Search:

Type: Posts; User: 19 D Guy

Page 1 of 2 1 2

Search: Search took 0.00 seconds.

  1. Replies
    2
    Views
    824

    Thank You-

    Thank You-
  2. Replies
    2
    Views
    824

    Nortech Industries

    One of my guys is looking for a water filter for a computer room unit. The Model is DAAD3034 and the SERIAL is 2002-1640A. The only name given to me by our "service coordinator" is Nortech...
  3. Replies
    21
    Views
    1,843

    The orifice on this machine has never been...

    The orifice on this machine has never been drilled out.
  4. Replies
    21
    Views
    1,843

    I heard from a pretty reliable source that the...

    I heard from a pretty reliable source that the oil pump fixed it. Freonpusher-How would trash get beyond the oil filter to stop up the orifce?:confused:
  5. Replies
    21
    Views
    1,843

    It fixed it just fine. Machine was brought online...

    It fixed it just fine. Machine was brought online Friday before last.:D:D
  6. Replies
    21
    Views
    1,843

    Did you check to make sure that the correct...

    Did you check to make sure that the correct fitting was in the top of the motor on the back side? It has a restrction in it. This will also cause what you are having. Something that you will also...
  7. Replies
    21
    Views
    1,843

    Replace motor and oil pump. Bet you have a bad...

    Replace motor and oil pump. Bet you have a bad motor, with high ampdraw. Replace pump to since you have it out. I had an apprentice have the same exact problem on a similar machine.
  8. Replies
    117
    Views
    12,076

    In Houston one of the factory stores did it not...

    In Houston one of the factory stores did it not to long ago and they lost one of there best guys, that was not the only reason but the final one. He wasn't screwing off to much and he got all of his...
  9. Replies
    21
    Views
    18,793

    You might try 18886832665.... I tried the number...

    You might try 18886832665.... I tried the number they gave us in Lacrosse from a couple of years ago, it has now been changed to a dial-a-good-time. I new they were always gonna screw us, just didn't...
  10. Replies
    39
    Views
    4,292

    In our office we have 4 full time, including...

    In our office we have 4 full time, including myself and 3 that can. We all range from 29 being the youngest, 31,32,36(me),40,60, and 61. We have a few young guys that talk the talk but aren't willing...
  11. Replies
    10
    Views
    1,536

    Hey Stickerhead- I was supposed to call you...

    Hey Stickerhead- I was supposed to call you today. I will get in touch w/ you tomorrow. Yes, it was from SF. Believe it or not though they stepped up and are going to "help out". New motor, parts,...
  12. Most union shops around Houston pay about $3-4...

    Most union shops around Houston pay about $3-4 above scale. 1 union shop (a factory) here pays about $8.00 over scale to there highest guys. Some other union shops can pay pretty high depending on...
  13. Replies
    10
    Views
    1,536

    Hunton sales was surprisingly helpful, even...

    Hunton sales was surprisingly helpful, even though they are supplying ALL PARTS. When I say all, I mean ALL. My new motor will be here in 10 days. We have a great salesman over there who really steps...
  14. Replies
    10
    Views
    1,536

    We give up!

    Well- I have conceeded, called Hunton Trane and told them we need a new motor, or at least have this one sent out and rebuilt.I tried to download pics but I guess they are to big. I will try and...
  15. Replies
    10
    Views
    1,536

    CVHE Tail Bearing

    We have a 1000 Ton CVHF that has lost the tail bearing on it. Motor only six months old, but factory only supplies "replacement parts". Our real problem is that it seems that the bearing race has...
  16. Thread: CVHE Starter

    by 19 D Guy
    Replies
    8
    Views
    1,612

    Thanks guys- I am scheduled over there tomorrow...

    Thanks guys- I am scheduled over there tomorrow and will get back tomorrow night if this works.
  17. Thread: CVHE Starter

    by 19 D Guy
    Replies
    8
    Views
    1,612

    I appreciate everyones input. There have not been...

    I appreciate everyones input. There have not been any VFD's or wiring changes made, we have kept the starter panels closed and the starter cabinet clean, on the molex wiring, this just started...
  18. Thread: Pump seals

    by 19 D Guy
    Replies
    9
    Views
    1,669

    I did not see where you were from but, there is a...

