  1. Replies
    7
    Views
    361

    I guess what I am saying, before you try to get...

    I guess what I am saying, before you try to get the DS to properly control the humidity in any mode, DO YOU HAVE A PROPER vapor barrier??

    Read ICOM manual, 3.7.2 of the Humidity Sensor Reading...
  2. Replies
    7
    Views
    361

    It doesn't matter where and what the DH ' styles...

    It doesn't matter where and what the DH ' styles ' are selected - crappy vapor barrier, nothing can catch up.

    I can't answer why the DH goes off at the 60 range, but what tells me a lot is the...
  3. Replies
    7
    Views
    361

    Techie: A bit sparse on info, but the humidity...

    Techie:

    A bit sparse on info, but the humidity problems I see usually stem from poor to no vapor barrier.

    The only true Data Centre I worked in was double vapor barrier(ed ), air lock double...
  4. Replies
    9
    Views
    746

    Looks normal to me - ' seamed ' pipe will split...

    Looks normal to me - ' seamed ' pipe will split like that - -

    Do what HVAC_Marc says - call it a day.

    Freonguy
  5. Replies
    0
    Views
    241

    RITTAL ' Toptherm ' A/C issues

    Greetings:

    We have a RITTAL TOPTHERM spot cooler ( M/N # SK3384500 )air cooled A/C that was installed about a year ago.
    It replaced a similar unit that was over 12 years old - I was not involved...
  6. Like Doublebogey said - recover it into a tank...

    Like Doublebogey said - recover it into a tank with some integrity - a butt joint, soft solder assembly on the side of a can is asking for trouble.

    I have silver soldered the copper ' saddle '...
  7. Replies
    16
    Views
    2,348

    LU91tech: Yes, this is a new version compared...

    LU91tech:

    Yes, this is a new version compared to 2 others I commissioned less than 6 months ago - - -

    Freonguy CM
  8. Replies
    16
    Views
    2,348

    Push It : Yeah, it throws a guy for a loop,...

    Push It :

    Yeah, it throws a guy for a loop, especially when you have worked on so many that were all the same ( in the pump down regard ).

    After a long and hot installation, one system has no...
  9. Replies
    16
    Views
    2,348

    Gentle(persons): Just got off the phone with...

    Gentle(persons):

    Just got off the phone with Liebert - Tech Support.

    Seems as though the ' pump down ' mode has been disabled for about a year or so, scrolls or Carlyle - I suppose they should...
  10. Replies
    16
    Views
    2,348

    Six: As noted, AFTER 20 minutes of running, it...

    Six:
    As noted, AFTER 20 minutes of running, it still dumps the compressor immediately on shutting off the control OFF / ON @ the iCOM touch pad.
    I have worked on / commissioned well over 200...
  11. Replies
    16
    Views
    2,348

    Liebert Start up question(s)

    Greetings:

    Just a brain picking exercise - ( I have been working on Lieberts for nearly 30 years - iCOM trained , couple of AM/AG training sessions etc. )

    Just comissioning a VS053WUA000266A...
  12. Replies
    17
    Views
    2,452

    [QUOTE=SuperStar79;4402902]Im guessing the...

    [QUOTE=SuperStar79;4402902]Im guessing the compressor blew a gasket.

    SS79:
    I 'll send you 5 bucks if the compressor really blew a gasket. Just doesn't happen.
    Chillerwhisperer makes a good point...
  13. Replies
    20
    Views
    2,775

    [QUOTE=Tech Rob;14036911]Wow! Not many of them...

    [QUOTE=Tech Rob;14036911]Wow! Not many of them around! I think I have seen one or two in my travels. Oldest one I take care of at the moment is a 1991 model with the Level 10 controls. I upgraded...
  14. Replies
    20
    Views
    2,775

    ZW17: I have a few 1989/1990 vintage units here...

    ZW17:
    I have a few 1989/1990 vintage units here and they all have the ' 00 ' board which is the version just after what you have - I have worked on units like the one you listed, but I am inclined...
  15. Replies
    15
    Views
    1,723

    Heater issue

    Glennhvac:

    Without getting in to it, what a bout a spring wound timer ( 15 minute version ).

    It could be used to energize the CC, as it is rated for 230v, and you may even find one that handles...
  16. Replies
    53
    Views
    24,305

    MO99

    Thanks Toptech!!

    FreonguyCM
  17. Replies
    53
    Views
    24,305

    R-438a - opinions

    Thanks for the feedback so far gentlemen ( women ) - this Forum is a wealth of knowledge if we all share.

    Freonguy CM
  18. Replies
    53
    Views
    24,305

    R-438a - retrofit

    Boilerman:

    We are located on the West Coast where it never gets really warm - yes, I was aware that the capacity drop was in the 5% range, but, in my situation, most of the equipment in the Mill...
  19. Replies
    53
    Views
    24,305

    Toptech: Do you have the Copeland bulletin of...

    Toptech:

    Do you have the Copeland bulletin of which you refer to? Or it's number?

    We have used it in 7 systems so far at the Mill I work at, with good results. All A/C systems - Six Lieberts...
  20. Replies
    9
    Views
    1,283

    H2S ATTACKS!!

    Genduct:

    Yes, the copper gets attacked - but to a lesser degree.

    First off, copper and brass components turn black - a thick, scaly oxide forms, especially on suction lines where there is...
  21. Replies
    9
    Views
    1,283

    Holey joints !

    JSWIN:

    I am at a Pulp and Paper Mill - all coils are Heresite coated, and, unfortunately all equipment comes with Silfos joints. THe H2S is the culprit to be sure - I suggest using Easy Flo 45 as...
  22. Refrigeration / HVAC Work

    Danny:

    What exactly do you do now? I have been in the trade for over 30 years in Western Canada and cannot imagine doing it without doing gas work.

    Do you have a gas ticket?

    PM me if you...
  23. Replies
    5
    Views
    869

    ****

    Sorry, my bad - will get the proper designation -

    Freonguy
  24. Replies
    25
    Views
    3,033

    Potsibilities

    I work at a Pulp and Paper Mill - we use activated carbon ( Westvaco ) units to neutralize chemicals.

    I was once talking to a somewhat unsavoury chap - when he found out I worked at a P & P Mill,...
  25. Thread: O2 Leak

    by freonguy
    Replies
    6
    Views
    603

    Leak look out

    HVACkid:

    What about ultra sonic? The ones sold by the HVAC wholesalers are fair at best; I am at a Pulp and Paper Mill where the instrumentation guys have a $2300.00 unit that is unbelievable -...