    Sounds like 1800LIEBERT time.

    Sounds like 1800LIEBERT time.
  2. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,022

    This right here could save us some headaches with...

    This right here could save us some headaches with some customers fooling with their network all the time...
  3. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,022

    Cisco then sold Linksys to Belkin almost two...

    Cisco then sold Linksys to Belkin almost two years ago, another company I dont trust with the job. Who knows who is providing software updates for those now.
  4. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,022

    Excellent point, I've also been burned by cheap...

    Excellent point, I've also been burned by cheap consumer routers and I'll never get anything with the words Dlink or Linksys on them again. I'm thinking some of the better SOHO routers from the big...
  5. Thread: BBMD vs VPN

    by MaxBurn
    Replies
    43
    Views
    3,022

    That's an interesting comment on the speed...

    That's an interesting comment on the speed difference. I'm not sure why that might be.

    How are you all handling the tech training for these VPN devices deployment, repair and troubleshooting?
    ...
  6. Replies
    3
    Views
    361

    Planning the network layout for devices that need...

    Planning the network layout for devices that need to talk to each other is one that is starting to be an issue on some sites I've seen. Good mention kontrol.
  7. Replies
    20
    Views
    509

    I don't believe it is, all you are really doing...

    I don't believe it is, all you are really doing with he switches is changing the media type on the CMnet port. So if it's part of the same system that could be a concern. Can you download to the...
  8. Replies
    20
    Views
    509

    I guess the key question is does it still work on...

    I guess the key question is does it still work on ARCnet if you put it back? ;)

    Other random thoughts
    For MS/TP the other dip switches need to be left off. You don't want to wire to port A or...
  9. Replies
    20
    Views
    509

    Is this a SiteLink-12 2mb with no network port?...

    Is this a SiteLink-12 2mb with no network port? Or is it a SiteLink-12E with a network port?

    IF a SiteLink-12 2mb currently working on ARCnet you should be able to move the ARCnet/9600/38400 3 pin...
  10. Replies
    6
    Views
    453

    How difficult is it to get the right parts?

    How difficult is it to get the right parts?
  11. Replies
    22
    Views
    1,572

    Submit to wall of shame?

    Submit to wall of shame?
  12. Replies
    4
    Views
    769

    If I remember correctly to pull info out of the...

    If I remember correctly to pull info out of the SiteLink you want modbus function code 3 which results in a 4xxxx register request.

    I think the intellislot cards support both function code 3 and...
  13. Replies
    4
    Views
    273

    I've had some trouble with this driver in the...

    I've had some trouble with this driver in the past. Take a look at the network points page and pay attention to the count down timers to the next point refresh. See if they stick at zero, if they are...
  14. Replies
    16
    Views
    1,013

    Non union here and always been non union. I have...

    Non union here and always been non union. I have worked with union installers in the past and in general I thought they did a good job but it wasn't ever possible to be quick with them.

    One of my...
  15. Replies
    9
    Views
    524

    Some of the OEM's don't even download source...

    Some of the OEM's don't even download source files for the same reason.
  16. Replies
    5
    Views
    339

    RC642D is still available but I hesitate to...

    RC642D is still available but I hesitate to mention it because you need ALC tools to program it. There is some modes where they can be set up with dip switches but not sure how useful that is on...
  17. Replies
    5
    Views
    339

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  18. Replies
    5
    Views
    339

    I had a big problem with an OEM KMC FlexStat and...

    I had a big problem with an OEM KMC FlexStat and as such I wouldn't recommend it.
    We didn't get into programming the stat at all though, used it as Bard supplied. They would all start...
  19. Replies
    3
    Views
    400

    On the LGR properties page there is a modstat...

    On the LGR properties page there is a modstat button, below that button there is a "show bindings" button. Hit that and give us the results here. If you don't have bindings you aren't going to be...
  20. Replies
    20
    Views
    913

    On the ALC WebCTRL side of things the batteries...

    On the ALC WebCTRL side of things the batteries on older modules seem to be good for 8+ years with the 2330 or 2325 button batteries. The newer modules with the CR123 can go quick if it sees a lot of...
  21. Bard OEM KMC BACnet stat and Dehumidification

    We have three wings of Bard units with OEM KMC stats all running on BACnet MS/TP. Just noticed a problem with their dehumidification sequence. Or a problem with my understanding on how to run it.
    ...
  22. Replies
    6
    Views
    308

    Good point, I forgot about that. Do you know what...

    Good point, I forgot about that. Do you know what linux distro they are using on that box?
  23. Replies
    6
    Views
    308

    This is for the black box server that i-Vu comes...

    This is for the black box server that i-Vu comes on right? Seems a little under specc'd to me, for WebCTRL I've been recommending a minimum of 4gb ever sense 7 shipped and a little before honestly....
  24. Replies
    17
    Views
    1,208

    Thank you, my email is in my profile here, just...

    Thank you, my email is in my profile here, just click on my name.
  25. Replies
    17
    Views
    1,208

    Nope.

    Nope.
  26. Replies
    17
    Views
    1,208

    Regarding the KMC flex stats does anyone have a...

    Regarding the KMC flex stats does anyone have a BACnet point list for them? Something with point descriptions?

    We worked from a discovery and seemed to get things working after adding a couple...
  27. Replies
    6
    Views
    402

    Is this for WebCTRL? ALC does tend to lag in...

