    I didn't see any mention of checking voltage drop...

    I didn't see any mention of checking voltage drop on start up. The start assist can only do so much before it can't help. Try using a VOM with Min/Max recording and connect it as close to compressor...
  2. No cheap installation here. Notice the canvas...

    No cheap installation here. Notice the canvas duct connector!
  3. Replies
    18
    Views
    5,029

    Leaked slow like a leak would be if the spring...

    Leaked slow like a leak would be if the spring adjuster cap were left off. Had some from a major manufacturer that blew right through the equalizing line. I was told initially that they shouldn't do...
  4. Replies
    7
    Views
    1,005

    Even beer cans fold under the thumb when you...

    Even beer cans fold under the thumb when you hoist for a sip.
  5. Replies
    18
    Views
    1,471

    Look for missing fiber turbulators. As you look...

    Look for missing fiber turbulators. As you look at the inlet of the heat exchanger tubes, where the burners fire into, there should be fiber turbulators visible. If not, they vibrated down the tube,...
  6. Replies
    9
    Views
    4,252

    Low on charge is often overlooked as a reason for...

    Low on charge is often overlooked as a reason for freeze-up. Anytime your saturated suction pressure falls below the freezing point, (58psi for R22, 100psi for R410) there will be a freezing...
  7. Replies
    12
    Views
    1,547

    You want everyone's opinion?? Well, a somewhat...

    You want everyone's opinion?? Well, a somewhat old-timer like me, 35 years in the business is 100% sold on R410a for high temp air conditioning. Carrier got lucky on this one. They could have kept...