    I did not see where you were from but, there is a company in Houston called EEMC, these guys are great, have always been very helpful. There number is 713-460-3600, ask for Dennis or James.
  19. Thread: CVHE Starter

    by 19 D Guy
    Replies
    8
    Views
    1,612

    CVHE Starter

    I have a Trane solid state starter on a CVHE that is about 3-4 years old. The problem is that when the machine comes online it runs fine for about 5-7 minutes and then shuts down on starter fault....
  20. Replies
    5
    Views
    1,548

    The xl and xr's from what I have seen are like...

    The xl and xr's from what I have seen are like the old d machines except w/out a tail bearing. Well the xl's, I have not been through a xr yet.
  21. Thread: 19xr chiller

    by 19 D Guy
    Replies
    2
    Views
    712

    Could possibly be due to power surge. I had the...

    Could possibly be due to power surge. I had the same issue on an xr also, found out that problem was from when the afterhours engineer tested there generator monthly. Mine was a wye delta starter.
  22. Replies
    2
    Views
    883

    Refrigerant Flush

    I am looking for a company to flush out a centrifigal chiller thats system was saturated with aluminum shavings and such from impellar and bearings. Previous contractor put in compressor assembly on...
  23. Thread: Entech

    by 19 D Guy
    Replies
    11
    Views
    2,334

    I have been to several of there classes. They put...

    I have been to several of there classes. They put on good schools. They seem to give you more since they are not a factory, extra little tips stuff like that. I would highly recommend there classes,...
  24. Replies
    15
    Views
    2,898

    Call your local Carrier office, give them...

    Call your local Carrier office, give them model#,serial#, and if still on chiller somewhere the job order name and number. Your local Carrier startup department should be able to get you a copy of...
  25. Thread: Carrier XRV

    by 19 D Guy
    Replies
    8
    Views
    1,309

    Carrier XRV

    I thought I had seen on here some info or a thread to a sight for troubleshooting the Reliance drives in a Carrier XRV chiller. Carrier does not officially have a troubleshooting guide per say....
  26. Replies
    5
    Views
    1,195

    Yes this is the same one. I got back my report...

    Yes this is the same one. I got back my report from the factory with pics of the cracked seperator. The second ran fine and then we got a call that it was going to fla shortly after start up then...
  27. Replies
    5
    Views
    1,195

    Anyone having Trane Screw problems?

    Is anyone having problems with Trane screw rebuilds from Charlotte? I am replacing my 3rd this summer. All on the same machine, 1st replaced due to bad oil seperator, 2nd, don't know yet. We are...
  28. Replies
    20
    Views
    2,647

    I deal with a lot of Carriers and have friends...

    I deal with a lot of Carriers and have friends that work @ Carrier in Houston and have only heard of 1 with a leak on condenser. The leak came from a nut found vibrating against the condenser wall.
  29. Replies
    19
    Views
    1,840

    Hey guys, thanks for the input. My customer...

    Hey guys, thanks for the input. My customer cannot believe these posts. I don't know if he was so mad that he owes me lunch or the fact that he was wrong. Oh yeah BergerMech-Dude you are so wrong....
  30. Replies
    19
    Views
    1,840

    no, not trying to imply anything, but this just...

    no, not trying to imply anything, but this just goes along with a conversation that I was having with a customer and it resulted in this post. We laid down a few requirements of what a top mechanic...
  31. Replies
    19
    Views
    1,840

    Top Techs across the country...

    Ok- Top techs across the country, how much are yall making? Just curious what the scale across the country is for a truly top mechanic. No less than 15 years and true chiller, water and air cooled...
  32. Replies
    19
    Views
    2,198

    The part about you thinking Carrier machines suck...

    The part about you thinking Carrier machines suck was pretty amazing seeing how you work for York. I guess that since Mcquay has a nice controller that makes up for there equiptment being trash. And...
  33. Replies
    19
    Views
    2,198

    York, Carrier, then Mcquay, absbrtek, are you on...

