Search:

Type: Posts; User: kwillmech

Page 1 of 14 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    4
    Views
    975

    Regardless or whether or not it is on a Lan, if...

    Regardless or whether or not it is on a Lan, if the JACE has an IP address then you are Bacnet/IP and the Bcu will require one as well to communicate with the JACE.
    The Bcu dip-switch sets the...
  2. Replies
    10
    Views
    1,219

    The 2001 date may just be a guess on their part. ...

    The 2001 date may just be a guess on their part. To know for sure check the board software revisions.


    This information applies to: INTELLIPAK ROOFTOP 20-130

    To install a LCI in an existing...
  3. Replies
    11
    Views
    1,836

    PANGEA? What do they think this is a...

    PANGEA? What do they think this is a one-continent world?
  4. Replies
    10
    Views
    1,219

    Sorry to hear that. Sometimes the thought of...

    Sorry to hear that. Sometimes the thought of communicating integration is great but that comes with a cost and you have to ask if its worth it.
  5. Replies
    24
    Views
    3,997

    kwillmech1972 AT yahoo DOT com ...

    kwillmech1972
    AT
    yahoo
    DOT
    com


    gracias carnal.
  6. Replies
    3
    Views
    957

    Radiant Systems.

    Radiant Systems.
  7. Thread: LCPEdit

    by kwillmech
    Replies
    8
    Views
    890

    Wear one of these....

    Wear one of these. http://news.thomasnet.com/images/large/009/9207.jpg
  8. Replies
    10
    Views
    1,219

    Why not replace the Intellipak modules with newer...

    Why not replace the Intellipak modules with newer versions? I'm sure the price is reasonable... Sorry just had to toss that it there.
  9. Replies
    3
    Views
    957

    Older ones or newer ones?

    Older ones or newer ones?
  10. Replies
    24
    Views
    2,380

    As for cables, you need a 9pin (db9) straight...

    As for cables, you need a 9pin (db9) straight through cable. "Connect your PC to the CH530 main processor using a standard 9-pin male/9-pin female RS-232 cable. "

    Techview is ONLY available at...
  11. Replies
    24
    Views
    3,997

    I have seen people post looking for ICE software...

    I have seen people post looking for ICE software quite regularly, but I have not seen anyone clearly say they have it. I too run into some york stuff from time to time and thought it might be nice...
  12. Thread: LCPEdit

    by kwillmech
    Replies
    8
    Views
    890

    Excellent idea! :D

    Excellent idea! :D
  13. Replies
    9
    Views
    817

    As I stated, you were thinking correctly for the...

    As I stated, you were thinking correctly for the VV550. This thread is regarding the Ucm. Different beast altogether.
  14. Replies
    24
    Views
    2,380

    CH530 is the controller on the chiller. Techview...

    CH530 is the controller on the chiller. Techview is the software used to configure it. Available on www.Trane.com here http://www.trane.com/Commercial/DNA/View.aspx?i=1271
  15. Replies
    9
    Views
    817

    No, you are thinking of VV550. The Ucm only...

    No, you are thinking of VV550. The Ucm only calibrates on power cycle or calibrate command.


    Not exactly, if the Ucm sees 0 flow and at 0% it will not go into Pressure Dependent Mode, it knows...
  16. Replies
    24
    Views
    2,380

    Sound like RTAC. Your LCI-C card will need two...

    Sound like RTAC. Your LCI-C card will need two setups. One in CH530 with Techview program, other in Rover. The Rover Flash Download Wizard can download the file for the model chiller you have.
  17. Replies
    22
    Views
    1,433

    To minimize shock on boiler you should have a...

    To minimize shock on boiler you should have a circ bypass. Since your customer can not afford this then the best you can do is reducing impact on loop. When the water is cold disable reheat...
  18. Replies
    24
    Views
    2,380

    What model chiller?

    What model chiller?
  19. Summit-dude, Remember the name Global Controls...

    Summit-dude, Remember the name Global Controls and Contracting? That is the exact kind of work they were after. Lots of money to be made there ya know.
  20. Thread: LCPEdit

    by kwillmech
    Replies
    8
    Views
    890

    Here (http://tinyurl.com/3y8lxm).

    Here.
  21. Replies
    13
    Views
    1,425

    Hmmm...

    Hmmm...
  22. Replies
    22
    Views
    1,433

    With your 30* temp rise and no way to bypass then...

    With your 30* temp rise and no way to bypass then I would just suggest abandoning the reset logic. Might be more trouble then its worth to adjust a 10* range. Instead look at other ways to be...
  23. Replies
    11
    Views
    1,005

    www.vmware.com

    www.vmware.com
  24. Replies
    24
    Views
    2,380

    If it is 22awg un-shielded it should be fine. ...

    If it is 22awg un-shielded it should be fine. The most important part is to keep all the wiring the same type and capacitance.
  25. Replies
    3
    Views
    555

    Decimal place limitations.

    Decimal place limitations.
  26. I do not understand your meaning here about the...

