  1. How do you get CO problems from a heat pump?

    How do you get CO problems from a heat pump?
  2. Replies
    19
    Views
    905

    Might work, might not. My guess is he fan will...

    Might work, might not. My guess is he fan will run but who knows how much air you'll move.

    BTW if the 2.5 you mention in the first post is in this unit, there is your problem, the 2.5 wasn't put...
  3. Replies
    19
    Views
    905

    ECM = electronically commutating motor. The end...

    ECM = electronically commutating motor. The end of the motor that holds the electronics is called to module.

    The way you are describing things is very confusing.

    Is the blower your trying to...
  4. Replies
    19
    Views
    905

    It is a proprietary motor made by Regal Beloit....

    It is a proprietary motor made by Regal Beloit. The GE name is a left over used for brand recognition.

    The 2.5 was found only in C/B equipment. You won't find a 2.5 in a Trane, 2.0 2.3 or a 3.0,...
  5. Replies
    19
    Views
    905

    The 2.5 was a proprietary motor to carrier /...

    The 2.5 was a proprietary motor to carrier / Bryant. There was a tool that could be used similar to the tech mate that is just for the 2.5. Your local C/B supplier should be able to get you one.
  6. Replies
    11
    Views
    655

    How do you know there was 38 oz of oil in the...

    How do you know there was 38 oz of oil in the compressor to start with, that number sounds like way too much, Resi compressors oil charge is usually expressed in CC's.
  7. Replies
    13
    Views
    734

    ^ ohms law stuff. I agree with the guy who...

    ^ ohms law stuff.


    I agree with the guy who pointed out the transformer issue, the system should have never run.
  8. Thread: Dual Fuel

    by Ed Janowiak
    Replies
    29
    Views
    962

    If my economic balance point is well below a temp...

    If my economic balance point is well below a temp where I'll get frost on the outdoor coil why would you want to set the heat pump to shut off if defrost cycles are required? That seems to defeat...
  9. Replies
    32
    Views
    1,636

    Target SH = [(3 x indoor wb) - 80 - ambient] / 2...

    Target SH = [(3 x indoor wb) - 80 - ambient] / 2 (F)
  10. Replies
    26
    Views
    1,628

    Then what is your next move? 17 degree split...

    Then what is your next move?

    17 degree split low load low SH the unit is low on capacity, dry bulb split should be way higher. If there is a hint of low airflow problem the split should have been...
  11. Replies
    26
    Views
    1,628

    Or do CFM x TD x .317 = watts output Divide...

    Or do
    CFM x TD x .317 = watts output

    Divide by watts input to calculate COP 😁
  12. Replies
    26
    Views
    1,628

    BTUH/ (TD x 1,08 ) = CFM Amps x volts x 3.412=...

    BTUH/ (TD x 1,08 ) = CFM
    Amps x volts x 3.412= BTUH

    The 1.08 and 3.412 cancel out to 3.16
  13. Replies
    26
    Views
    1,628

    if you question the airflow why not just measure...

    if you question the airflow why not just measure it?

    Run elec strips at same fan speed as comp runs -
    amps x volts / TD x 3.16 = CFM

    Quantify and stop guessing :cheers:
  14. Why would you need to know what direction the...

    Why would you need to know what direction the room faces? The largest heat loss would happen in the dark wouldn't it?
  15. Thread: EPA cert

    by Ed Janowiak
    Replies
    4
    Views
    429

    www.eh-cc.org Too bad I didn't see this till...

    www.eh-cc.org

    Too bad I didn't see this till now, I'm doing a 608 review and test tomorrow in Pleasantville. If all you want to do is test, call the office and you can test on line at your...
  16. Replies
    53
    Views
    5,055

    I think you'll miss the snow :putergreet:

    I think you'll miss the snow :putergreet:
  17. Replies
    22
    Views
    1,597

    I believe the 80 / 20 mix with the oil will...

