  1. Replies
    5
    Views
    736

    Why not spec an HMI from GE, AB or Wonderware for...

    Why not spec an HMI from GE, AB or Wonderware for this volume of IO/points, most of which talk natively with AB? What was the reasoning for selecting Tridium, sounds intriguing??
  2. Replies
    2
    Views
    736

    Siemens TEC remote programming

    Is it possible to program BACnet TEC Siemens controllers from the MSTP network trunk via WCIS?

    That would be instead of accessing thru the local MMI with a cable on the individual TECs.
  3. Replies
    11
    Views
    701

    I like alarms, histories and other extensions on...

    I like alarms, histories and other extensions on the JACE. Let the alarm station to station connection do all the work. If you zap or redo the supervisor folders for redesign, tweaking or some other...
  4. Replies
    4
    Views
    701

    if u have an Android phone download "Scaler"...

    if u have an Android phone download "Scaler" program, saves some time!
  5. Replies
    6
    Views
    906

    crazy week. i'll try to get step-by-step off...

    crazy week. i'll try to get step-by-step off tomorrow to you
  6. Replies
    6
    Views
    906

    I think i used embedded px file (pxInclude i...

    I think i used embedded px file (pxInclude i think it's called) in a parent px file with variables. That way the trends, if named properly, can be dynamically referenced using the VAV name etc to...
  7. Replies
    7
    Views
    1,602

    You could just replace the UNC with a JACE-6 but...

    You could just replace the UNC with a JACE-6 but would still need the programming software for the field devices. If you have that then you could reverse engineer the SOO for the equipment. Still a...
  8. Replies
    1
    Views
    1,138

    The points should be autodiscovered in the NV/NC...

    The points should be autodiscovered in the NV/NC manager when controller is discovered/added, you don't need xif file...
  9. Replies
    16
    Views
    1,659

    Sorry didn't get the driveware open today but the...

    Sorry didn't get the driveware open today but the working USB adaptor is an IO gear
  10. Replies
    16
    Views
    1,659

    i can look it up tomorrow - it does depend on the...

    i can look it up tomorrow - it does depend on the USB model (i.e. Hit&Miss) but the trick was to not choose AutoConfig under the custom COM settings but choose the User-defined type or custom for the...
  11. Thread: TAC I/A series

    by roverXE
    Replies
    11
    Views
    1,352

    Yep, that should be a UNC which is the...

    Yep,

    that should be a UNC which is the Invensys JACE, it probably has MNL Lonworks controllers wired to it..
  12. Thread: TAC I/A series

    by roverXE
    Replies
    11
    Views
    1,352

    If it's MNL then it's LON (MicroNet Lon) and...

    If it's MNL then it's LON (MicroNet Lon) and programmable by Workplace Tech, a Visio Addon only available to suppliers and end users in my experience
  13. Replies
    16
    Views
    1,989

    fought this for a while, please forward what you...

    fought this for a while, please forward what you have for compare thanks
  14. Replies
    10
    Views
    4,083

    First find out if you have .DMO files (DX...

    First find out if you have .DMO files (DX controller file) which contain the user tag names. If you don't then you can reverse engineer them from the ddl and model files in PMI, assuming you can get...
  15. Thread: tridium dilema

    by roverXE
    Replies
    5
    Views
    873

    Free/Available memory will ramp down over a...

    Free/Available memory will ramp down over a period of 1-2 months almost linearly and always repeats, i have them all trended! When memory is almost gone the box reboots and downward trend starts anew.
  16. Thread: tridium dilema

    by roverXE
    Replies
    5
    Views
    873

    FWIW, I have had memory leak problems on 403...

    FWIW, I have had memory leak problems on 403 series since install and will eventually/soon install only JACE-6's. I have some of the 6 series installed in parallel and no probs of this type yet.
  17. Replies
    9
    Views
    1,141

    Would be nice if the upgrade prompted as "version...

    Would be nice if the upgrade prompted as "version upgrade not supported" seems like a pretty easy software check if it makes bricks? seems a bit sloppy to me
  18. Replies
    11
    Views
    1,261

    Niagara AX runs as a service and will accept IO...

    Niagara AX runs as a service and will accept IO with exp cards or you can get the JCI driver with the FX brand. Maybe IT can help fund the upgrade
  19. Replies
    10
    Views
    788

    Maybe the Lost finale will help you find these...

