Search:

Type: Posts; User: DCVoltZ

Search: Search took 0.00 seconds.

  1. Replies
    58
    Views
    6,186

    Sam Thank you for your comments and I am not...

    Sam Thank you for your comments and I am not aggravated not at all. But I think you miss my point..:censored:. my point is this "why the gateway at all!!!" :payattention: In this case we are talking...
  2. Replies
    58
    Views
    6,186

    After my last post I tried to maintain a positive...

    After my last post I tried to maintain a positive attitude towards the JCI / York but I have to say that even after having job visits from a local Rep from York/JCI and Fieldserver the gateways still...
  3. Replies
    58
    Views
    6,186

    The total product description is as follows...

    The total product description is as follows
    ProtoCessor FFP485 Camry
    Firmware V2.01k
    application software verison V6.06h (A)
    protocol version 1
    protocol revision 4


    You are very correct in...
  4. Replies
    58
    Views
    6,186

    The End to the Rage

    After all of the negative reports that I have made on here concerning my problems with the S-Linc Modbus to MSTP Gateway I want to also report the Positive! We had a FieldServer and a JCI Rep come to...
  5. Replies
    58
    Views
    6,186

    Status update

    I received a phone call from JCI control department telling me that they want to visit to my site. They asked about local airport and hotel accommodations. They stated that they want to fix this...
  6. Replies
    58
    Views
    6,186

    I have no idea but one thing is for sure, pure...

    I have no idea but one thing is for sure, pure diligence and not allowing them to get away with it, is the only thing they respond to. The more you allow them to slide the the less they will do to...
  7. Replies
    58
    Views
    6,186

    The Result of Raging intelligently against the Machine

    I finally got a response from my manufacture and their answer to my issue. I will let everyone be the judge of the outcome.

    To fill everyone in I received new Gateways in the mail with no...
  8. Replies
    58
    Views
    6,186

    In my case I listed all issues tested and...

    In my case I listed all issues tested and prepared a detailed itemized list of problems. We did our part from testing with an oscilloscope to trying everything I could think of doing. My correct...
  9. Replies
    58
    Views
    6,186

    As for me like I stated in the beginning If it...

    As for me like I stated in the beginning If it was not for my customer I would have already done the modbus but my customer is wanting what he spec'ed so here we go! I do not know how it got to be...
  10. Replies
    58
    Views
    6,186

    IMOHO They may or may not have even known of the...

    IMOHO They may or may not have even known of the issues at hand. I been in this trade for over 20years and been working in and on computers for even longer. The Idea of Alpha, Beta, Gama testing has...
  11. Replies
    58
    Views
    6,186

    Not trying to judge. but it does not look good...

    Not trying to judge. but it does not look good
    At this point I am leaving the situation back in the hands of York/JCI

    I have talked to many different people and I guess Fieldserver will build on...
  12. Replies
    58
    Views
    6,186

    :oops:It is in essence a ProtoCessor FFP485 Camry...

    :oops:It is in essence a ProtoCessor FFP485 Camry and its made by FieldServer Technologies for York/JCI

    http://www.fieldserver.com/docs/pdf/FST_DFS_Bacnet_PIC_BTL_Approved.pdf
  13. Replies
    58
    Views
    6,186

    The reason I did not list company's, or name...

    The reason I did not list company's, or name brands on this post
    I have not done many posts on here and was a little concerned for the reputation of this forum. My mouth has gotten me into many...
  14. Replies
    58
    Views
    6,186

    I too have seen poor Lon gateways but they are...

    I too have seen poor Lon gateways but they are more uncommon than the RS485. Mainly because of the many different configurations and types of services provided ie. COV, Confirmed COV. Write on ...
  15. Replies
    58
    Views
    6,186

    The Rage (because) of the (Gateway) Machine

    I have a soap box to climb on and something to say if it is deemed inappropriate I will submit myself for disciplinary action... but someone needs to say it and it might as well be me!

    This letter...
  16. I have gotten notified by JCI telling me that...

    I have gotten notified by JCI telling me that they do have a hardware issue with the ProtoCessor they found it on the ones I shipped back to them.

    You going to press them to get a resolution....
  17. What Fieldserver told me

    I did a FST Diagnostic capture under the requests from Field server this is what they told me after they got my Diagnostic logs

    "I can see that the Bacnet client is requesting properties that do...
  18. Looking for a plain simple answer?

    New update this morning. I upgraded my site to 3.5.39 Sorry to say the Points are in the poll list but still are not updating.. I can still update the points just by looking at them in the virtual...
  19. [QUOTE=DCVoltZ;13214371]I did get the points to...