    I believe the 80 / 20 mix with the oil will result in zero problems. Flushing to get rid of contaminants is good, flushing to rid the piping of oil is a scam. I like 407C more and more every day.
    ...
  18. Replies
    15
    Views
    942

    A "tight" shaft on a motor with permanent magnets...

    A "tight" shaft on a motor with permanent magnets is normal. Ohm the motor out like any 3 phase motor to see if it's good. A spin test on the shaft with a comparison to a PSC motor is not a a good...
  19. Replies
    13
    Views
    1,005

    Cool, that's why I asked :-). Gunslinger, yes...

    Cool, that's why I asked :-).

    Gunslinger, yes the new version will be out soon.
  20. Replies
    13
    Views
    1,005

    Can you clarify what you mean there? Manual S...

    Can you clarify what you mean there?

    Manual S is not a guess at anything, it's a procedure to select equipment and recommend airflow based on the SHR and BTUH loss provided by Manual J.
  21. Replies
    3
    Views
    504

    thanks for the help fellas, i looked for a while...

    thanks for the help fellas, i looked for a while and came up blank on both glad i asked.
  22. Replies
    3
    Views
    504

    AHRI cert #

    I'm having a difficult time finding AHRI reference numbers for these combo's, can anyone lend a hand please.

    Goodman:
    OUTDOOR model SXC180361AC

    INDOOR ARUF36C14BB

    Goodman:
    OUTDOOR...
  23. Replies
    10
    Views
    937

    So you want split hairs about this but ball...

    So you want split hairs about this but ball parking the actual selection is ok, I'm sorry I said I was done before but this was too good not to mention, have a good night.
  24. Replies
    10
    Views
    937

    You added this after my last reply. Highly...

    You added this after my last reply.

    Highly technical ? I call that doing it correct and not ball parking, LOL, you win I'm done.
  25. Replies
    10
    Views
    937

    Fan speed affecting SHR is covered in Manaul S,...

    Fan speed affecting SHR is covered in Manaul S, what you are leaving out is the total capacity will start to drop as latent work disappears. If you can produce application data with the high airlfows...
  26. Replies
    10
    Views
    937

    Show me application data for a 2 ton split unit...

    Show me application data for a 2 ton split unit running 600 CFM per ton. I've never seen a resi split over 500 per ton. If this info doesn't exist what might happen theoretically is moot.

    I have...
  27. Replies
    10
    Views
    937

    If you install a 2 ton system on a 22k gain with...

    If you install a 2 ton system on a 22k gain with a SHR of .98 you just installed a unit that does not have enough capacity to meet the gain.

    SHR is sencible gain divided by total gain. With this...
  28. Replies
    16
    Views
    1,191

    Sure about that? ...

    Sure about that?

    http://i591.photobucket.com/albums/ss352/EdJanowiak/null_zps4d3970c5.jpg
  29. Replies
    16
    Views
    1,191

    Close all the windows in the house, close all the...

    Close all the windows in the house, close all the doors and turn on all the fans in the house (furnace / air handler/ kitchen / fart etc) and see if the water heater is still drafting, my guess is...
  30. Yes, yes it is. St Louis was the best standard...

    Yes, yes it is. St Louis was the best standard air discussion I witnessed.


    Didn't know I could subscribe without making a post.
  31. I'm not permitted to comment in this forum, but...

    I'm not permitted to comment in this forum, but I'm doing so to get emails when this thread updates. I've seen some really fun discussions on this topic in person from some of the participants, and...
  32. When you say "maxes out" do you mean the units...

    When you say "maxes out" do you mean the units stops cycling and the temp starts to rise in the space?

    If so, you have never seen a system installed after an accurate load calc was performed. It's...
  33. Replies
    7
    Views
    1,022

    Wright J moble does block load calcs, you need...

    Wright J moble does block load calcs, you need room by room to do a duct layout.

