Search:

Type: Posts; User: controldude

Page 1 of 12 1 2 3 4

Search: Search took 0.02 seconds.

  1. Replies
    15
    Views
    739

    Also if your the Integrator it's your...

    Also if your the Integrator it's your responsibility to control the unit not Trane.
  2. arcnet drivers available were for xp/2000 and...

    arcnet drivers available were for xp/2000 and older machines. Win 7 has no known drivers at this time.
  3. The multiplier and offset sets your min and max...

    The multiplier and offset sets your min and max assuming 4 is min and 20 is max.
  4. I've only seen 2 of these in Gun Barrel/ Boulder,...

    I've only seen 2 of these in Gun Barrel/ Boulder, Co. sorry no info though.
  5. The other thing you need to know is if the input...

    The other thing you need to know is if the input is setup as current this needs to be done with Rover The Tracer MP503 has four inputs. Each input can be configured to be
    binary, thermistor, 0–20...
  6. Multiple options need more info FCS521-SD-420E...

    Multiple options need more info
    FCS521-SD-420E 0-10A 20A 50A 1% 4-20mA
    FCS2151-SD-420E 100A 150A 200A 1% 4-20mA
    FCS521-SP-420E 0-10A 20A 50A 1% 4-20mA
    FCS2151-SP-420E 100A 150A 200A 1% 4-20mA...
  7. Hey Crabby, He did take a new job and I know he...

    Hey Crabby,
    He did take a new job and I know he was tired of the Union BS for a manager. I would have worked for him years ago but I won't do the union thing either I rely on my abilities period...
  8. What type sensor and min and max of it's range

    What type sensor and min and max of it's range
  9. Replies
    8
    Views
    787

    no you can't talk to a comm4 rtu just vav's and...

    no you can't talk to a comm4 rtu just vav's and tuc's, Varitrac software will allow you to see what the rtu is doing. it probably is off on hi/lopressure switches or economizing hard to say not...
  10. Thread: Trane WCIs

    by controldude
    Replies
    8
    Views
    1,029

    It also makes the Sensor's networkable instead of...

    It also makes the Sensor's networkable instead of just going to it's own UC controller they only have zigbee radio's now. You can also average temps with them now too.
  11. Replies
    19
    Views
    2,471

    1 hour service call and if your there Priceless...

    1 hour service call and if your there Priceless knowledge from 1 hour's worth of work if they charge you a penny more you've been had!
  12. Replies
    6
    Views
    1,190

    how does your ID number keep changing unless your...

    how does your ID number keep changing unless your trying to put it on another computer!
  13. Also make sure you clear out your cache it could...

    Also make sure you clear out your cache it could be bringing up the original stored in your browser.

    Good Luck!
  14. Use I.E. 11 or Google Chrome version...

    Use I.E. 11 or Google Chrome version 40.0.2214.115 m also Animations rarely work directly in the server you need to remote to it for animations.
  15. Replies
    1
    Views
    457

    NO

    NO
  16. Replies
    9
    Views
    1,411

    Then all you have to do is Print on the remote...

    Then all you have to do is Print on the remote machine as a PDF and copy the report to your computer. That's all I do.
  17. Replies
    9
    Views
    1,411

    can you get remote access to that computer?

    can you get remote access to that computer?
  18. Replies
    5
    Views
    1,734

    longview

    longview
  19. Replies
    3
    Views
    798

    Why do you need sp13 just because it exists? It...

    Why do you need sp13 just because it exists? It is for the new Comm3/4 Bridge if you don't have the bridge you won't need the SP!
  20. Replies
    33
    Views
    2,972

    I think I would get the Emerson guy out for an...

    I think I would get the Emerson guy out for an hour and be done then have your IT Dept. set this as a Vlan and make sure they know it is for hvac including their cooling units and not F with it again.
  21. Thread: Snow Melt

    by controldude
    Replies
    20
    Views
    3,282

    I only shoot for 32-33 deg surface temp due to...

    I only shoot for 32-33 deg surface temp due to our snoww is so dry it will evaporate before the moisture sensor sees it that is also why I use a min run time.
  22. Thread: Snow Melt

    by controldude
    Replies
    20
    Views
    3,282

    This is how Iv'e been doing it. I haven't been...

    This is how Iv'e been doing it. I haven't been doing an idling or reset but they both make sense.
  23. Okay, It's 92 deg. and 9% rh currently in Apple...

    Okay, It's 92 deg. and 9% rh currently in Apple Valley. My question is do you have this problem all day long or are you guys coming home to a system that is turned off all day then trying to get it...
  24. Replies
    9
    Views
    2,809

    You are correct Iguess I was taking the easy way...

    You are correct Iguess I was taking the easy way out and I have used forwarding on a few jobs before so not sure why it's not working on yours but here's a classic tech support question is your...
  25. Sounds like a perfect time to upgrade with...