    Is this for WebCTRL? ALC does tend to lag in getting a patch out after finding some new java update breaks something for 5.5 and lower.

    Your dealers service dept should be able to send you the...
  28. Replies
    6
    Views
    402

    Constant annoyance, I'm so glad we don't need...

    Constant annoyance, I'm so glad we don't need java anymore with the latest version.
  29. Replies
    29
    Views
    1,649

    I have a couple of these, one for the laptop and...

    I have a couple of these, one for the laptop and one for me. They fit in my backpack. About $9.

    http://www.dickssportinggoods.com/graphics/product_images/pDSP1-10886923p275w.jpg

    I must admit...
  30. Replies
    3
    Views
    364

    That driver suggests that you are looking at an...

    That driver suggests that you are looking at an integration already, to a Dataguard system. You will likely find something between 200 and 1000 points of integration under that LGR. The points in the...
  31. Sounds like you need a local account added to...

    Sounds like you need a local account added to that computer so you can login to it with no network access. If it's normal for it to not have network access than that's not really optional.
  32. Replies
    3
    Views
    307

    Depending on what version of software the LGE was...

    Depending on what version of software the LGE was used under there are two different ways to put the IP in.

    If it is "legacy" exec 6 it needs to be programmed with supervision or webctrl as a...
  33. Replies
    9
    Views
    1,221

    It might already depending on how it was...

    It might already depending on how it was programmed.

    Turn it off and move the ARCnet/9600/38400 jumper to the 9600/38400 side and turn dip switch 1 on for 38,400 or off for 9600. Wire your MS/TP...
  34. Replies
    8
    Views
    644

    Thanks for sharing! Wonder how many hours of...

    Thanks for sharing!

    Wonder how many hours of programming went into that thing? Each one had to be a one off production I bet.
  35. Replies
    4
    Views
    358

    Yes just some basic due diligence before you call...

    Yes just some basic due diligence before you call them back but it does seem to be that device that's the issue.
  36. Replies
    4
    Views
    358

    Does your module work right next to the device...

    Does your module work right next to the device you are reading?

    Do the other usual wire checks, ohming to each other and each to ground etc.

    Can you get modscan and a communication adapter to...
  37. If you are concerned with the wall contaminating...

    If you are concerned with the wall contaminating the temp reading of the stat I don't think you need a new stat, just add some insulation behind the stat. Should be a foam wall plate backing...
  38. Replies
    21
    Views
    1,559

    I'm now carrying a fluke 376 with integrated amp...

    I'm now carrying a fluke 376 with integrated amp clamp and back light, I've taken a real liking to it. For ages I've carried the various versions of the fluke 77 and I still have one but that's...
  39. Replies
    8
    Views
    354

    Seconded, I ran into this as well. The new ZN...

    Seconded, I ran into this as well. The new ZN modules are shipping with updated hardware which requires a 6.xx.xxx module driver.

    Basically the stance of ALC is always use the latest module...
  40. Replies
    10
    Views
    464

    What got me ahead or on track etc was taking the...

    What got me ahead or on track etc was taking the equipment and software home and taking the time to understand what's going on and nailing how to do certain tasks. Ask to take some things home (on...
  41. Replies
    4
    Views
    666

    Yes, on the ALC side there are several updates...

    Yes, on the ALC side there are several updates you need to view trends with the most recent java version. For us the patches are posted on ALC support site, do you have such a thing?
  42. Replies
    5
    Views
    365

    Hey ControlsFreak, where do I get seeds for one...

    Hey ControlsFreak, where do I get seeds for one of those?
  43. Replies
    1
    Views
    224

    As I understand it that isn't a comm port, it's...

    As I understand it that isn't a comm port, it's for bias and termination.

    http://www.ccontrols.com/pdf/TD0712000I1.pdf
  44. Replies
    9
    Views
    502

    If you want to run anything in the LGR yes, it...

    If you want to run anything in the LGR yes, it has to be an execB equipment file.

    From the cut sheet: The Hybrid LGR is supported in WebCTRL v4 SP1b or later systems.
  45. Replies
    9
    Views
    502

    The hybrid LGR is a way to go, you can run legacy...

    The hybrid LGR is a way to go, you can run legacy CMnet off of port S1 and new ARCnet modules off of that port. The only drawback I can think of is you can't run a legacy FB in it.
  46. Replies
    2
    Views
    391

    As I understand it they are using HTML5 somehow....

    As I understand it they are using HTML5 somehow. I don't really know at that level but you don't need java or flash for most of WebCTRL now.
  47. Yes, before I made the switch I had OSX running...

    Yes, before I made the switch I had OSX running in a VM too.
  48. Thread: Control Jobs

    by MaxBurn
    Replies
    3
    Views
    492

    I'm not sure, maybe you want to bring that up to...

    I'm not sure, maybe you want to bring that up to the committee?
  49. Replies
    14
    Views
    1,483

    Do you have a make and model number to share with...

    Do you have a make and model number to share with us? Does it have the Google play store on it?
  50. Thread: Control Jobs

    by MaxBurn
    Replies
    3
    Views
    492

    I believe it's limited to professional members...

    I believe it's limited to professional members but, yep.
Results 1 to 50 of 653
Page 1 of 14 1 2 3 4
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event