    [QUOTE=DCVoltZ;13214371]I did get the points to refresh but had to do many different steps which may or may not be the total fix to the issue. :gah:

    Well I did not have to wait long for the...
  20. The Fix is in? or is it?

    I did get the points to refresh but had to do many different steps which may or may not be the total fix to the issue. :gah:

    1. Slowed down the MS/TP baud rate from 38.8k to 19.2k
    2. Deleted and...
  21. @ kontrolphreak Most Gateways in my experience...

    @ kontrolphreak Most Gateways in my experience are very weak. In this case either their MSTP Transceiver supports COV or they do not.. According to their Bibbs and pics statements and to quote their...
  22. @ Berg2666 COV only makes it much worse was told...

    @ Berg2666 COV only makes it much worse was told by JCI and Fieldserver NO, NO, NO
  23. weather service is unrelaiable due to local...

    weather service is unrelaiable due to local network so no I do not use the weather service
  24. MSTP to Modbus (Simplicity Linc/Fieldserver) connect to (Niagara Ax)

    Running AX 3.5.34 Jace 6. Only two JCI rooftops isolated on their own separate MSTP port @38.4k all wiring practices observed. We did our homework and setup the port as instructed by JCI with no COV....
  25. Replies
    22
    Views
    1,865

    I found how to do this and thanks for the reply....

    I found how to do this and thanks for the reply. I am still having issues. Distech posts the normal check your services and License SOP. It seems to me that if you use a binary point on their image...
  26. Replies
    22
    Views
    1,865

    I am having the same issues. maybe a ignorant...

    I am having the same issues. maybe a ignorant question but... I am trying to figure out how to switch to wb px view and back again. :anyone: Can anyone explain?
  27. I do not know about the 5 ton but the 20 ton RTU...

    I do not know about the 5 ton but the 20 ton RTU has the VFD in the condensing side of the fan section with no I repeat no enclosure on the ABB drive
  28. Replies
    0
    Views
    555

    Old Honeywell Part TIM P/N 50000083-001

    I have need of hooking up T7350H T stats to a PC for configuration and was told that there once was a cable (noted in title) that was used in conjunction with a null modem cable to access...
  29. Replies
    1
    Views
    412

    T7300 with Q7300 Subase and Niagara

    I have a T7300 with a Q7300 subbase attached to a Jace.. This stat has a remote sensor attached and ever since it has been attached to the Jace it shows a room temp of 32 deg F. I have been looking...
  30. Thread: Lon Errors

    by DCVoltZ
    Replies
    9
    Views
    2,642

    The only file I deleted was the LDRF.cat file as...

    The only file I deleted was the LDRF.cat file as was told me I then added the directorys under the user directory as suggested.... What other files should I have deleted?
    As for contacting Echelon I...
  31. Thread: Lon Errors

    by DCVoltZ
    Replies
    9
    Views
    2,642

    Still get the error

    First I want to thank all you guys for the suggestions and advice this site is really first rate... But I have done all that has been suggested but the error message still happens three different...
  32. Thread: Lon Errors

    by DCVoltZ
    Replies
    9
    Views
    2,642

    I am a integrator so I deal with many different...

    I am a integrator so I deal with many different systems but of the many here are a few Distech, Honeywell (I had problems with their T7350 plugin), Trane. These are what I have been working on as of...
  33. Thread: Lon Errors

    by DCVoltZ
    Replies
    9
    Views
    2,642

    Lon Errors

    I have Lonmaker 3.1 nonturbo with all of the upgrades/updates. When I open any network database off or online I get a error stating
    "Opening the ECHLON Lonmark Device Resource Files.
    File Not...
  34. Replies
    4
    Views
    1,371

    I finaly figured it out your line of code...

    I finaly figured it out your line of code
    getMonth().setValue(babstime.getMonth().getMonthOf Year());
    has a typo it should be
    getMonthOfYear

    no space between Of and Year
    when I edited it and...
  35. Replies
    4
    Views
    1,371

    Pardon my Nube ignorance

    I just Graduated from NU so pardon my ignorance :o
    I did just as you asked and I can connect the new object in the wire view to the nvi's but how does the new object get the time date to xfer
  36. Replies
    4
    Views
    1,371

    T7350H and Tridium Jace

    I have got a job with 15 T7350ís and I am trying to send a time stamp to them but the snvt that Honeywell uses (nvitimeset not nvitimestamp) does not conform to the normal Lontime applet in the...