    Sounds like a perfect time to upgrade with comm3/4 bridge to an SC I've done a few so far and have had great results!
  26. Replies
    9
    Views
    1,558

    not everybody's controller can do that. nice...

    not everybody's controller can do that. nice feature
  27. Replies
    15
    Views
    1,952

    Crabby your right about the terminator but that...

    Crabby your right about the terminator but that is for Bacnet they are working on a Lon system it just needs the Resistor
  28. Replies
    1
    Views
    767

    Did you try Johnson Controls?

    Did you try Johnson Controls?
  29. Replies
    4
    Views
    759

    Not entirely true I even found one of our Test...

    Not entirely true I even found one of our Test and Balance guys had a full rover setup which I thought was weird but I'm not the salesman so what can I say.
  30. Replies
    9
    Views
    2,235

    Check the DJM board I had 1 that kicked my...

    Check the DJM board I had 1 that kicked my butt.Finally found pushing on the board in the right place would kill the pilot solenoid and lock out the burner. All it was is bad solder connections. Good...
  31. YK Optiview rev k Lon snvt sheet with enumerations

    Anyone have a copy of a snvt list for JCI/York model# YKGEEXP9-ERG I don't know what all the fault codes are and they had a couple of snvt's I wasn't sure about.
  32. Replies
    11
    Views
    3,429

    To the new guys First post more questions often....

    To the new guys First post more questions often. You might find what your looking for. Also Google Images has a pretty good option for a lot of Manufacturers Products. Not to be a total ass but your...
  33. @Denhvax:Tell J Hep I said Hi!

    @Denhvax:Tell J Hep I said Hi!
  34. Replies
    20
    Views
    2,627

    It may be supported but not yet!

    It may be supported but not yet!
  35. Replies
    3
    Views
    1,136

    385831 Did you enter the BCU's IP address...

    385831 Did you enter the BCU's IP address into ES?
  36. Replies
    9
    Views
    1,932

    Varitrac isn't (comm5) or Lon the interface...

    Varitrac isn't (comm5) or Lon the interface between the Tracker and Varitrac is Lon and any other devices outside of the Varitrac system are also Lon ie: other stand alone rtu's, mp503's, and so on.
  37. Thread: DanFoss

    by controldude
    Replies
    7
    Views
    1,702

    Thanks, Mike

    Thanks, Mike
  38. Thread: DanFoss

    by controldude
    Replies
    7
    Views
    1,702

    I am having problems with the Embedded card as...

    I am having problems with the Embedded card as well I found the mac Address I set it too which was 4 I couldn't find it on the comm link changed it to 8 then it worked I only had 2 other devices on...
  39. I'm in for a ticket but I didn't here anything...

    I'm in for a ticket but I didn't here anything about beer yet!
  40. If you don't have Rover it's real simple hire a...

    If you don't have Rover it's real simple hire a Trane Tech to do it for you.
  41. Try Whisler in Denver, www.whislerbearing.com/

    Try Whisler in Denver, www.whislerbearing.com/
  42. At minimum I would make the system v16 sp8...

    At minimum I would make the system v16 sp8 preferably v17 sp11 you will need a computer w/ winxp pro or newer, lon board@(BCU), zn520, wire commissioing and assigned to bcu should take 10 minutes. lol
  43. Replies
    28
    Views
    4,269

    Are these on tracer summit or standalone, if...

    Are these on tracer summit or standalone, if summit write a cpl to lock out mech cooling when you only want economizer enabled.
    If standalone lockout comp at terminal strip @ comp1 & 2 disable...
  44. Replies
    55
    Views
    9,933

    incontrol nailed it!! ...

    incontrol nailed it!! I...
  45. Replies
    6
    Views
    1,120

    Open says a me

    Open says a me
  46. Replies
    9
    Views
    1,932

    Thank You mallron

    Thank You mallron
  47. Replies
    9
    Views
    1,932

    CCPIII was never intended for integration!

    CCPIII was never intended for integration!
  48. Replies
    48
    Views
    6,503

    Amigo, and Dapper this is the one I was referring...

    Amigo, and Dapper this is the one I was referring to is Trane.
  49. Replies
    17
    Views
    3,173

    I am a ham radio operator and today they should...

    I am a ham radio operator and today they should change their name to Cell Phone Shack I'm suprised the guy even knew where the resistors were let alone variable our store is a complete loss. But I...
  50. Replies
    2
    Views
    880

    v6 is out of date so you might as well up date...

    v6 is out of date so you might as well up date to 7.1 sp9 from your local Trane office they can install and register it for you.
Results 1 to 50 of 576
Page 1 of 12 1 2 3 4

Related Forums

Plumbing Talks | Contractor MagazineThe place where Electrical professionals meet.
Comfortech 365