Search:

Type: Posts; User: prostock

Page 1 of 2 1 2

Search: Search took 0.01 seconds.

  1. Thanks I will check them out.

    Thanks I will check them out.
  2. Looking for Dual channel BTUh meter, anyone familiar?

    I need to measure BTUh on AHUs with hot and cold water coils. I need to measure both. Does anyone know of a multi-channel meter that will do this? I prefer turbine but I will look at ultrasonic unit...
  3. Rather the dip switches, not jumpers.

    Rather the dip switches, not jumpers.
  4. The jumpers need to be set for 2 volts and temp...

    The jumpers need to be set for 2 volts and temp to read that sensor. That controller will read 250DegF when the sensor circuit is open and -50 when shorted. Wire a sensor directly to the AI. See if...
  5. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    908

    WTF?

    WTF?
  6. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    908

    Thanks. I am bidding on taking out some Carrier...

    Thanks.
    I am bidding on taking out some Carrier and planning on putting in somenew JCI stuff, likely on Bacnet. Do you think the comm wire will be sufficient? I am kinda doing this estimate blind...
  7. Thread: Carrier CCN

    by prostock
    Replies
    9
    Views
    908

    Carrier CCN

    Anybody know what comm protocol the Carrier CCN network is? Modbus maybe or some proprietary thing like JCI N2.
  8. Replies
    6
    Views
    879

    Dang, I should proofread for grammar. I think...

    Dang, I should proofread for grammar. I think much faster than I type.
  9. Replies
    6
    Views
    879

    Froz is right. In PMI and override creates...

    Froz is right.

    In PMI and override creates and SWO condition on the point. It is released with an "Auto" command. "Release all" will not release an SWO, it will however release process commands...
  10. Replies
    6
    Views
    879

    What is the site terminal? Is it a PC running PMI?

    What is the site terminal? Is it a PC running PMI?
  11. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    This job is FX10 OEM style boards factory...

    This job is FX10 OEM style boards factory programmed supplied in water water source heat pumps. It is the FX10 that is in question. All I would do is map them up and do some S/S and setpoint control....
  12. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    I am open to suggestions. I am not the king of...

    I am open to suggestions. I am not the king of this stuff but I need to be in the face of my customer. That is why I am on here looking to learn and chat with the folks who have taken the...
  13. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    CCIKelly, I have an FX20 in the building right...

    CCIKelly, I have an FX20 in the building right now, with an FX07 on N2 doing some small tower work. (I plan to get started with that) I will certainly have to add numerous additional FX20/60/70...
  14. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    Sam is right that the FX05,7,14,15,16 line is...

    Sam is right that the FX05,7,14,15,16 line is being discontinued. But it is on a sales basis. I am not sure if the FX10 is inclusive of this, as it seems to be a OEM type product. I could not buy one...
  15. Replies
    1
    Views
    668

    York service valve question

    I have to pump down and change out a York h2cb036s06a. I found at the service valves are not the allen type I am used to seeing. they had deep caps on them and when I took one off, there was a pin...
  16. Thread: PID wound up?

    by prostock
    Replies
    14
    Views
    1,441

    Remember that the IT in ASCs are in seconds so...

    Remember that the IT in ASCs are in seconds so you should have a big number for room control, like +/-600.
  17. Replies
    4
    Views
    517

    dude this is not hard to do but a SOB to explain....

    dude this is not hard to do but a SOB to explain. I am at the desk today and I will help you through it if you send me your base file. (.dxs)
  18. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    I found the full FX10 .pdf today and plan to read...

    I found the full FX10 .pdf today and plan to read it tomorrow. I hope that the program written and installed in these factory boards is sufficient and easy to map up and control. I hope that the...
  19. Replies
    8
    Views
    4,021

    Bill and retube are right. Move it if you have...

    Bill and retube are right. Move it if you have to, but you could just change the setpoint until you get what you need where you need it. If it is that critical, them someone ought to be putting some...
  20. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    Hey Sam, Its been awhile. Go Capitals! So...

    Hey Sam, Its been awhile. Go Capitals!

    So maybe I advise Lon on this project?
  21. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    LOL. I doesn't matter. Jci controls group...

    LOL. I doesn't matter. Jci controls group historicly is carried
    by auto and battery. They will never go away! I am an old asc / gpl /dx /pmi guy so I can make their stuff work. Now doing the fx...
  22. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    Only 40 per trunk. I have 60 per floor. 19200...

    Only 40 per trunk. I have 60 per floor. 19200 baud. I was reading on here about folks having a hard time with the BACNET being very slow and communication issues with the FX10. If it were bacnet/IP...
  23. Thread: FX10

    by prostock
    Replies
    28
    Views
    2,058

    FX10

    Got a client looking to install a bunch (over 500 eventually) new heat pumps. They are available with the FX10. Literature says Bacnet is 19200 and folks on here say to stay away. I have an FX20 in...
  24. Replies
    2
    Views
    633

    Thanks for the help. It seems to have fixed my...

    Thanks for the help. It seems to have fixed my problem, halfway. I can now open hvacpro files if I double click on them from windows explorer, but I still get the same "invalid file format" if I try...
  25. Replies
    2
    Views
    633

    HVACPRO "Invalid file format"

    I have been using hvacpro for years (ex JCI guy). I have some files from a few months ago that I need to get opened so I can do my asbuilts that are way overdue. Now I get the "invalid file format"...
  26. Replies
    3
    Views
    494

    I would second all that phreak said. I have used...

    I would second all that phreak said. I have used the Veris stuff alot, and had very little difficulty with it. I have done everything from single breaker apps to whole buildings with it. 27 pieces of...
  27. Replies
    11
    Views
    1,520

    hockey puck, viceman? Do you have a part name or...

    hockey puck, viceman? Do you have a part name or number?Maybe I can look at it to use.

