    It 46F at my house and my hp is putting out 101F...

    It 46F at my house and my hp is putting out 101F heat with no aux at a register ~35' from unit.
  2. Replies
    8
    Views
    2,782

    The txv on outside is the only one used for heat...

    The txv on outside is the only one used for heat mode, txv on inside is for ac mode. He may have left a freon leak when the valve was changed. If its not able to keep up at 45F outside it won't have...
  3. Replies
    8
    Views
    2,782

    Sounds like its either low on refrigerant and/or...

    Sounds like its either low on refrigerant and/or leaky ductwork. Could be other things as well, have a pro come give it a check up.
  4. Replies
    8
    Views
    2,782

    If its lower than ~90F you probably have a...

    If its lower than ~90F you probably have a problem with the unit or leaky ductwork
  5. Replies
    8
    Views
    2,782

    With no aux on it should be ~95-105F.

    With no aux on it should be ~95-105F.