Search:

Type: Posts; User: ctrlguy

Page 1 of 20 1 2 3 4

Search: Search took 0.04 seconds.

  1. I have since installed several 50 series...

    I have since installed several 50 series controllers. Every point can be accessed and adjusted/overridden and it displays network variables from other controllers (haven't tried the BACnet version...
  2. Replies
    38
    Views
    2,023

    First choice for Lonworks would be Distech gfx. ...

    First choice for Lonworks would be Distech gfx. For BACnet, it would be Distech gfx.
  3. Replies
    4
    Views
    300

    Another option would have been to use an LNS tool...

    Another option would have been to use an LNS tool (Lonmaker, etc) and the Honeywell plugin.
  4. I've had one on order for a couple of weeks -...

    I've had one on order for a couple of weeks - still no sign. I was disappointed to hear the schedule can't be edited through the display - yet - they're working on it. We use a lot of Distech too...
  5. Replies
    49
    Views
    5,063

    Not to dig up a fossil, but I have a project with...

    Not to dig up a fossil, but I have a project with Data Aire units with LON cards and it appears they still haven't figured out how to build a proper Lonworks interface or gateway for an LNS system. ...
  6. I know better than that. I was referring to the...

    I know better than that. I was referring to the segment. There are 3 routers.
  7. Thanks for the reply. The wire is 22-2 LON...

    Thanks for the reply.

    The wire is 22-2 LON wire (non-shielded). The network segment is double terminated daisy-chain with a Loytec FT-10/FT-10 router. I have 160 devices communicating fine on...
  8. Control Techniques Commander SK VFDs with LON Card

    As part of a large job, I need to integrate 14 domestic water pressure booster pumps with Emerson / Control Techniques (how many business names do those people need??) Commander SK VFDs into an LNS...
  9. Assuming there are 2-way valves on the job and...

    Assuming there are 2-way valves on the job and the pumps were designed for a 100% call on all valves, the proper procedure would be to open all the valves, run the pump at 60 Hz, measure the...
  10. Replies
    4
    Views
    350

    I'm using Lonwatcher. Echelon sent a replacement...

    I'm using Lonwatcher. Echelon sent a replacement and I have the same problem. I have other 4.04.119 units out there working fine. I think my database is possessed.
  11. Replies
    4
    Views
    350

    SmartServer Schedule Problem

    I have an iLON SmartServer (4.04.119) which continuously reboots if I apply an exception schedule (like a holiday) to the scheduler. Echelon has acknowledged that it's a bug that will be addressed...
  12. Replies
    3
    Views
    853

    American made thermostat

    I'm doing a job with Obama bucks involved that requires "Buy American" products. Does anyone know of an American made line voltage thermostat and remote bulb temperature controller?
  13. Replies
    30
    Views
    2,149

    Maybe I'm misunderstanding what you're trying to...

    Maybe I'm misunderstanding what you're trying to do, but if you're trying to use a temperature from a hardware input on one device as a temperature in a gfx device, you're going about this the wrong...
  14. Replies
    6
    Views
    523

    From the user guide:

    From the user guide:
  15. Replies
    4
    Views
    575

    I've used a variety of sensors with Distech and...

    I've used a variety of sensors with Distech and yeah, I just create a translation table. In gfx, you can save them as a code snippet.
  16. Replies
    2
    Views
    233

    I set up the forwarding on the remote end and I...

    I set up the forwarding on the remote end and I know that works. The LAN was set up by others, but I'm assuming since Config Server can communicate over 1629 and I can access the RNI on 1628, that...
  17. Replies
    2
    Views
    233

    IP852 Network Problem

    I have an LNS 3.02 Lonworks IP852 network consisting of an iLON100e3 with IP852 enabled and two iLON600s (version 1.06.01). The iLON100 and one of the 600s are on the LAN. Another 600 is connected...
  18. I've had a problem - had to change it manually...

    I've had a problem - had to change it manually and at least on some computers or browsers, I get a time error (PC and iLON don't match). I haven't had time to trace it down.
  19. Replies
    2
    Views
    447

    Your connection is fine, but there's no program...

    Your connection is fine, but there's no program in the controller. There may be a backup in the memory of the controller which you can restore using the XI582. Otherwise, you'd need to have the...
  20. Thread: JCI plugins

    by ctrlguy
    Replies
    2
    Views
    470

    I've used the Johnson LXs because Distech was...

    I've used the Johnson LXs because Distech was unacceptable to an engineer. I loaded them with the Distech .apb or .nxe and used the Distech plug-ins (or wizards) because I had them.
  21. If the original programmer did his job correctly,...

    If the original programmer did his job correctly, there is a copy of the program written to the non-volatile memory in each controller. Use the restore function in the FreeProg plug-in (or wizard)...
  22. Replies
    3
    Views
    456

    What software are you using?

    What software are you using?
  23. Replies
    9
    Views
    748

    It basically can't be done. With regard to...

    It basically can't be done.

    With regard to configuring W7750C, if I recall correctly, you can configure them as B models using the pulse width modulation setting and the controller will output...
  24. Replies
    24
    Views
    1,364

    The I/O is Lonworks, so you need something with a...

    The I/O is Lonworks, so you need something with a lot of network variables and some control logic capability to replace the XCL5010s. Sounds like a job for Loytec or possibly a JACE.
  25. Would you be located anywhere near Mt. Desert...

    Would you be located anywhere near Mt. Desert Island? Just an informed hunch. You don't have to answer.
Results 1 to 25 of 500
Page 1 of 20 1 2 3 4