Search:

Type: Posts; User: ascj

Page 1 of 20 1 2 3 4

Search: Search took 0.05 seconds.

  1. Replies
    0
    Views
    136

    Trane Voyager Points

    I had a Trane Voyager points list, that I can't seem to find anymore. It listed all the points and descriptions. This was Com4/MicroControl. Anyone have a copy?
  2. Thread: Summit and Win 7

    by ascj
    Replies
    3
    Views
    193

    Thanks for the reponses. This is kinda of good...

    Thanks for the reponses. This is kinda of good in a way, since they are looking into pushing the full upgrade sooner.
  3. Replies
    6
    Views
    367

    The most recent Maxline CommFour Module is...

    The most recent Maxline CommFour Module is 3.7.106.6. It came out April 5, 2014.

    If you have the Maxline CommFour Driver, then it just a simple update to the module. There are no dependencies. ...
  4. Thread: Summit and Win 7

    by ascj
    Replies
    3
    Views
    193

    Summit and Win 7

    We have a customer who lost their Summit front end hard drive. It was running Windows XP. They got a new computer with Windows 7 Pro. I installed Summit on it, with no issues.

    They called Trane...
  5. Replies
    12
    Views
    454

    Is there anyway I could get them also?

    Is there anyway I could get them also?
  6. Replies
    6
    Views
    312

    Is nvoHeatCool ever going to HVAC_HEAT...with...

    Is nvoHeatCool ever going to HVAC_HEAT...with nviApplicMode set to HVAC_HEAT? If it isn't, then I would be double checking nviPriHeatEnable(for the DAC) and nviAuxHeatEnable(for the SCC). Remember...
  7. Replies
    35
    Views
    2,477

    I would appreciate a copy. Email in...

    I would appreciate a copy. Email in profile.....thanks.
  8. Replies
    3
    Views
    328

    If you have a Bacnet license already and want to...

    If you have a Bacnet license already and want to trend in the Jace.......then you are good to go. You don't need the Tcomm driver. The Tcomm driver is required to pull trending out of the EasyIO. ...
  9. Thread: Trane UPCM to PCG

    by ascj
    Replies
    4
    Views
    237

    I normally find it easier to just go through the...

    I normally find it easier to just go through the Inputs and open them. It's quicker then going through UPCMedit.
  10. Replies
    3
    Views
    328

    Do you need schedules and histories? EasyIO's...

    Do you need schedules and histories? EasyIO's can be brought into a Jace via Bacnet MS/TP or TCP, Modbus, or Sedona. Tcom driver gives you the most flexibility. But if price is a issue and you...
  11. Replies
    6
    Views
    367

    Will agree with chadtech.........this was an...

    Will agree with chadtech.........this was an issue with their 3.7.46.4 driver and earlier.

    It has been resolved......if you need the newest driver, just let me know. Also, if your module is...
  12. Replies
    9
    Views
    558

    What was the model of RTU? What was the actual...

    What was the model of RTU? What was the actual alarm you were seeing? Is it the VFD that is locking out? Why isn't the phase monitor shutting the unit down, first?

    My experience with Carrier...
  13. Replies
    3
    Views
    239

    I trigger it by UnOccupied to Occupied. Then...

    I trigger it by UnOccupied to Occupied. Then setup a max time and a start/stop temps.

    Here is the application I use-

    499511
  14. Replies
    6
    Views
    473

    Just curious....why the 7 Jace 700's?

    Just curious....why the 7 Jace 700's?
  15. Thread: Jace CCN Inteface

    by ascj
    Replies
    15
    Views
    710

    You might want to look into bringing them in...

    You might want to look into bringing them in Bacnet with a UPC Open Controller for each. Another option is a Ivu link. You are limited to 500 Bacnet points, but with just 4 chillers.....that should...
  16. Thread: Carrier Ivu

    by ascj
    Replies
    1
    Views
    204

    Carrier Ivu

    Is there a network point limit per controller?

    I have a 6400 on a Ivu 4.2, that I'm trying to fix some points. Looking at the equipment file they are all there and mapped. I download to the Ivu...
  17. Replies
    7
    Views
    972

    You verified you only have one broadcast...

    You verified you only have one broadcast acknowledger per buss? You verified you only have one controller per schedule broadcasting? Meaning you don't have duplicate schedule numbers being...
  18. Thread: Service tool 5

    by ascj
    Replies
    7
    Views
    551

    Sent you an email.

    Sent you an email.
  19. Replies
    5
    Views
    254

    Sent you an email.

    Sent you an email.
  20. Replies
    5
    Views
    254

    It's amazing how often they update their drivers....

    It's amazing how often they update their drivers. The newest version I have is 3.7.106.2.

    I sent a email to my connection at Maxline for the newest driver and their patch notes. But since the...
  21. Replies
    5
    Views
    254

    What version driver? What kinda of devices?

    What version driver? What kinda of devices?
  22. Replies
    19
    Views
    2,778

    360 seconds is the stroke time. Be careful with...

    360 seconds is the stroke time. Be careful with retrofit controllers......those VAV's have ends switches, which can wreck some controllers with triacs. You can add some isolation relays or add some...
  23. Thread: CCN Issue

    by ascj
    Replies
    10
    Views
    323

    My bad....yes they are Gen3. I'm changing the...

    My bad....yes they are Gen3. I'm changing the BCACK point. It just doesn't recognize the buss, element when I do a scan for broadcast acknowledgers.

    Anyway, I spent some more time with the...
  24. Thread: CCN Issue

    by ascj
    Replies
    10
    Views
    323

    No....I'm changing the controller to a broadcast...

    No....I'm changing the controller to a broadcast acknowledger......but when I do a buss scan on that buss, my service tool show nothing. I'm pretty familiar with using the Carrier service tool and...
  25. Thread: CCN Issue

    by ascj
    Replies
    10
    Views
    323

    Changes and scanning are through NSTV. No Ivu...

    Changes and scanning are through NSTV. No Ivu onsite.