    Hi All, Thanks for the time everyone spent...

    Hi All,

    Thanks for the time everyone spent looking over the post and replying.

    I thought I post an update and give some of my feelings on this whole situation as well.

    The more I thought...
  2. Replies
    52
    Views
    2,843

    The current outdoor temperature where I live is...

    The current outdoor temperature where I live is 86* F and the humidity is 40%. Inside the house is 75* and the humidity is 56%. There is a setting for changing the humidity in the house, which was...
  3. Replies
    52
    Views
    2,843

    Hi darctangent, Measured air volume at the...

    Hi darctangent,

    Measured air volume at the evaporator was 1426 CFM. This was tested with the filter in place. Filter is 20"X25"X5" - Healthy Climate X6675.

    The heat pump does have heat strips....
  4. Replies
    52
    Views
    2,843

    Return Static .3 Supply Static .1 Total ESP...

    Return Static .3
    Supply Static .1
    Total ESP .40

    Is that what you were looking for? Nothing on that form was in red. This was sent to me as Excel Attachment. On one of the pages "Entering Air...
  5. Replies
    52
    Views
    2,843

    Return Static - Before Coil Supply Static -...

    Return Static - Before Coil
    Supply Static - After Blower
    Measured air volume at evaporator 1426 CFM which falls into the parameters at 356.5

    Thanks.
  6. Replies
    52
    Views
    2,843

    OK - so it's either 16" or 18", right? Thanks.

    OK - so it's either 16" or 18", right? Thanks.
  7. Replies
    52
    Views
    2,843

    Thanks for the thoughts. I mentioned your point 1...

    Thanks for the thoughts. I mentioned your point 1 to the owner of the HVAC company yesterday. I left it in their hands to design a system that as they put it, would be perfect for my house. As...
  8. Replies
    52
    Views
    2,843

    Hi lkapigian, I talked the HVAC company...

    Hi lkapigian,

    I talked the HVAC company yesterday and they sent over the Commissioning Report. (CR) What numbers would you like to see?

    BTW I wasn't trying to give anyone the impression that...
  9. Replies
    52
    Views
    2,843

    I'll climb up into the attic tonight. I could...

    I'll climb up into the attic tonight. I could have sworn there was a 20" return there before with about 8' before the air handler. Now it's 17" and the unit is in the same position as the previous...
  10. Replies
    52
    Views
    2,843

    So a 20* drop would be typical? What are they...

    So a 20* drop would be typical? What are they doing in more extreme climates to get the temperatures lower? Let say Vegas where it might get to 115*, 95* is better than outside, but...
  11. Replies
    52
    Views
    2,843

    This was a SCE QI and I checked on SCE's website...

    This was a SCE QI and I checked on SCE's website and they are listed as a Platinum Installer. Funny the other companies said they were too, but I don't see them listed. They mentioned we'd get the...
  12. Replies
    52
    Views
    2,843

    I measured the diameter of the return. It's 17"...

    I measured the diameter of the return. It's 17" in diameter. The filter size is 20"X25"X5" - Healthy Climate X6675. And yes the other HVAC companies were going with another 5 ton to replace the...
  13. Replies
    52
    Views
    2,843

    Hi jimj, The HVAC company. I curious to why...

    Hi jimj,

    The HVAC company. I curious to why getting the hot air out of the attic could be a bad thing. Wouldn't cooler air where the air handler/evaporator is located be a good thing?
    If you got...
  14. Replies
    52
    Views
    2,843

    Hi kdean, I understand what you mean by...

    Hi kdean,

    I understand what you mean by radiant heat from everything inside the house, but everything was at 79* F before I lowered the temperature. I just talked to the service tech that's at my...
  15. Replies
    52
    Views
    2,843

    The humidity when started was at 45% in the...

    The humidity when started was at 45% in the house. This system can maintain a certain humidity level. It stayed at the 45%. There's only one return, but I was told it was sized correctly and located...
  16. Replies
    52
    Views
    2,843

    Unreasonable Cooling Expectations?

    A few years back I was looking for advice on a new install. http://hvac-talk.com/vbb/showthread.php?1155451-Recommendation-For-New-Heat-Pump

    It took a few years, but I finally bit the bullet and...
  17. Replies
    14
    Views
    2,214

    Hi Krzyd, That's what the second HVAC...

    Hi Krzyd,

    That's what the second HVAC contractor mentioned. 5 ton was actually undersized. He said we have a couple of options. There was a new 6 ton unit out there, or living with a 5 ton, or...
  18. Replies
    14
    Views
    2,214

    Hi Krzyd, The home is in Canyon Lake,...

    Hi Krzyd,

    The home is in Canyon Lake, California....
  19. Replies
    14
    Views
    2,214

    "The TRUE highest cost system is the system not...

    "The TRUE highest cost system is the system not installed properly..."

    Isn't that the truth vstech!
  20. Replies
    14
    Views
    2,214

    Thanks for the replies. The second guy that...

    Thanks for the replies.

    The second guy that came out called me back a couple of days ago. He apologized for not spending more time on the house when he was here. He said he wanted to get back out...
  21. Replies
    14
    Views
    2,214

    Recommendation For New Heat Pump

    11 years ago my wife and I bought a new home in Canyon Lake, California. It was a Spec home and we got into it at a point where we could make some changes. The builder was constantly patting himself...