    I do not understand your meaning here about the unit using supply air temp as the setpoint. This could be a bad referenced value in the Summit editor.

    The Tuc can do cascade temperature control...
  27. Replies
    5
    Views
    888

    Does not sound right to me either. Where is this...

    Does not sound right to me either. Where is this TIM-E module located and what is connected to it?
  28. Correct non-isolated com-3 is a red card. Needed...

    Correct non-isolated com-3 is a red card. Needed if any of the Vav controllers on the link are VAV-I. If theyre all VAV-II/III/IV then com-4 is the link. Easy way to tell from the Command Unit is...
  29. Replies
    18
    Views
    1,934

    Data flow rate through the rs-232 interface. ...

    Data flow rate through the rs-232 interface.

    "Beyond the BCU memory sizing consideration, it is recommended that the total number of BACnet objects passing through an EIA-232 port be limited to...
  30. Me too.

    Me too.
  31. Replies
    29
    Views
    5,102

    Bmn and Pcl edit are required to save or restore...

    Bmn and Pcl edit are required to save or restore the Tracer 100 and Tracker panel database memory files.
  32. Replies
    8
    Views
    638

    Mine run on XP no problems.

    Mine run on XP no problems.
  33. The Vav's are com-3, the Command Unit goes away.

    The Vav's are com-3, the Command Unit goes away.
  34. Replies
    29
    Views
    5,102

    np.

    np.
  35. Replies
    18
    Views
    1,934

    Incorrect Jeff. Your comment suggests we never...

    Incorrect Jeff. Your comment suggests we never had Bacnet capability prior to 2000 when the Bmtw was released. The Bmts does and always has supported Bacnet via the serial, arcnet, and ethernet...
  36. Replies
    6
    Views
    1,731

    Its not is it. Use the Summit on-line help...

    Its not is it. Use the Summit on-line help buttons. Heres the Engineering Bulletin.
  37. Replies
    54
    Views
    11,012

    I own part of Trane. Who cares about the rest.

    I own part of Trane. Who cares about the rest.
  38. Replies
    11
    Views
    831

    Many people check public profiles for email...

    Many people check public profiles for email addresses so they can email stuff to help ...yours is not there.
  39. Replies
    29
    Views
    5,102

    Default login username is AAA, password is 1111. ...

    Default login username is AAA, password is 1111. Have fun!
  40. Replies
    6
    Views
    1,731

    What is in the Supply Air Temperature box below...

    What is in the Supply Air Temperature box below the Heat/Cool Input? This is the duct temperature the Vas communicates to the Vav box so it can decide its control action: direct acting or reverse...
  41. Replies
    4
    Views
    625

    Double check the unit configuration in your...

    Double check the unit configuration in your plugins. Try saving the configuration file from a similar unit and downloading to this one. It sounds like either a bad configuration file or bad board.
  42. The Quatech driver for Windows 98 does NOT work...

    The Quatech driver for Windows 98 does NOT work for Rover software. You need to be on Windows 2000 or XP in order for Rover to correctly manipulate the card.
  43. Replies
    18
    Views
    1,934

    All model Bcu's "speak" Bacnet on all ports:...

    All model Bcu's "speak" Bacnet on all ports: serial, ethernet, arcnet.

    Only analog and binary I/O points are visible to Bacnet scanners/software.

    Summit speaks Bacnet to the Bcu.
  44. Replies
    3
    Views
    596

    http://www.hvac-talk.com/vbb/showthread.php?t=1201...

    http://www.hvac-talk.com/vbb/showthread.php?t=120130
  45. Replies
    8
    Views
    1,027

    I assumed you were talking about a TUC already...

    I assumed you were talking about a TUC already being used to control a unit. If not then just use the fan output on the board to control whatever you want. Control the fan output through occupancy...
  46. Replies
    13
    Views
    1,102

    For a simpler and more cost effective...

    For a simpler and more cost effective installation I would suggest the mp501. Not nearly as robust as the mp581 but still effective for simple tasks. ...
  47. Replies
    8
    Views
    1,027

    Not sure I follow you there about the point...

    Not sure I follow you there about the point configuring...
    A new board comes from Trane parts without configuration.
    You can use EWARE or Rover Comm-4 to set the configuration.
    Valid...
  48. Replies
    8
    Views
    768

    Modem connection to VariTrac v12 with/out Tracker...

    Modem connection to VariTrac v12 with/out Tracker panel? You can not use Hyper-Terminal software.
  49. Thread: Trane tracer

    by kwillmech
    Replies
    5
    Views
    665

    The vav will re-calibrate itself after power-up...

    The vav will re-calibrate itself after power-up based on its address number. The Tracer100 will have a calibration schedule similar to Summit. Typically uses a binary point controlled by a Time Of...
  50. Replies
    8
    Views
    1,027

    Tucs can be configured for many different unit...

    Tucs can be configured for many different unit types.
    Many i/o points are unused with each configuration.
    There is no way to take advantage of the unused points.