    Maybe the Lost finale will help you find these answers
  20. Replies
    11
    Views
    2,657

    We usually use PREHEAT, REHEAT, COOLING COIL,...

    We usually use PREHEAT, REHEAT, COOLING COIL, (DE)HUMIDIFICATION TEMPS etc if there are multiple temps on a unit. If there is only one temp we call SUPPLY TEMP (or discharge temp, user preference)
  21. Replies
    9
    Views
    695

    Did you weed down the PRN file generated for the...

    Did you weed down the PRN file generated for the VMA thru HVAC Pro and use it as the resouce file input for the tags when discovering the device?

    Don't know and can't assume since you didn't...
  22. Replies
    3
    Views
    1,128

    make sure you're relative to a component folder...

    make sure you're relative to a component folder which contains the points and not opening the px directly from the file directory
  23. Replies
    2
    Views
    493

    Just create point folders on the server for...

    Just create point folders on the server for anything you need rom the field controllers. Once inside the point folder do a discover and, if easier, do a custom query using SLOT_PATH = 'matching...
  24. Replies
    22
    Views
    3,567

    mine never showed up in my email yet - can you...

    mine never showed up in my email yet - can you try a reforward? Still haven't needed it but a little advance reading will surely help.
  25. Replies
    8
    Views
    1,333

    I agree on the hardwire philosophy, we have...

    I agree on the hardwire philosophy, we have hundreds of drives on site and we always hardwire the speed, hoa sts, s/s and current/status. We also use some industrial buses for the fluff with PLC/HMI...
  26. Replies
    8
    Views
    1,333

    Thanks guys, I have the FX so good there - Used...

    Thanks guys, I have the FX so good there - Used it for some other stuff and had a project coming up for the drives. It's got other N2 devices on the same chain so I'm stuck with N2 comms w/o some...
  27. Replies
    8
    Views
    1,333

    ABB AFD ACHxxx - JCI N2 to JACE Ax

    Can anyone give a short description on how to map a ABB VFD on N2 comm bus into a JACE Ax? Any experience or pitfalls with doing this?

    A point list screenshot with data addresses from the...
  28. thx, i did like you mentioned, created...

    thx,

    i did like you mentioned, created separate screens (with a chartpane at the root - fullscreen) for some PV/SP/CO trends and added several of these to a px screen using pxinclude.

    Then I...
  29. Relativizing Histories for px viewing AX 3.3.x

    What's the best practice for doing what's listed in the title?

    I've got as an example 20 duplicate AHUs on 4 JACEs.

    Each has histories configured on the JACE for SAT, Static etc etc for each...
  30. Replies
    22
    Views
    3,567

    Can you ship me the manual too? - thx have a job...

    Can you ship me the manual too? - thx have a job coming up and i'll need to get in the TRANE panel.
  31. Replies
    19
    Views
    1,830

    i'll take a forward too! thx e-mail in profile

    i'll take a forward too! thx e-mail in profile
  32. Replies
    15
    Views
    2,733

    http://www.tac.com/data/internal/data/05/63/117770...

    http://www.tac.com/data/internal/data/05/63/1177701732429/F_25833_4.pdf

    maybe that'll help -- sorry don't have these types although the form factor is the same
  33. Replies
    15
    Views
    2,733

    Workplace Tech and a Lonworks card if they're MNL...

    Workplace Tech and a Lonworks card if they're MNL VAVs and you want to directly connect - requires Visio for WPT - latest i have is 5.6
  34. Replies
    8
    Views
    2,381

    I use a couple core 2 duo machines. Each machine...

    I use a couple core 2 duo machines. Each machine has long lags on start-up/splash screen and the first time property or config sheets are opened for the function blocks.

    WPT does this everytime....
  35. Replies
    8
    Views
    2,381

    I know WPT was not dual-core friendly on the old...

    I know WPT was not dual-core friendly on the old P4s. Also there are some important security settings for the Visio plugin functionality but that was usually either works or doesn't work vs....
  36. Thread: metasys

    by roverXE
    Replies
    5
    Views
    753

    Usually you'd reset (or change) your supply air...

    Usually you'd reset (or change) your supply air setpoint. If the cooling valve or DX unit is controlling space temp directly then when the return air temp you need to lower the space temp controller...