    I usually use the Veris MX-1. Works great with DDC BI points. Needs power. Does the puck need power to work?...
  28. Replies
    11
    Views
    1,520

    I am with you sleddog, I just didnt want to build...

    I am with you sleddog, I just didnt want to build 17 of these if something cool exist. I try to remember that someone has probably done this before and a cool product got developed for just this app....
  29. Replies
    11
    Views
    1,520

    Drain pan leak detectors

    Anyone know of a cool product to monitor for water in a drain pan under a unit, with an associated "audible and visual alarms". Would love to just use a DDC controller to one light and horn location,...
  30. Replies
    4
    Views
    512

    I priced a setup with B&B electronics with some...

    I priced a setup with B&B electronics with some line-of-site antennas, they seems confident that it would work great. I didnt buy them cuz I didnt sell the project. Maybe it will work for you. I...
  31. Replies
    17
    Views
    1,527

    I have been getting "unknown controller errors"...

    I have been getting "unknown controller errors" for a while now. Mine happens right at the end of a download, while "waiting for controller reset". I have discovered that it takes the download and...
  32. Thread: oil detector

    by prostock
    Replies
    3
    Views
    474

    Perfect! They had exactly what I needed. Thanks

    Perfect! They had exactly what I needed. Thanks
  33. Thread: Old JCI Parts

    by prostock
    Replies
    6
    Views
    823

    Call Gene Casey at International Systems of...

    Call Gene Casey at International Systems of America. 502-499-9485
  34. Thread: oil detector

    by prostock
    Replies
    3
    Views
    474

    oil detector

    Has anyone seen a tape style oil detector, like the moisture detectors around lieberts and such? I need to monitor a generator room for oils spills and leakage. I have seen the one-spot type, and...
  35. Replies
    5
    Views
    500

    10-4, I went and read the rules. The stat...

    10-4, I went and read the rules.


    The stat is where I am heading with this thing also. I too thought about slaving multiple FCUs from one stat. Office space is constantly being re-configured,...
  36. Replies
    5
    Views
    500

    It has a Siemens system installed. The Building...

    It has a Siemens system installed. The Building folks are trying to keep them out of this.

    The programmable stat is my choice also. The small line voltage return air stats are about Removed each....
  37. Replies
    5
    Views
    500

    remote bulb stat

    If there is a better forum let me know.

    I need to replace the small operator t-stats on old FCUs. It is a remote bulb for RA control and has an adjustabel knob on top. Many are broken

    I also...
  38. Replies
    4
    Views
    643

    I agree on the potential problems and...

    I agree on the potential problems and liabilities. I really dont want to do the project for the same reasons. I was hoping to show the owner some options and let him run with it. I think now that I...
  39. Replies
    4
    Views
    643

    need to detect oil and stop sump pump

    I have a transformer vault on the side of a building with 2 sump pits and pumps to remove water. The pit is open with grates at the top. The pumps were replaced with grinder pumps so that the leaves...
  40. Replies
    8
    Views
    928

    You may be getting that error on every upload of...

    You may be getting that error on every upload of that controller, but dx9100s will not give that error if the programming in the current configuration and the controller match.

    Someone has...
  41. Replies
    8
    Views
    928

    If that were the case, you wouldnt you get that...

    If that were the case, you wouldnt you get that error on every upload?
  42. Replies
    8
    Views
    928

    LRS1-64 and EXD dont effect the uploading of GX...

    LRS1-64 and EXD dont effect the uploading of GX files.
    I they weren't already there, then they get added on every upload. No reason why, just a johnson thing. Delete or use freely.

    The modules...
  43. Replies
    14
    Views
    1,320

    oh yeah, you do not have to disconnect the...

    oh yeah, you do not have to disconnect the network connection, but you should undo anything you do if you have a supervisory system. Sometimes the DX, especially the older ones, would get jammed up...
  44. Replies
    14
    Views
    1,320

    the key is a jumper from 1 to 4. I have mashed...

    the key is a jumper from 1 to 4. I have mashed all the pins together before and had no problems with the dx. I constantly use my leatherman tool to jump it. the dumb key falls apart on your keyring...
  45. Replies
    3
    Views
    572

    Thanks, I will pass this info on to the customer...

    Thanks, I will pass this info on to the customer and it may help him make his decision. Anyone with any other experience with this please respond. I am sure that there are some unsuccessful attempts...
  46. Replies
    3
    Views
    572

    FEC and FX40, will they work together?

    Anyone out there tried to get an FEC to work on an FX40?
    I have a project that may want to do this. Both talk BacNet MSTP, but I am sure JCI has thrown a wrench in there somewhere. My purpose is not...
  47. Thread: NCM Demon??

    by prostock
    Replies
    23
    Views
    1,214

    dont delete gpl processes if you do not have the...

    dont delete gpl processes if you do not have the source code!
    they usually do more than one thing and you will get screwed because other stuff will stop working. Just remap the effected point with...
  48. Replies
    36
    Views
    3,926

    Bar-b-que salmon

    Y'all should try bar-b-qued salmon. Cook it on the grill just like you have indicated in the prior post, but use some bar-b-que sauce. It best if you spread it thin and get it to carmalize.
  49. Replies
    12
    Views
    1,202

    I haven't quite figured out which one does what...

    I haven't quite figured out which one does what level of control yet. In my head I think that one is like a UNT and another like a AHU and another like a DX9100. As I get into them I will learn more....
  50. Replies
    12
    Views
    1,202

    I take the FX 40 supervisor class in Feb. I will...

    I take the FX 40 supervisor class in Feb. I will take the field controller class asap.

    Mixed air single path AHUs mostly, lead lag pumping, plants, HX and towers.

    All the normal stuff.
    ...