Search:

Type: Posts; User: lwarren

Page 1 of 20 1 2 3 4

Search: Search took 0.02 seconds.

  1. Thread: NAE Lon to FX

    by lwarren
    Replies
    14
    Views
    417

    You can change the points to poll only in the Lon...

    You can change the points to poll only in the Lon Link Manager
  2. Thread: NAE Lon to FX

    by lwarren
    Replies
    14
    Views
    417

    You can go to the property sheet of the device...

    You can go to the property sheet of the device config under each device and set the config state back to config online.
  3. Replies
    29
    Views
    941

    I don't think your platform daemon is running. Or...

    I don't think your platform daemon is running. Or something is blocking the port.
    See this link, https://community.niagara-central.com/ord?portal:/discussion/DiscussionThread/13383
  4. Replies
    5
    Views
    250

    Use the elapsed active time numeric.

    Use the elapsed active time numeric.
  5. Replies
    8
    Views
    488

    Just go to Echelon's site and download NodeUtil...

    Just go to Echelon's site and download NodeUtil and you can extract it yourself.
  6. Replies
    20
    Views
    847

    The station you sent me looks pretty much the...

    The station you sent me looks pretty much the same as the one I got from Hutchey several years ago. It does look like he has renamed some of the nv's and made them custom snvt's. You will have to...
  7. Replies
    20
    Views
    847

    Can you send me the station and I will look at...

    Can you send me the station and I will look at it. Email is in my profile.
  8. Replies
    20
    Views
    847

    It should certainly have the terminal load nv's

    It should certainly have the terminal load nv's
  9. Replies
    20
    Views
    847

    My bad, I just knew I sent it to someone...

    My bad, I just knew I sent it to someone recently. The one I have I got from Hutchey several years ago.
  10. Replies
    20
    Views
    847

    It shouldn't be a problem if you are using the...

    It shouldn't be a problem if you are using the VVT Spyder App that I sent you. I have already done this on a job so I know it will work. You just need to link nvoTerminalLoad from the boxes to...
  11. Replies
    20
    Views
    847

    Let me dig it up and I will send it to you.

    Let me dig it up and I will send it to you.
  12. Replies
    16
    Views
    855

    Good point.

    Good point.
  13. Replies
    16
    Views
    855

    I have the Picoscope 2105, im not sure if they...

    I have the Picoscope 2105, im not sure if they still have that model but if they do I don't see any reason why it would not do what you needed for and RS485 network.
  14. Replies
    16
    Views
    855

    I have the picoscope. It is a USB scope that you...

    I have the picoscope. It is a USB scope that you run from your laptop. You can record and save the data. It has proven fine for troubleshooting Lon networks for me.
  15. Replies
    5
    Views
    367

    I think you mean Node Clash alarms. This would...

    I think you mean Node Clash alarms. This would indicate a problem on the Lon Network. IE, Not terminated properly, poor wiring installation, bad controller, noise on the network etc.
  16. Replies
    20
    Views
    847

    I have the one Hutchey did. I have used it. You...

    I have the one Hutchey did. I have used it. You just have to link the network points nvoZoneData from the boxes to the RTU and nvoAhuData from the RTU to the boxes. Then just set your terminal load...
  17. Replies
    1
    Views
    294

    Yes, I ran into this in July of last year. I have...

    Yes, I ran into this in July of last year. I have done many upgrades since then and have not seen this behavior in every one of them.

    This was the suggestion from Hutchey when I first ran across...
  18. Replies
    9
    Views
    571

    Well I need to clarify. It appears that price was...

    Well I need to clarify. It appears that price was to go from Central to Pro. The price is $299.00 per year for up to 100 computers I think.
  19. Replies
    9
    Views
    571

    I had to start paying for the free version last...

    I had to start paying for the free version last year because of the number of computers we had on it. It was $200.00. Now I see it is going to cost me $1000.00 per year.
  20. Never mind, I yelled at it long enough and it...

    Never mind, I yelled at it long enough and it started working.
  21. I guess I would like to verify that I have the...

    I guess I would like to verify that I have the right pinout connections in the attached image as well.

    454281
  22. Andover Infinity NetController to Jace Setup?

    I am trying to setup my first integration to a Net Controller model 9900 I believe to a jace via the Andover Infinity driver.
    I was able to get the pinout connection to go from the jace's 9 pin...
  23. Thread: FLON ABB Card

    by lwarren
    Replies
    2
    Views
    287

    What is parameter 9802 set to? It should be set...

    What is parameter 9802 set to? It should be set to EXT-FBA.
  24. Replies
    4
    Views
    507

    I have used GMX for several sites as well. They...

    I have used GMX for several sites as well. They do not require SSL connections.
  25. I use the Spyders all the time for plant control...