  1. Replies
    6
    Views
    601

    If you have access to CCT rev. 6.0 the state...

    If you have access to CCT rev. 6.0 the state tables are live and will highlight the blocks that are driving your modes. In your screenshots HX Heat could be putting the glycol loop into T-Control,...
  2. Replies
    1
    Views
    346

    Trane's product lines

    I've got an interview coming up with Trane and I've been studying up on their control lines (past and present), but all the pieces aren't quite fitting together for me. Much of the literature on...
  3. Replies
    8
    Views
    685

    What type of controller is it (on the PMI side)?...

    What type of controller is it (on the PMI side)?
    What is the point type and address? (ie. AI 1, BO 2, ADF 131)
  4. Replies
    3
    Views
    1,148

    1) From the Start button go to the Control Panel...

    1) From the Start button go to the Control Panel for Windows.
    2) Double-click on Administrator Tools.
    3) Double-click to select Services.

    In the list of services, look for Metasys III Action...
  5. Replies
    4
    Views
    363

    Global search would work if you put the caret in...

    Global search would work if you put the caret in the name field. I use Mass Edit Live (MEL) to search and you can search the description field that way. Funny enough, we originally used * to mark the...
  6. Replies
    4
    Views
    363

    We have the same problem. What we've done is add...

    We have the same problem. What we've done is add a special character to the description field, we use the caret ^. The only other way that I know of is to get into the SQL database. We have a lot of...
  7. Replies
    3
    Views
    1,616

    From JCI Lit... For Metasys 4.1.9.0200, Java...

    From JCI Lit...

    For Metasys 4.1.9.0200, Java 1.6.0_21 is required.
    For Metasys 4.1.5 to 4.1.8, Java 1.6.0_16 is required.
    For Metasys 4.1, Java 1.6.0_07 is required.


    CAUTION: If you are...
  8. Replies
    8
    Views
    1,206

    If they already have an NAE onsite that is not...

    If they already have an NAE onsite that is not maxed out, your JACE points could be added to the existing NAE. We have a problem with JCI thinking they have you over a barrel, but there are ways...
  9. Replies
    8
    Views
    1,206

    NAE Integrations Limits

    JCI doesn't require an NAE beside every BACnet integrated device. The limitation is the number of integrated points. The soft guidelines are NCE, NAE-35, and NAE-45 2500 objects, NAE-55 5000 objects,...
  10. Replies
    4
    Views
    408

    Have you checked the JCI product website?...

    Have you checked the JCI product website? http://cgproducts.johnsoncontrols.com

    Maybe some useful documents/schematics.
  11. Replies
    5
    Views
    760

    We inherited a SoftJace from a retrofit project...

    We inherited a SoftJace from a retrofit project and I would have much prefered a QNX mounted neatly in a panel. Instead we have a PC hanging out in a mechanical room basically unprotected from the...
  12. Replies
    3
    Views
    530

    I think the reason he says it's messy is that all...

    I think the reason he says it's messy is that all the field points show up under 1 device. An NAE-55 can have 5000+ field points, combination of software points and hardware points coming from the...
  13. Replies
    12
    Views
    652

    Sorry screwed up the link: Try #2 N1 ARCNET...

    Sorry screwed up the link:

    Try #2

    N1 ARCNET Local Area Network Technical Bulletin
  14. Replies
    12
    Views
    652

    Did you check this document? ...

    Did you check this document?

    http://cgproducts.johnsoncontrols.com/MET_PDF/636017.PDF
  15. Replies
    8
    Views
    675

    There was a poblem with IOMs toggling for a quick...

    There was a poblem with IOMs toggling for a quick second, but I don't know of any other issues with N2 controllers.
  16. Replies
    8
    Views
    675

    If you haven't already, I would recommend setting...

    If you haven't already, I would recommend setting the parameter "Disable Automatic Alarming" to True. This is under the Hardware tab of the DX. We do this for all of our field controllers on campus...
  17. Replies
    1
    Views
    365

    ADX graphics can use .jpg, .svg, &, .svgz...

    ADX graphics can use .jpg, .svg, &, .svgz formats. I don't know anything about the Siemens system, but one quick and dirty way to do it would be to take a screenshot of the graphic and use that as...
  18. Replies
    10
    Views
    966

    @Ansonf UW-Madison was a pretty early adopter of...

    @Ansonf UW-Madison was a pretty early adopter of DDC, maybe it's our proximity to Milwaukee and Johnson Controls. There are a few pneumatically run units but for the most part controls are largely...
  19. Replies
    10
    Views
    966

    Most of our projects are coordinated by the...

    Most of our projects are coordinated by the State, so when I say we I mean "they with our input on how busy we are". We do a lot of projects in house, primarily retrofits of a single air handler or a...
  20. Replies
    2
    Views
    1,089

    GPL will not work as configured b/c Win 7 doesn't...

    GPL will not work as configured b/c Win 7 doesn't run a true MS-DOS. I was able to do it by loading a virtual machine of Windows 98, but that wasn't worth the mess. I think exwtk has the right idea,...
  21. Replies
    10
    Views
    966

    University/College DDC Groups

    Just looking for fellow University DDC techs to share ideas and see how other organizations are setup/staffed. I think there are some unique challenges/experiences of working for a research...
  22. Replies
    8
    Views
    1,591

    SQL

    Yes, SCT, ADS, and RAP (and CCT) will all work with a fresh installation of SQL Express 2005. (Beginning in ver. 5.0 SQL Express 2008 will be fully supported). JCI employees use MSDE b/c a utility...