Search:

Type: Posts; User: Webbyz

Page 1 of 8 1 2 3 4

Search: Search took 0.01 seconds; generated 10 minute(s) ago.

  1. Replies
    6
    Views
    663

    What we have found is that if a schedule is...

    What we have found is that if a schedule is created inside a Unit Controller, the JACE will be able to import that on the MSTP link, and then you can use the Schedule Exporter and it will work.
    ...
  2. Replies
    6
    Views
    663

    Create BACNET Writeable Schedule in AX

    Hello all.

    We have a site that we are using a JACE6 to control some units at a site where we need the AX Schedules to be BACNET Writeable.

    So there will be another controller writing to the...
  3. Replies
    4
    Views
    901

    Does anyone know if there is a standard point...

    Does anyone know if there is a standard point that would be triggered to Re-Calibrate the VAV on a VAV-SD Controller?

    I know that these are freely programmable, but I didn't know if there was a...
  4. Replies
    4
    Views
    901

    Alerton VAV-SD BACNet Point Issues

    Hello all. I am working with a Tridium front end on an Alerton BACNet MS/TP link. The VAV's on the link are the VAV-SD units. I have not dealt with these before and I am having some strange issues so...
  5. Replies
    10
    Views
    1,400

    Sure do. Shoot me an email or a PM.

    Sure do. Shoot me an email or a PM.
  6. Replies
    17
    Views
    1,704

    Well the diagnostic for an "8" code is "Processor...

    Well the diagnostic for an "8" code is "Processor in reset, or no functioning software. A persistent “8” means that service is
    required." So you could have something as serious as a processor issue....
  7. Replies
    17
    Views
    1,704

    What did the LED Display do during the DIP reset?...

    What did the LED Display do during the DIP reset? Did it do any EC codes?
  8. Replies
    17
    Views
    1,704

    When you are replacing the Memory Cards, are they...

    When you are replacing the Memory Cards, are they brand new? You should be doing a DIP Switch reset and then letting the panel re-download Code/Database from the local Summit PC.
  9. Replies
    13
    Views
    3,441

    I would double check that the DIP Switches are...

    I would double check that the DIP Switches are addressed properly. It is easy to get the On and the Off confused on those.

    -P means that it is waiting for a database from the Tracer Summit...
  10. Replies
    10
    Views
    1,325

    It sounds to me like you have a varience between...

    It sounds to me like you have a varience between the setpoints in the Area Control and the setpoints in the VAV's. First off, are you using UCM I/II/III/IV VAV's or Comm5 VV550/1's? Remember that...
  11. Replies
    1
    Views
    474

    Just making sure, you have the custom graphic...

    Just making sure, you have the custom graphic going to "Universal Input[1]" as opposed to something like "Universal Input Units[1]" correct?

    I have seen things like this with UI13 on an AH540...
  12. Replies
    10
    Views
    1,325

    Well it should at least make it so it won't try...

    Well it should at least make it so it won't try to use the Termainal Reheat if your zone temp gets too low where it would normally use it so you won't be aimlessly trying to reheat a zone with the...
  13. Replies
    0
    Views
    364

    Jace IO Bus RS-485 Port Settings?

    Hello all. Hoping that someone might have some information here for me.

    I have a Security Jace that has an R2R Module attached to it, but I want to add another R2R in a remote location. So...
  14. Replies
    10
    Views
    1,325

    We have this happen occasionally as well. Here is...

    We have this happen occasionally as well. Here is basically what happens...

    When a PC connects to the site, the internal database on the BCU and the PC compare timestamps on their last database...
  15. Replies
    0
    Views
    220

    JACE BDT Table Question

    Hello all. Hopefully someone can answer this easily becuase I can't find the answer in WorkPlace Help.

    If you have a BDT table under IP Port BAC0 (47808) and another BDT table under IP Port BAC1...
  16. Replies
    13
    Views
    2,798

    I have ARCNET and Ethernet cards. Shoot me an...

    I have ARCNET and Ethernet cards. Shoot me an email and let me know what you need.
  17. Replies
    0
    Views
    509

    PoolPak ECCIII Lon Fault Codes?

    Hello all. Long time no post!

    I have a PoolPak with an ECCIII controller on it and some how we lost programming in our BCU for it. I have the .xif file but there are some points like...
  18. Replies
    8
    Views
    2,102

    I am confused. Are you asking if the Comm5 card...

    I am confused. Are you asking if the Comm5 card is compatible or the Version 5 software? The card itself is and you need Rover version 7 if you want to run on 7 pro or ultimate. It is not approved...
  19. I guess what I am curious to know is if you are...

    I guess what I am curious to know is if you are trying to use this on the LAN side of the router or if you are trying to use this on the Internet from home. BACNET does not traverse the internet very...
  20. Replies
    2
    Views
    555

    Trane ZN517 TOV on an AX Platform?

    Hello all,

    I have a ZN517 that has been integrated into a JACE. The issue that I am running into is that I need to have TOV at the stat using the On/Off buttons (Or Occ/UnOcc if you prefer).
    ...
  21. Replies
    6
    Views
    1,895

    If you want to look to see what boxes are...

    If you want to look to see what boxes are associated with an Area, go to Setup -> Area -> Select the area where the VAV boxes should be associated -> then look at the "Members" tab. Your VAV boxes...
  22. Replies
    10
    Views
    1,400

    Just throwing it out there again that I have a...

    Just throwing it out there again that I have a stock of these =)
  23. Replies
    5
    Views
    1,286

    I would suggest a DD-WRT configuration...

    I would suggest a DD-WRT configuration personally.

    It is 3rd party firmware for wireless routers where you can tweak transmit power signals.

    I would suggest something with RP-TNC or SMA...
  24. Replies
    9
    Views
    935

    This method seemed to work. It takes the...

    This method seemed to work. It takes the 12345.6789 and takes it down to 12345.6700. That works for me since I don't need to be absolute.

    Unfortunatly the methods that tShort described resulted in...
  25. Replies
    9
    Views
    935

    OK I will try to explain a little better. I...

    OK I will try to explain a little better.

    I have a Service that is figuring out CO2 Carbon Footprint and kBTU usage. In the service wire sheet, I cannot edit the format of the output.

    So lets...