely remember this issue but never experienced it for my self. Here is a description of...
  20. Replies
    7
    Views
    258

    Man, maybe I should have looked at a calendar...

    Man, maybe I should have looked at a calendar before I posted that.

    The date is correct, but the day is off one. I've never encountered that problem. What version of Summit are you running? ...
  21. Replies
    7
    Views
    258

    I'm not exactly sure what you're asking. The...

    I'm not exactly sure what you're asking. The picture shows the schedule for "1st and 2nd floor conf/lobby" for the weekdays M-F. It appears that you have optimal events starting at 7:00am and...
  22. Replies
    4
    Views
    319

    Are you referring to a software BO/AO withing...

    Are you referring to a software BO/AO withing Tracer Summit, or a physical BO/AO on the MP581?
    Overriding a Summit point, BO/AO, will only change it's value being sent to the MP581. You'll have...
  23. If it's a reliatel just remove the RTCI board and...

    If it's a reliatel just remove the RTCI board and connect conventional T-stat connections to the RTRM. You can use your controller to control the unit. No need to completely gut the unit. If it's...
  24. Replies
    2
    Views
    309

    I found this in the archives, watch out for the...

    I found this in the archives, watch out for the spiderwebs and dust.
  25. Replies
    3
    Views
    458

    Verify that each RTU has a unique address set and...

    Verify that each RTU has a unique address set and you should be good. Granted those are the older UCP control boards which are safely 13+years old, so you may have a bad one or two. I think they...