    I see the value and time savings in a computer based load calc but just don't see it in the duct design. I see so...
  34. Is it a good way to do a calc? Ballpark yes truly...

    Is it a good way to do a calc? Ballpark yes truly accurate? No.

    In the world of good better best, it's good (it's a dumbed down version of 7). The abridged version of 8 is better and best would be...
  35. Replies
    5
    Views
    1,158

    The disks are done by Jack Rise, they are very...

    The disks are done by Jack Rise, they are very good at explaining step by step how to fill out the friction rate worksheet and how to select the proper size ducts as per Manual D.
    The first RSES...
  36. Replies
    14
    Views
    1,596

    Manual J gives you your sensible & latent gains,...

    Manual J gives you your sensible & latent gains, Manual S explains how to manipulate your SHR's with different air flows by looking at the application data, very logical and actualy simple once you...
  37. Replies
    14
    Views
    1,596

    Your total gain is the sensible gain plus the...

    Your total gain is the sensible gain plus the latent gain. If you divide the total gain into the sensible gain it will give the SHR of the space (sensible to latent ratio).

    A "perfect" match is a...
  38. Replies
    14
    Views
    1,596

    Total capacity will be higher with a higher...

    Total capacity will be higher with a higher sensible heat ratio. Higher air flow will give you a higher SHR, lower airflow produces a lower SHR. You should match the SHR of your equipment to the SHR...
  39. Replies
    10
    Views
    1,120

    In heating (heat pump only): CFM x TD x .317 =...

    In heating (heat pump only):

    CFM x TD x .317 = Watts output

    Watts output x 3.412 = BTUH

    This thread shows how to do the AC EER calculation.
    ...
  40. Replies
    8
    Views
    1,016

    You just described the difference between zeroing...

    You just described the difference between zeroing a gauge and calibrating a gauge, nice job. :det:
  41. Replies
    9
    Views
    2,466

    If you understand how to fill out the friction...

    If you understand how to fill out the friction rate worksheet all the effective length charts as well as the excel version of the friction rate worksheet can be downloaded free on the ACCA website....
  42. Replies
    48
    Views
    2,993

    Line of sight is my answer for the TD question...

    Line of sight is my answer for the TD question (avoid it). A way to convince yourself is to simply take the temperatures in multiple locations and draw your own conclusion.

    Amp draw question. ...
  43. Replies
    15
    Views
    1,812

    Klenks are the best snips of any I have ever used.

    Klenks are the best snips of any I have ever used.
  44. Replies
    3
    Views
    795

    If an x-13 receives a signal from more than 1...

    If an x-13 receives a signal from more than 1 tap, it runs at the higher speed. If it receives a signal on all taps it runs at the highest speed. It is designed to receive multiple signals and know...
  45. Replies
    3
    Views
    294

    It's in the install instructions. But off the...

    It's in the install instructions.

    But off the top of my head, you have to set the gas pressure in low fire (you find low fire scrolling through the set up on the personalty mod) I wana say at...
  46. Thread: EPA test

    by Ed Janowiak
    Replies
    3
    Views
    408

    http://www.escoinst.com/ They have practice...

    http://www.escoinst.com/

    They have practice exams.
  47. Replies
    33
    Views
    1,903

    The motors are programmed to mantain a constant...

    The motors are programmed to mantain a constant RPM / torque value which is going to fluxuate depending on SP. the higher the SP the more torque and higher RPM will be required to mantian CFM. The...
  48. Replies
    19
    Views
    3,556

    No, the product you describe dos not exist. ...

    No, the product you describe dos not exist.

    All caps = shouting, shouting will not get you more responses, it will have the opposite effect.
  49. Replies
    19
    Views
    3,556

    Why dont you want round?

    Why dont you want round?
  50. I have a very throrough understanding of the...

    I have a very throrough understanding of the topic, but I find your persistence to try to prove things that I have many years of experience with to be wrong with BS analogies to be very entertaining...