    York, Carrier, then Mcquay, absbrtek, are you on CRACK? I would never even tell anyone that Mcquack still makes a chiller. As far as York before Carrier, them guys from the chiller group have you...
  34. Replies
    16
    Views
    2,543

    Just finished up on a job yesterday on a RTHB...

    Just finished up on a job yesterday on a RTHB with the same problem. The slide valve shaft rides in a groove and has a little notch on the end of it. If you open up the compressor measure amount of...
  35. Replies
    5
    Views
    816

    Had same problem last year on a RTAA as well....

    Had same problem last year on a RTAA as well. Only one right way to fix it, especially if you are the one reponsible for the machine. If you can't financially then turn the compressor off. When the...
  36. Replies
    9
    Views
    1,187

    Absorbertek- I believe that Entech in Dallas does.

    Absorbertek- I believe that Entech in Dallas does.
  37. Got a invoice from them last week. Dated...

    Got a invoice from them last week. Dated September of '05. The Houston office is about the best office as far as in stock parts. There paper trail sucks. Also, had a warranty call out for them last...
  38. Thread: CVHF Trips

    by 19 D Guy
    Replies
    11
    Views
    983

    Don't know if this has anything to do with it or...

    Don't know if this has anything to do with it or not. I am finishing up a teardown on a CVHF 910, it had several trips at main breaker. The last time I went in had shut down on a diagnostic, found...
  39. Replies
    32
    Views
    2,626

    The reason that they don't is that it is over...

    The reason that they don't is that it is over $25,000 generally when a piece of equiptment like this one is to be replaced. This being a facility that all projects over $25,000 has to be bid out he...
  40. Replies
    32
    Views
    2,626

    On the thought that they are getting a better...

    On the thought that they are getting a better price, I would not be so sure. I have a customer that just bought a 200 ton machine, bought straight from the manufacturer. I priced the same machine...
  41. Replies
    13
    Views
    6,337

    If you need any more of a password to reset any...

    If you need any more of a password to reset any further info. you half to call your York service office. They have a computer program that creates a password for that day for you to use. The password...
  42. Replies
    32
    Views
    2,626

    ga1279- Yeah I have a friend from Dallas and they...

    ga1279- Yeah I have a friend from Dallas and they have rebuilt a lot of them, well 12 or 14, they have not had any problems with them after they have rebuilt them either. There are some good...
  43. Replies
    13
    Views
    1,688

    From Japan, I heard that absorbers are really big...

    From Japan, I heard that absorbers are really big over there. I would personally follow the advice you got on the xrv's. They are the best most reliable on the market I think. We have put alot of...
  44. Replies
    32
    Views
    2,626

    I am from Houston, where the Trane here is not a...

    I am from Houston, where the Trane here is not a factory owned store. We usually can't get much help from local but we do from Pueblo, N.C., or Lacrosse. If you are a tech and that have been to the...
  45. Replies
    32
    Views
    2,626

    I have an rthb I replaced 3-4 weeks ago. Started...

    I have an rthb I replaced 3-4 weeks ago. Started up and this sucker was loud. I mean you could hear it over the other two big time. Brought Trane in and first we were gonna change out the oil...
  46. Replies
    2
    Views
    662

    I have an xrv with a blown up drive right now....

    I have an xrv with a blown up drive right now. Started with two boards gone, brought power up to let oil warm up, and boom, let all the magical smoke out. Carrier Houston has only lost a couple of...
  47. Replies
    12
    Views
    3,922

    Make sure all changes that have been are for this...

    Make sure all changes that have been are for this machine. York has several different types of boards made buy different people on there optiview. Although same machine, just different manufacturers...
  48. Replies
    6
    Views
    1,016

    Check your auxillaries on contactors.

    Check your auxillaries on contactors.
  49. Replies
    17
    Views
    1,426

    Maybe he needs to buy a hoosker doo and get the...

    Maybe he needs to buy a hoosker doo and get the psio reconfigured to cure the "swishing" noise. I'll bet you'll be back to cooling in no time.
  50. Replies
    17
    Views
    1,426

    Sounds like the flux capacitor is unbalanced.

    Sounds like the flux capacitor is unbalanced.