Search:

Type: Posts; User: eyeLON

Page 1 of 7 1 2 3 4

Search: Search took 0.01 seconds.

  1. Replies
    10
    Views
    545

    If you're onsite, connect a serial cable and use...

    If you're onsite, connect a serial cable and use hyperterminal (speed set accordingly) to logon to the JACE. Menu will allow you to configure IP ports. DynDNS has worked well for us. It's cheap and...
  2. Replies
    5
    Views
    312

    Check your priority inputs. in1 thru in16.

    Check your priority inputs. in1 thru in16.
  3. Stop before it's too late! Get some assistance...

    Stop before it's too late! Get some assistance immediately.
  4. Replies
    9
    Views
    366

    You are right in that the Mediator is pretty much...

    You are right in that the Mediator is pretty much a dead dog. Cisco purchased the Mediator (and the company) from Richards Zeta a few years ago. So Cisco probably wouldn't be a good source for any...
  5. Replies
    9
    Views
    366

    Define "Everything"

    Define "Everything"
  6. Replies
    9
    Views
    366

    Got JACE?

    Got JACE?
  7. Replies
    2
    Views
    295

    I'm with the phreak. I teach a controls class at...

    I'm with the phreak. I teach a controls class at our local JC entitled "Control Systems Networking". The text book I use is entitled Building Automation, System Integration with Open Protocols. It's...
  8. Replies
    5
    Views
    301

    You also need to find out how the system was...

    You also need to find out how the system was originally configured. Did they use Echelon's LNS platform or was it integrated into Tridium. If Tridium, was it R2 or AX?
  9. Thread: Lon Scanner FX

    by eyeLON
    Replies
    1
    Views
    250

    This is just the updated version of Protocol...

    This is just the updated version of Protocol Analyzer that can sniff LON packets on an LNS network. Not sure what the manual you are referencing. PA allows you to observe a LON network and generate...
  10. Replies
    10
    Views
    336

    Hold on, LockwoodLakeman. Gazoo is referring to...

    Hold on, LockwoodLakeman. Gazoo is referring to the ECC-VAVS which was pre-programmed prior to the ECL line of programmable VAV controllers that use gfx to configure. The sequence may or may not be...
  11. Replies
    10
    Views
    336

    You need to add bindings for supply air...

    You need to add bindings for supply air temp->controller (nviDuctInTemp). Basically, the controller is programmed not to dump cold air in the space on heating. There's also an NV (nviWaterTemp) that...
  12. You're probably experiencing a problem Distech...

    You're probably experiencing a problem Distech identified last year that was patched (see attached). I don't know how you update your LON/Distech support files or what controllers you are using so...
  13. Have you looked at this post?...

    Have you looked at this post?
    http://hvac-talk.com/vbb/showthread.php?1014361-Shop-drawing-and-Point-list-Software&highlight=visio
    Osiyo has a ton of controls/Visio information on his website.
  14. Plain old PFM works much better and is easier to...

    Plain old PFM works much better and is easier to clean up.
  15. Replies
    16
    Views
    1,537

    Jeepers-Thermostats are not rocket science! The...

    Jeepers-Thermostats are not rocket science! The science is in the web-enabled part of the stats you mentioned. All the stats you listed will do well to maintain comfort in the space but will differ...
  16. Replies
    3
    Views
    381

    You've got several issues in trying to connect...

    You've got several issues in trying to connect the this system. First off, since you're using SI software to connect, this is an older Circon API system and not an LNS database. You need a backup...
  17. Replies
    16
    Views
    899

    There was a thread posted in 2012 regarding USB...

    There was a thread posted in 2012 regarding USB scopes.
    http://hvac-talk.com/vbb/showthread.php?1284951-Bacnet-comm-problems&highlight=picoscope
  18. Replies
    4
    Views
    452

    If you're stuck on keeping the original...

    If you're stuck on keeping the original controllers, you could install Tridium JACE for front end. If you update your LonWatcher to 3.x and are willing to make NO changes to your LNS database then...
  19. Replies
    3
    Views
    393

    Make sure supply air temperature from AHU is...

    Make sure supply air temperature from AHU is connected to box nvi for same, otherwise cooling will not engage.
  20. Thread: E Series JACEs

    by eyeLON
    Replies
    10
    Views
    722

    Not possible...SRAM is supported by hardware and...

    Not possible...SRAM is supported by hardware and firmware in v3.7 and later. Battery version works on different hardware and older versions.
  21. Replies
    8
    Views
    465

    VMWare still has a free version called "Player"...

    VMWare still has a free version called "Player" and is very solid. I use it all the time to run WIN XP on my laptop. Google it.
  22. Replies
    3
    Views
    304

    No, I think he is asking how to get the total...

    No, I think he is asking how to get the total number of zones calling for cooling at any given time.
  23. Replies
    12
    Views
    1,109

    Great to see members helping each other. Nice Job!

    Great to see members helping each other. Nice Job!
  24. Thread: Lon Bind

    by eyeLON
    Replies
    9
    Views
    600

    Echelon's LNS Report Generator works great. Lots...

    Echelon's LNS Report Generator works great. Lots of options.
  25. Replies
    7
    Views
    1,355

    Update your Java. Also remove any old versions....

    Update your Java. Also remove any old versions.
    www.java.com